Technibel GR9FI65R5IAA Скачать руководство пользователя страница 2

0.8180.531.00     05/2007

IMPORTANT!
Please read before installation

This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important  to install or
service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical  codes.
• Pay close attention to all warning and caution notices given in

this manual.

•The unit must be supplied with a dedicated electrical line.

This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.

If necessary, get help

These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.

In case of improper installation

The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system and

then the wiring one; proceed in the reverse orden when removing
the units.

When wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing are

completed or reconnected and checked, to ensure the grounding.

• Highly dangerous electrical voltages are used in this system.

Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause

accidental injury and death

.

Ground the unit 

following local electrical codes.

• The Yellow/Green wire cannot be used for any connection

different from the ground connection.

• Connect all wiring tightly. Loose wiring may cause overheating

at connection points and a possible fire hazard.

• Do not allow wiring to touch the refrigerant tubing, compressor,

or any moving parts of the fan.

• Do not use multi-core cable when wiring the power supply and

control lines. Use separate cables for each type of line.

When transporting

Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.

When installing...
... In a ceiling or wall

Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.

... In a room

Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls
and floors.

... In moist or uneven locations

Use a raised concrete base to provide a solid level foundation for
the outdoor unit.
This prevents damage and abnormal vibrations.

... In area with strong winds

Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)

Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.

When connecting refrigerant tubing

• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare

and union tubes before connecting them;  screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.

• Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.

When servicing

• Turn the power OFF at the main power board  before opening

the unit to check or repair electrical parts and wiring.

• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no

metal scraps or bits of wiring have been left inside the unit being
serviced.

• Ventilate the room during the installation or testng the refrigeration

system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.

WARNING

CAUTION

WARNING

2

Содержание GR9FI65R5IAA

Страница 1: ...TECHNICAL DATA SERVICE MANUAL OUTDOOR UNIT GR9FI65R5IAA TRIAL SPLIT SYSTEM AIR CONDITIONER Model No Product Code No GR9FI65R5IAA 38 7107 102 0 8180 611 01 06 2011...

Страница 2: ...t allow wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of...

Страница 3: ...ant Flow Diagram 9 4 2 Dual Split System Refrigerant Flow Diagram 10 4 3 Mono Split System Refrigerant Flow Diagram 11 5 PERFORMANCE DATA 12 5 1 Performance Charts 12 6 ELECTRICAL DATA 13 6 1 Electric...

Страница 4: ...Outdoor Air Intake Temp Cooling Maximum 32 C D B 23 C W B 43 C D B Minimum 10 C D B 6 C W B 15 C D B 24 C D B 18 C W B Minimum 5 C D B 15 C D B GR9FI65R5IAA Heating Maximum 27 C D B Temperature Indoor...

Страница 5: ...mensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Ra...

Страница 6: ...model Q ty No Of poles rpm Nominal output W Coil resistance Ambient temp 25 C Safety devices Type Operating temp Open C Close C Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA...

Страница 7: ...sistance k Thermistor narrow tube B sensor Resistance k Thermistor wide tube C sensor Resistance k Thermistor narrow tube C sensor Resistance k Crank case heater Resistance at 20 C Base heater Resista...

Страница 8: ...3 DIMENSIONAL DATA GR9FI65R5IAA dimension mm SERVICE VALVE TUBE 2x 6 35 1 4 NARROW TUBE 3x 6 35 1 4 4 12 for anchor bolt WIDE TUBE 2x 9 52 3 8 1x 12 7 1 2 8...

Страница 9: ...xpansion valve is used in the outdoor unit both the wide and narrow tubes of this air conditioner become cold To prevent heat loss and wet floors due to dripping of condensation both tubes must be wel...

Страница 10: ...ed in the outdoor unit both the wide and narrow tubes of this air conditioner become cold To prevent heat loss and wet floors due to dripping of condensation both tubes must be well insulated with a p...

Страница 11: ...utdoor unit both the wide and narrow tubes of this air conditioner become cold To prevent heat loss and wet floors due to dripping of condensation both tubes must be well insulated with a proper insul...

Страница 12: ...0 1 20 10 15 20 25 30 35 40 Outdoor inlet air D B temperature C Low pressure at wide tube service valve MPa 1 5 1 7 1 9 2 1 2 3 2 5 2 7 2 9 0 5 10 15 20 Outdoor inlet air D B temperature C High pressu...

Страница 13: ...W B HEATING 3 Indoor Unit Performance at Rating conditions Running Amps A 0 66 7 5 Power input kW 0 148 1 690 Rating Conditions Indoor Air Temperature 20 C D B Outdoor Air Temperature 7 C D B 6 C W B...

Страница 14: ...6 2 Electric Wiring Diagram GR9FI65R5IAA 14...

Страница 15: ...unit GR9FI65R5IAA Indoor unit MPA9FIB0R5I x1 MTAFIA0R5I x2 6 4 Dual Split System Wiring Diagram Outdoor unit GR9FI65R5IAA Indoor unit MPA9FIB0R5I MTAFIA0R5I 6 5 Mono Split System Wiring Diagram Outdoo...

Страница 16: ...r F F F F F automatically restart after 3 min 1 fault on outdoor unit O O F O O during this time the signalling is showed 0 wrong mode selected F F O system does not operate to restart the system sele...

Страница 17: ...R D 28 Reyrieux BP 131 01601 Tr voux CEDEX France T l 04 74 00 92 92 Fax 04 74 00 42 00 R C S Bourg en Bresse B 759 200 728...