FAN MOTOR CONTROL

 

 
In the electric panel there is an outlet for fan motor (MV) control.  
If the applied electric load is lower than that shown in the table set forth hereunder, such outlet can be 
used directly; otherwise it can be used to operate a relay and/or contactor. 

 

Fan motor power -  table: 

TYPE 

 

1-2-3-7-8-9 

4-10 

5-11 

6-12 

Power 

kW 

0,5 

0,75 

1,1 

1,5 

 
A paper version of the wiring diagram is included in the appliance. It is an integral part of these instructions 
and we recommend keeping it carefully. 

 
 

 

CHECKS

 

 
In order to ensure that the machine works properly, some basic parameters should be checked. Activate the 
machine and: 
 

 

Check that the ventilation unit starts after max. 30 s from the burner activation. 

 
While the warm air heater is normally working (after approx. 20 minutes of uninterrupted working), perform 
the following operations: 
 

 

Measure the air flow, as it is crucial to get an optimal room heating and furthermore is necessary in 

order to adequately cool the heat exchanger. The absence of any kind of resistance on the air flow 
generated by the fan is essential. Therefore, avoid any obstacles hindering air supply and return. 

 

Check that there is no fuel leakage. 

 

Check that the fuel flow is correct by reading the meter. 

 

Check the combustion parameters. 

 

Check that the installed safety devices do not operate anomalously. 

 

On the remote control panel, lower the set-point to a value lower than the room temperature and 

check that 

only the burner

 turns off and that the fan unit does not simultaneously stop. 

 

Check that the fan works for 3 minutes after the burner has stopped, before stopping as well. 

 

Check  that  the  thermal  gradient  is  equal  to  the  one  specified  in  the TECHNICAL  DATA  paragraph. 

The thermal gradient is the difference between the air outlet and air inlet temperature. Since the air 
outlet  temperature  is  not  constant  through  its  outlet  section,  in  order  to  get  this  value,  several 
temperature  measurements  have  to  be  carried  out  (throughout  its  outlet  sections)  and  then  the 
arithmetical mean has to be calculated. 

 

Check  that  the  air  pressure  gauge  of  the  burner  is  correctly  calibrated,  so  that  it  stops  if  the 

comburent air is not enough - since this might cause a non hygienic combustion     

 

All  the  checks  above  mentioned  should  be  performed  in  all  the  arranged  working 
conditions (max and min).

 

 
 

Содержание SR-UT 106

Страница 1: ...HERIC BURNER SERIE SR UT SR UT K Manual attached to the USE AND MAINTENANCE INSTRUCTIONS of the UT and UT K series As to what is not expressly mentioned in this manual it is valid what is set forth in...

Страница 2: ...d TRADE NAME TYPE TRADE NAME TYPE SR UT 26 1 SR UT K 26 7 SR UT 36 2 SR UT K 36 8 SR UT 46 3 SR UT K 46 9 SR UT 66 4 SR UT K 66 10 SR UT 86 5 SR UT K 86 11 SR UT 106 6 SR UT K 106 12 5 0 WARRANTY The...

Страница 3: ...is heated increasing its temperature then it can be distributed both directly and through proper channels Trough this heating system the plant costs can be remarkably reduced and a reliable operating...

Страница 4: ...outdoor installation design TYPE 1 7 2 8 3 9 4 10 A mm 460 460 460 460 B mm 460 460 460 460 C mm 840 840 840 D mm 464 464 464 464 E mm 435 515 695 940 F mm 464 464 464 464 G mm 350 460 655 900 H mm 27...

Страница 5: ...GHT Type 5 6 11 12 This drawing represents the outdoor installation design TYPE 5 11 6 12 A mm 460 460 B mm 460 460 C mm 895 895 D mm 464 464 E mm 1300 1540 F mm 464 464 G mm 1260 1500 H mm 27 27 TYPE...

Страница 6: ...s in force generally special authorisations are to be obtained e g town planning architectural fire fighting environmental regulations etc Therefore before installing the appliance it is advisable to...

Страница 7: ...s follow the instructions included in the relevant package 37 0 CONDENSATION CHECK The appliance is designed to be operated with the heating capacity and the air flow rate specified in the Data Sheet...

Страница 8: ...should they be accidentally torn off it will be the last to be detached Have authorized personnel check that the wire sections and the electric plant are adequate for the max absorbed power specified...

Страница 9: ...flow generated by the fan is essential Therefore avoid any obstacles hindering air supply and return Check that there is no fuel leakage Check that the fuel flow is correct by reading the meter Check...

Страница 10: ...ing wipe carefully the surface Do not use sponges with abrasive products or washing powder During the installation the transparent film protecting the pre painted metal sheet shall be removed 50 0 SMO...

Страница 11: ...larly carry out a combustion analysis not least in compliance with the relevant regulations 57 0 HEAT EXCHANGER CLEANING The heat exchanger cleaning inside and outside is to be performed by skilled an...

Страница 12: ...9 tel 0461 53 16 76 fax 0461 51 24 32 www tecnoclimaspa com tecnoclima tecnoclimaspa com Since our Company is constantly committed to improve its products their esthetical features size technical data...

Отзывы: