2. SPECIFICATIONS
2-1. Unit Specifications
2
Indoor Unit MCAV127C5VAB KPAV128C5TAA
Outdoor Unit GRV247M2C5TAA
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature 27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.
Power Source
220 / 230 / 240 V Single phase 50 Hz
Cooling
Max.Capacity
kW
6.85
(230V)
BTU/h
23,400
No. of indoor unit
1 – Unit
2 – Units
Capacity
kW
3.50 / 3.55 / 3.60
6.80 / 6.85 / 6.90
BTU/h
11,950 / 12,100 / 12,300
23,200 / 23,400 / 23,500
Available voltage range
V
198 to 264
Running amperes
A
5.9 / 6.0 / 6.1
11.9 / 12.0 / 12.1
Power input
W
1,260 / 1,300 / 1,350
2,510 / 2,570 / 2,620
Power factor
%
97 / 94 / 92
96 / 93 / 90
C.O.P.
W/W
2.8 / 2.7 / 2.7
2.7 / 2.7 / 2.6
Compressor locked rotor amperes
A
33 / 33 / 33
66 / 66 / 66
Fan speeds
Auto (Hi, Lo)
Compressor
Rotary (Hermetic)
Refrigerant / Amount charged at shipment
g
R22 / 2,480 (1,240 x 2)
Refrigerant control
Capillary tube
Operation sound
dB-A
53.0
Refrigerant tubing connections
Flare type
Max. allowable tubing length at shipment
m
7.5
Refrigerant tube
Narrow tube
mm (in.)
6.35 (1/4)
diameter
Wide tube
mm (in.)
12.7 (1/2)
Refrigerant tube kit
Optional
Unit dimensions
Package dimensions
Height
mm
835
913
Width
mm
850
1,000
Depth
mm
305
400
Net weight
kg
67.5
Shipping weight
kg
76.5
Shipping volume
m
3
0.365
Electrical Rating
Features
Dimensions & Weight
Performance