In case of two part system, install the fork probe on vessel, connect wires/ cable between fork probe 

and controller, refer fig 2 .  

 

4.

 

Maintenance 

 

 

If the material has built up tendency, over a period of time, tines should be cleaned whenever need occurs. 
Ensure that the cable glands and the housing lid are sealed to prevent ingress of moisture. 

 

 

5.

 

Trouble Shooting  

 
 

 

 

 

 
 
 
 
 
 
 

 

 
 
 
 
 
 

 

 
 
 
  
 

 

SL  Problem 

Cause  

Solution 

1.  Switch not working   1.

 

Loose connection or disconnected 
power supply connection 

2.

 

Incorrect power supply 

3.

 

Wrong probe connections in case 
of two part system 

 
4.

 

Forks are not vibrating due to 
bend  

1.

 

Check and tighten connection

 

2.

 

Check and connect correct power 
supply. Ensure correct polarity for 
24 VDC supply 

 

3.

 

Check and make correct connection 
of fork probe and controller.

 

4.

 

Check and install the fork probe 
properly. Ensure forks are not bent. 
Else contact service dept. 

MAN/ VFSL/ REV 00/07‐22