POINT TYPE FLAME DETECTOR "ALMAZ" 

www.technotrade.ua

 

                                                                                               Page 21 of 27 

 

APPENDIX F 

 

Definition of area, controlled by FD in guarded premises. 

 

FD is installed on the walls and enclosing structures of buildings, as well as under ceilings 

or floors in premises controlled. 
 
1. FD wall mounting. 
In case of mounting the FD on the wall of guarded premises controlled area is as follows 

(see. Figure F.1): 
 

  

 

Figure F.1 

 

 
 
 
 

POINT TYPE FLAME DETECTOR "ALMAZ" 

www.technotrade.ua

 

                                                                                               Page 22 of 27 

 

In  general,  configuration  of  the  controlled  area  looks  like  an  ellipse,  a  square  value  is 
calculated using the formula (1.1): 
 
                                                  S = 

π

 · a · b,                                                                      (1.1) 

 
where a, b - semi-axis of the ellipse. 
Semi-axis a and b can be obtained from the canonical equation of the ellipse and 

trigonometric ratios sides and angles of triangles, which are cone section view of the FD. 
At small angles of the optical axis of the FD you should be aware that some of the 
controlled area is cut off by a wall where the FD is mounted, thus the controlled area Scon 
= S - S1, where S1 - area, cut off by the wall. 

Because  the  controlled  premises  usually  have  a  rectangular  shape,  the  quality  of 
evaluative value of the area you can use the square inscribed in an ellipse rectangle: 
 

                                       S

P

  =  2  ·  a  ·  b  –  S

1P

,  ,                                                                (1.2) 

 
where S

1P

 – is the cut off the by wall area. 

Scon  and  Sr  values  of  the  area  for  the  FD  "Almaz",  depending  on  the  height  of  FD 

mounting H, the maximum range of flame ignition source Lmax, the angle of inclination of 
the  optical  axis 

σ

  and  the  viewing  angle  of  FD 

Δ

,  and  the  distance  from  the  wall  to  the 

center  of  the  ellipse  x  and  the  half  the  length  of  the  cutting  y  are  given  in  table  F.1. 
Calculation and optimization of these values in the criteria of maximum protected area are 

performed using software mathematical provisions on PC. 

 

1.1. FD "Almaz" 

Δ

 = 90 °, Lmax = 50 m.  

FD "Almaz" is usually selected to mount at a sufficiently great height. The  most optimal 
angle of the FD - 

σ

 = 30 °. When installation height is up to 7 m you can increase the angle 

by (5 

÷

 10) degrees. This will increase the protected area in 1,5 

÷

 2 times. 

 

Table F.1 (

σ

 = 30 °) 

 

 

 
 

 
 
 

 
 

Содержание ALMAZ

Страница 1: ...ATIONS 4 4 PRODUCT SET CONTENTS 5 5 DEVICE AND ITS OPERATION PRINCIPLE 6 6 SAFETY REQUIREMENTS 7 7 INSTALLATION AND MOUNTING 8 8 TECHNICAL MAINTENANCE 10 9 POSSIBLE MALFUNCTIONS AND TROUBLESHOOTING 12 10 HANDLING AND STORAGE 13 11 CERTIFICATE OF ACCEPTANCE 14 12 MANUFACTURER WARRANTY 14 APPENDIX A 15 APPENDIX B 17 APPENDIX C 18 APPENDIX D 19 APPENDIX E 20 APPENDIX F 21 APPENDIX G 26 APPENDIX H 27 ...

Страница 2: ...R ALMAZ www technotrade ua Page 4 of 27 3 TECHNICAL SPECIFICATIONS Sensitivity and inertia of operation 3 1 The sensitivity of the FD meets the intensity of ultraviolet radiation caused by fire of normalized test fire source of methane gas burner B1 and n heptane flame C1 under the DSTU EN54 10 mounted on the optical axis of the sensor of FD at a distance of 25 m corresponding to class 1 according...

Страница 3: ...5 case 1 rotary device 2 5 2 2 Base of FD 4 is inextricably connected to the FD unit 5 and rotary device 2 The fire alarm system wires are connected to the FD through the cable input on the base Connection is made to the lower PCB connector of FD unit see Appendix B On the front surface of the FD unit there is a sensitive element UV detector 6 and 7 LED operation indicator Inside the FD unit there...

