Technovision 421VS Operating Guide 

Page 5 

CONTROL MODE: 2-line TTL Control 

DIP-switch position 1 and 2 must be 

OFF

. Control lines 

MUST

 be kept low 

to select the video input.   
 

 

INPUT # 

PIN 1 on CONTROL  

PIN 6 on CONTROL 

HIGH (OPEN) 

HIGH (OPEN) 

Pulled LOW to Ground 

HIGH (OPEN) 

HIGH (OPEN) 

Pulled LOW to Ground 

Pulled LOW to Ground 

Pulled LOW to Ground 

Example: To select INPUT #2 you must contact pin 1 to ground (pin 5). 
Releasing it would return the INPUT to #1. 
 

CONTROL MODE: 4-line TTL Control (dry contact closure) 

DIP-Switch position 1 must be 

OFF

 and position 2 must be 

ON

. Input 

control lines can be pulled low (

dry contact closure with pin 5

) momentarily 

to select the input. 
 

INPUT # 

PIN 1 

PIN 6 

PIN 2 

PIN 7 

PULLED 

LOW 

HIGH 

(OPEN) 

HIGH 

(OPEN) 

HIGH 

(OPEN) 

HIGH 

(OPEN) 

PULLED 

LOW 

HIGH 

(OPEN) 

HIGH 

(OPEN) 

HIGH 

(OPEN) 

HIGH 

(OPEN) 

PULLED 

LOW 

HIGH 

(OPEN) 

HIGH 

(OPEN) 

HIGH 

(OPEN) 

HIGH 

(OPEN) 

PULLED 

LOW 

 
Example: To select INPUT2 you can momentarily contact pin 6 to ground 
(pin 5). 

Page 6 

Technovision 421VS Operating Guide 

 

CONTROL MODE: RS232 Control (9600, 8, N, 1) 

• 

You will have to remove the lid on the 421VS and move Function switch 
position 1 to the 

ON

 position for RS232 control. 

• 

The protocol is 9600 baud, no parity, 8 bits, 1 stop. 

• 

The switcher receives data on pin 3 and transmits on pin 8 of the DB9 
male connector on the back of the switcher. Data ground is pin 5. 

• 

On start-up the switcher will transmit "Technovision 421VS". 

• 

A single byte is sent to the switcher to select the input signal. This byte is 
echoed back by the switcher upon receipt of the command. 

 
The protocol of the single byte command to the switcher is as follows: 

• 

Bits 7 to 4 are always 

∅∅

11 (30H) 

• 

Bits 3 and 2 are the switcher address (0 to 3). Default is 

∅∅

 

• 

Bits 1 and 0 are the input select value (I). Value of 

=input 1, 1=input 2, 

2=input 3 and the value of 3=input 4. 

 

Example for a switcher with the address of 

∅∅

 (

DEFAULT

):   

 

Input # 

RS232 character to transmit to the switcher (address 0) 

30H (30H+address

∅∅

 + 

), ASCII "

" , decimal 48 

32H (30H+address

∅∅

 + 1), ASCII "1" , decimal 49 

32H (30H+address

∅∅

 + 2), ASCII "2" , decimal 50 

33H (30H+address

∅∅

 + 2), ASCII "3" , decimal 51 

 
Determining the switcher address: 

Address  

Value to add 

12 

 

Example: To select INPUT#3 on the 421VS with the address of 0 (default), 
you would transmit (30H+0+3) - the character “3” to the 421VS. 

 

Example: To select INPUT#3 on the 421VS with the address of 1, you would 
transmit (30H+4+3)  - the character “7” to the 421VS. 
 
 