Menu Functions
32
Function parameter
Function parameters are set values which provide the user with the possibility to adapt the ready (i.e.
with all preset function modules) control unit to the characteristics of his system.
In the module
SOLAR CONTROL
these are parameters such as switch-on/off difference, maximum
limit to the possible sensors. In the module
HEAT.CIRC.CONT
these would be parameters such as
heating characteristic, desired room temperature in the heating and lowering mode and others.
In addition, the function parameters of the time windows in some of the modules allow a time-
controlled enable and blockage of the module or of parts of the module. There are maximum 5 time
programs with each 3 time windows available per function module. Each time program can be as-
signed separately to undefined days.
As the function parameters are an essential integrated part of a function module, they are explained
extensively in the description of the various function modules.
Time programs
They are set up in the same way in almost each function module and thus can be described here in a
general way.
Assumption
: The module
HTG CIRC.CTRL
has already been defined twice as the function (F3 =
HTG CIRC.1, F4 = HTG CIRC.2) with two time programs. We will now define separate time programs
for “HTG CIRC.2” on weekdays and the weekend.
In the menu "
FUNCTIONS
" where we are, scroll to the display:
SOLAR2 PAR?
Remaining text from function 2
3: HTG CIRC.CTRL
HTG CIRC.1 PAR?
4: HTG CIRC.CTRL
HTG CIRC.2 PAR?
◄
And after entering into “HTG CIRC.2”:
DES: HTG CIRC.2
FUNCTION STATUS:
INPUT VARIABLE:
OUTPUT VARIABLE:
MODE: RS
NORMAL
Other text lines by scrolling
ROOM TEMPERATURE:
T.room.ACT: 20.7 °C
T.roomSETBACK: 15 °C
T.room STD: 20 °C
TIME PRG:
◄