Страница 4: ... the FD to DC power supply with an output voltage 10 30 V and with load current at least 50 mA The contact FD plug positive contact and the contact negative contact of power supply 7 5 2 Switch on the power supply and check for at least 5 minutes if FD is not auto triggered 7 5 3 Light a paraffin candle of 25 mm diameter or portable gas lighter with a flame height 3 4 cm hold it at a distance of n...

Страница 5: ...g the FD operation Failure to comply with this requirement manufacturer is not responsible for the operation 8 1 2 Clean the glass surface of the aperture element of FD from dust and wipe it with a cloth moistened with industrial alcohol on the basis of 3 g of industrial alcohol per 0 04 m2 of rags per 10 FDs Then check the FD operation in the fire alarm system in the following sequence Switch the...

Страница 6: ...ble PSU power supply and check the FD is not triggered 8 2 9 Set the incandescent lamp 100 W x 220V at the distance 4 0 1 m from the FD sensor and connect it to the network Keep the FD the light of the lamp for 5 minutes and check the FD is not triggered 8 2 10 Turn off the power supply Disconnect the FD from scheme The test is finished 8 3 In case of the FD break down please contact the manufactu...

Страница 7: ... must be stored indoor providing protection from moisture solar radiation harmful fumes and mold POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 14 of 27 11 CERTIFICATE OF ACCEPTANCE Point type flame detector Almaz meets the technical conditions of TU 31 6 32251835 001 2010 Point Type Fire Flame Detector Almaz and found fit for use Stamp 12 MANUFACTURER WARRANTY Manufacturer guarantees tha...

Страница 8: ...lmaz General view of the FD Figure A 1 General view of the FD 1 case 2 rotary device 3 cable input 4 base 5 quartz glass 6 UV detector 7 LED operation indicator POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 16 of 27 FD Unit Top view Figure A 2 FD Unit Top view Bottom view Figure А 3 Bottom view ...

Страница 9: ... 3 connected in parallel Pins 2 4 connected in parallel POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 18 of 27 APPENDIX C Example circuit connection of FD Almaz to two wire fire alarm system Рисунок С 1 Figure C 1 NOTES 1 FD base pin assignment pin 1 wire connection pin 2 wire connection pin 3 wire connection pin 4 wire connection 2 ROK the end element of the alarm system loop which type...

Страница 10: ...given in the user manual of the control panel used ATTENTION It is recommended to use the control panel with the grounded of supply loop POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 20 of 27 APPENDIX E Example of connection circuit of FD Almaz to the four wire fire alarm system normally shorted contacts Figure E 1 NOTES 1 FD base pin assignment pins 1 3 wire connection pins 2 4 wire con...

Страница 11: ... off by a wall where the FD is mounted thus the controlled area Scon S S1 where S1 area cut off by the wall Because the controlled premises usually have a rectangular shape the quality of evaluative value of the area you can use the square inscribed in an ellipse rectangle SP 2 a b S1P 1 2 where S1P is the cut off the by wall area Scon and Sr values of the area for the FD Almaz depending on the he...

Страница 12: ...of mounting the FD on the ceiling the configuration controlled area will look like a circle see Fig F 2 The value of controlled area circle is calculated with the formula 2 1 SCON π Lmax 2 H 2 2 1 where Lmax 2 H 2 R 2 R the radius of circle SCON area value depending on installation height of FD H the maximum range of flame ignition source Lmax and radius R are shown in Table F 2 Figure F 2 ...

Страница 13: ...AME DETECTOR ALMAZ www technotrade ua Page 25 of 27 1 1 FD Almaz Δ 90 Lmax 50 м Тable F 2 POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 26 of 27 APPENDIX G Certificate of compliance with DSTU EN 54 10 2004 ...

Страница 14: ...POINT TYPE FLAME DETECTOR ALMAZ www technotrade ua Page 27 of 27 APPENDIX H Certificate for quality management system ISO 9001 2009 ...

Отзывы: