12. Alarms
12.1. Introduction
Alarm module of
TB
OX
MS
is the gate to the outside world.
An alarm consists in a communication event, not only for sending warning messages but
to establish a connection, like we will see.
Via alarms, you are able to call a SCADA, send SMS or message to Pagers, send e-mail,
send files to a FTP site, dial another
TB
OX
MS
or send a report to a printer.
Alarms can be used also to send historical data on regular base using e-mail or FTP. The
historical data is sent as the attached file of a report, developed using
Report Studio
(see
from ‘Windows’ the group of programs of ‘Techno Trade’).
TView
, the supervisory software can then be used to collect data from a mail box or a FTP
site.
The initiation of alarms in the
TB
OX
MS
relies on the variation of digital or analog Tags.
For example, an intrusion contact or a flow level generates a call.
There are two ways of activating an alarm:
By a condition: an edge on a digital Tag or the value of an analog Tag that passes
below a minimum threshold or above a maximum threshold, with adjustable hysteresis.
By the Ladder diagram: a complex Ladder sequence generates an alarm through a
specific function.
The first option affords a simple and quick way to create alarms (a state change of a
digital Tag or the variation of an analog Tag value to activate the alarm).
The Ladder diagram allows you to create a complex automated alarm condition by using
(for example) priorities or a set of analog or Boolean conditions.
Each new alarm is immediately entered into a 32-alarms queue (adjustable) and
processed, according to its severity level. Alarms are generated one by one.
The alarm queue represents an internal buffer of alarms: if several alarms happen at the
same time or if a communication port is not available when the alarm happens.
The Events stack, gives information about alarms status (Started – Stopped –
Acknowledged).
The
Events stack
is
discussed at chapter 12.7
Содержание TBOX MS
Страница 1: ...A Remote Terminal Unit User s Guide Technical specifications cabling...
Страница 7: ...Version 1 06 7 P P PR R RE E ES S SE E EN N NT T TA A AT T TI I IO O ON N N...
Страница 13: ...Version 1 06 13 H H HA A AR R RD D DW W WA A AR R RE E E...
Страница 24: ...Version 1 06 24...
Страница 38: ...Version 1 06 38...
Страница 116: ...Version 1 06 116...
Страница 119: ...Version 1 06 119 18 2 Power Supplies References MS PS230V MS PSDCN MS PS48VN 230 V 48 24 VDC 48 VDC...
Страница 164: ...Version 1 06 164 Cabling to Current actuator Cabling to Voltage actuator OUT Actuator Feedback OUT 24 V OUT Actuator OUT...
Страница 165: ...Version 1 06 165 18 12 8 x Relay Outputs References MS RELAY 8 relay outputs isolated one by one...
Страница 168: ...Version 1 06 168 18 13 4 x Analog inputs isolated References MS 4AI420 4 analog inputs isolated one by one 4 20 mA...
Страница 177: ...Version 1 06 177...
Страница 178: ...Version 1 06 178 18 17 Serial Ports Reference MS SERIAL 2 x Serial Ports each port RS232 or RS485...
Страница 182: ...Version 1 06 182...
Страница 183: ...Version 1 06 183 A A AP P PP P PE E EN N ND D DI I IX X XE E ES S S...
Страница 187: ...Version 1 06 187...
Страница 191: ...Version 1 06 191...
Страница 192: ...Version 1 06 192...