background image

 

 

 

 

 

 

 

 

 

Range

  

     

 

 

 

:

 

0

 

to

 

9999

 

Decimal

 

Position

     

 

:

 

Selectable

  

Accuracy

  

 

 

 

 

:

 

0.25%

 

FSD

 

Display

   

 

 

 

 

:

 

0.5”,

 

4

 

digits,

 

seven

 

segment

 

LED

  

Programming

   

 

 

:

 

Through

 

keypad

 

No

 

of

 

Set

 

Points

  

 

 

:

 

Four

  

Power

 

Supply

    

 

 

:

 

90

270VAC

 

or

 

24VDC

 

±

 

10%

 

Supply

 

to

 

transmitter

   

:

 

24VDC

 

@30mA

 

Input

   

 

    

 

 

:

 

4

20mA

  

Output

   

 

 

 

 

:

 

4

 

Relays

 

x

 

SPDT,

 

5A

 

250VAC

    

Power

  

 

 

 

 

 

:

 

15VA

 

LED

 

Indication

   

    

:

 

Green

Supply,

 

Red

‐ 

Level

 

set

 

point

 

Level

 

LED

 

Status

             

:

 

LED

 

On=

 

Relay

 

On

 

Enclosure

  

 

 

 

 

:

  

1)

 

ABS

 

plastic

 

IP41

 

panel

 

mtg

 

                                                    

Size:

 

96

 

x

 

96

 

x

 

134(D)

 

mm

 

                       

    

     

2)

 

Cast

 

Al.

 

IP65

 

/

 

Exd

 

Gr.

 

IIB

 

wall

 

mtg.

 

                                                    

Size:

 

275

 

(L)

 

x

 

185

 

(W)

 

x

 

175(D)

 

mm

 

Special

 

Feature

   

 

:

 

Retransmission

 

o/p

 

(4

20

 

mA)

 

isolated

 

Amb.

 

Temp

   

 

 

:

 

0

 ‐ 

55

C

 

Humidity

  

 

 

 

:

 

90%

 

Non

condensing

 

 

 

 

 

 

 
 

 
 

 

.

 

 

SL

 

Problem

  

Cause

 

Solution

 

1

 

No

 

Display

  

1.

 

Improper

 

supply

 

or

 

loose

  

  

connection

 

2.

 

Wrong

 

supply

 

polarity

 

in

 

case

  

  

of

 

24VDC

 

3.

 

Fuse

 

blown

    

1.

 

Check

 

supply

 

&

 

tighten

 

loose

 

connection

 

 

2.

 

Connect

 

24

 

VDC

 

with

 

correct

 

polarity

 

3.

 

Check

 

supply

 

is

 

within

 

limit.

 

Replace

   

  

fuse

 

(F1)

 

(500mA

 

for

 

230VAC)

 

2

 

No

 

change

 

in

 

display

 

value.

 

1.

 

No

 

change

 

in

 

signal

 

from

  

  

X'mitter.

 

2.

 

Wrong

 

connection

 

 

1.

 

Problem

 

in

 

transmitter

 

 

2.

 

Check

 

and

  

connect

 

X'mitter

 

with

 

correct

 

polarity

  

3

 

Fluctuation

 

in

 

display

 

value.

 

1.

 

O/P

 

of

 

'X'mitter'

 

is

 

fluctuating

 

2.

 

Turbulence

 

in

 

liquid

 

1.

 

Check

 

&

 

tighten

 

loose

 

connections

 

if

 

any

 

2.

 

Install

 

X'mitter

 

at

 

turbulent

 

free

 

location

 

5

 

Incorrect

 

Relay

 

Operation

 

1.

 

Incorrect

 

Relay

 

Setting

  

1.

 

Recheck

 

and

 

program

 

for

  

  

correct

 

set

 

&

 

reset

 

values

  

6

 

Re

‐ 

transmission

 

current

 

not

 

proper

 

1.

 

Incorrect

 

programming

 

for

 

re

‐ 

  

transmission

 

2.

 

Improper

 

wiring

  

1.

 

Recheck

 

programmed

 

values

 

2.

 

Refer

 

‘Termination

 

&

 

Wiring’

 

for

 

correct

  

  

wiring

  

 

Troubleshooting

  

MAN/TLIC /REV 03/06

19

 

Specifications

 

PUNE TECHTROL PVT. LTD 

S-18, MIDC Bhosari, Pune: 4110026 India 

Ph: +91-20-66342900, 

[email protected]

, www.punetechtrol.com  

Works: J-52/7, MIDC, Bhosari, Pune - 411026. India +91-20-67313600

 

Содержание TLIC

Страница 1: ...e 92 x 92 mm cutout on panel and mount the TLIC from front and secure it in place through fixing clamps Wall Mtd fig 2 Mounting surface should be flat and without vibrations Drill holes at appropriate location Mount TLIC on identified location and secure it on four mounting hole During wiring supply should be kept off for human safety prevention of accidents Connect 230VAC to supply terminal of TL...

Страница 2: ...tus i e LED ON RELAY ON Modes of operation Program Mode In this mode user can program the unit for measuring span bottom offset relay set reset points Run Mode In this mode unit will be ON and reads the level Panel Mounted Programming Key Functions Wall Mounted E 24VDC Supply 24VDC Supply Level Display Alarm LED Indication Keypad Unit Sticker TLIC Panel Front Bezel Function Key to enter in program...

Страница 3: ...position as required 1 6 0 0 1 0 0 0 Level Range Value Edited Level Range L r g B o F 0 1 0 0 0 0 0 0 Bottom Offset Value Edited Bottom Offset F F r S t 4 D o t 0 0 0 0 0 0 8 0 5 Reset value of relay 4 Edited reset value of relay 4 Decimal point position New decimal pt position RUN MODE DISPLAY S E t 4 0 0 0 0 0 8 0 0 Set value of relay 4 F F F Edited set value of relay 4 r S t 1 0 0 0 0 0 1 0 5 R...

Страница 4: ...ion 2 Connect 24 VDC with correct polarity 3 Check supply is within limit Replace fuse F1 500mA for 230VAC 2 No change in display value 1 No change in signal from X mitter 2 Wrong connection 1 Problem in transmitter 2 Check and connect X mitter with correct polarity 3 Fluctuation in display value 1 O P of X mitter is fluctuating 2 Turbulence in liquid 1 Check tighten loose connections if any 2 Ins...

Отзывы: