TechnipFMC Smith Meter MMRT Скачать руководство пользователя страница 2

2

Bulletin SS09040 Issue/Rev. 0.2 (10/14)

Specifications (continued)

   

 

Minimum High Time:

 20 microseconds 

   

 

 

(times are with a 0 to 5.0 volt swing)

 

   

 

 

Input Impedance: 2K Ω above 5 VDC

    

Voltage Thresholds:

 

   

 

 

Low 0 to 1.2 VDC

 

   

 

 

High 2.0 to 28 VDC

 

   

 

 

Maximum high 28 VDC

Reset Input (Reset Batch Totalizer to Zero)

 

 

Minimum Low Time:

 0.25 to 1.0 second (maintained)

  Required pulse width varies with count speed, scale 

 

  factor, and number of digits displayed

 

Voltage Thresholds:

 

   

Low 0 to 0.4 VDC

 

   

High 2.0 to 28 VDC

Program Enable Input

 

  Connection must be made between terminals 1 and 5

LCD Display

 

Totalizers

 

  

Type:

 Up counters (lead-zero blanking)

 

  

Digits:

 8 

  

Scaler:

 0.0001 to 100.0000 

  

Decimal Point:

 5 positions (programmable)

 

Rate Indicator

 

  

Type:

 1/Tau

 

  

Digits:

 4/5 (calculated, 5 displayed with a fixed 0) 

  

Scaler:

 0.001 to 9999

 

  

Decimal point:

 5 positions (programmable)

 

  

Accuracy:

 ±0.02%

 

Backlight

 

   

10-30 VDC @ 30mA max. (derate operating 

 

   

temperature 1°C/volt above 17 VDC)

 

   

Reverse polarity protected

 

Environment

Ambient Operating Temperature

 

-20°C to 70°C (-4°F to 158°F)

Humidity

 

60% non-condensing

Enclosure

 

UL/CSA/FM/CENELEC

 

FM Standard 3615

 

CSA Standard C22.2 No. 30

 

UL Standard 1203 

CENELEC Standard EN50014, EN50018

 

Class I, Division 1 and 2, Groups B, C and D

 

Class II, Division 1 and 2, Groups E, F, and G, EExd IIC, 
IP66

 

NEMA 4X

 

PA-11 Pulse Repeater

For turbine meter applications requiring a preamplifier, 

 

an optional PA-11 preamplifier can be fitted within the 

 

enclosure. Refer to Bulletin 

SS02019

 for preamplifier 

 

specifications.

Battery Safety

The lithium battery that powers the device contains 

 

inflammable materials such as lithium organic solvent, 

 

and other chemical ingredients. Explosion or fire may 

 

result if the battery is not handled correctly. To avoid 

 

an accident, follow these guidelines:

• 

Do not open enclosure if the area is known to be 

 

hazardous

• 

Do not replace batteries in a hazardous area

• 

Do not stack or jumble up batteries

• 

Do not heat batteries above 95° C

• 

Do not disassemble batteries

• 

Do not recharge lithium batteries

• 

Do not apply pressure to, or deform, batteries

• 

Do not solder batteries

• 

Do not dispose of batteries in fire

•  Insert battery with correct polarity.

Recommended Replacement Batteries

 

  Panasonic P/N: CR 2/3A

 

  Varta P/N: CR 2/3A

 

  Fuji P/N: CR 2/3 8.L

Initial Start-Up

 

In a non-hazardous area, remove the protective battery 

 

insulating tab between the battery and clip to activate 

 

the display.

Содержание Smith Meter MMRT

Страница 1: ...ication The MMRT has the ability to provide a local non resettable totalizer a resettable totalizer and a flow rate indicator on a meter that provides an electronic output The meters that provide a direct electronic output are the Smith Meter PRIME 4 meter the mass meter the turbine meter and the multi viscosity turbine meters This unit can also be used with positive displacement meters that have ...

Страница 2: ...ard 3615 CSA Standard C22 2 No 30 UL Standard 1203 CENELEC Standard EN50014 EN50018 Class I Division 1 and 2 Groups B C and D Class II Division 1 and 2 Groups E F and G EExd IIC IP66 NEMA 4X PA 11 Pulse Repeater For turbine meter applications requiring a preamplifier an optional PA 11 preamplifier can be fitted within the enclosure Refer to Bulletin SS02019 for preamplifier specifications Battery ...

Страница 3: ...on 1 Ground 2 Input B Count input Use with contact closure to ground up to 20Hz count speed 3 Input A Count input Use with current sensing up to 10KHz count speed 4 Reset Connect to ground to reset totalizer 5 Program enable Connect to ground to enter program 6 Backlight common 7 Backlight power Connect to power to light display 8 Rate and Totalizer Toggle Toggles between the Rate Meter and Totali...

Страница 4: ...e Rev 0 2 10 14 Solid State Count Rate Input Current Sinking Sensor Solid State Count Rate Input Magnetic Pickup Contact Closure Input Solid State Count Rate Input Current Sourcing Sensor VDC VDC VDC VDC Backlight Wiring VDC ...

Страница 5: ... 2 10 14 Program Mode Enable Remote Rate Totalizer Toggle Remote Reset VDC Smith Meter Turbine Meter with PA 11 Preamp Common 12 to 30 VDC PA 11 Reluctance Pickup Coil Jumper in Position J2 1 6k Pullup Resistor 1 2 3 4 5 VDC VDC VDC ...

Страница 6: ...rminal 3 a power assist feature of the Courier extends the life of the battery Terminal 2 is the low speed current sinking count input designed to be used with a contact closure to ground It has a maximum count speed of 20 Hz Inputs into this terminal are counted on the negative going edge Terminal 2 is pulled up to 3VDC When a contact closes pulling the voltage down to 4VDC or less one count is r...

Страница 7: ...s are accessible when the cover is off the unit These keys are typically used for setup Press the key on the front panel to toggle between the totalizer and rate meter screens when the cover is removed from the unit Magnetic Totalizer Rate Select Switch Magnetic Reset Switch Mounting Screw Press the key to reset the totalizer display to zero This button has no effect on the rate meter screen The f...

Страница 8: ...reamp produces 15 8 pulses per liter Calculate the count scaler required to indicate the number of liters of product that has passed through the meter XXXX XX Select the XXXX XX position on the totalizer decimal point menu CS DPF PPI CS 0 02000 1 50 CS 6 3291 100 15 8 Programming Count Scale Factor The first screen in the program mode is used to enter the count scale factor The far right digit wil...

Страница 9: ...Display rate in whole gallons per minute XXXX Example 2 A flow sensor produces 15 800 pulses per cubic meter Display flow rate in tenths of liters per hour RS for R x 10 Sec x DPF PPI x 10 RS 1 200 60 X 1 50 RS 2 278 3600 x 10 15 800 Programming Rate Scale Factor The third program mode screen allows you to enter the rate scale factor The lower case d appears on the right of the display when it is ...

Страница 10: ... the rear panel is still active when the front reset button is disabled To exit the program mode break the connection between terminals 1 and 5 The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in effect Otherwise the manufacturer assumes no responsibility for the use o...