– 21 –
Indoor Unit :CA250X5TAA Outdoor Unit : GR250X7TAA
TC : Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CI : Compressor Input (kW)
Rating conditions are
:Outdoor Ambient Temp. 35
°
C DB
:Indoor Unit Entering Air Temp. 27
°
C DB / 19
°
C WB
RATING CAPACITY : 7.3 kW AIR FLOW RATE : 1140 m
3
/h
EVAPORATOR CONDENSER
ENT. TEMP.
°
C AMBIENT TEMP. C
WB DB 25 30 35 40 45 50
TC 7.37 7.03 6.67 6.26 5.81 5.34
CI 2.32 2.48 2.66 2.92 3.19 3.45
21 SHC 4.9 4.7 4.5 4.3 4.1 3.8
23 SHC 5.4 5.2 5 4.8 4.6 4.4
15 25 SHC 6 5.8 5.6 5.4 5.2 4.9
27 SHC 6.5 6.3 6.2 5.9 5.7 5.34
29 SHC 7.1 6.9 6.67 6.26 5.81 5.34
31 SHC 7.37 7.03 6.67 6.26 5.81 5.34
TC 7.61 7.31 6.96 6.59 6.18 5.75
CI 2.38 2.55 2.74 3 3.27 3.53
21 SHC 4.1 4 3.8 3.7 3.5 3.3
23 SHC 4.7 4.6 4.4 4.2 4 3.8
17 25 SHC 5.3 5.1 4.9 4.8 4.6 4.4
27 SHC 5.8 5.7 5.5 5.3 5.1 4.9
29 SHC 6.4 6.2 6.1 5.9 5.7 5.5
31 SHC 6.9 6.8 6.6 6.4 6.18 5.75
TC 7.88 7.6 #7.3 6.94 6.54 6.1
CI 2.45 2.63 2.82 3.09 3.36 3.63
21 SHC 3.4 3.3 3.2 3 2.8 2.7
23 SHC 4 3.9 3.7 3.6 3.4 3.2
19 25 SHC 4.6 4.4 4.3 4.1 4 3.8
27 SHC 5.1 5 4.9 4.7 4.5 4.3
29 SHC 5.7 5.5 5.4 5.3 5.1 4.9
31 SHC 6.2 6.1 6 5.8 5.6 5.4
TC 8.14 7.85 7.56 7.21 6.86 6.46
CI 2.52 2.7 2.9 3.18 3.45 3.73
23 SHC 3.3 3.2 3 2.9 2.8 2.6
21 25 SHC 3.8 3.7 3.6 3.5 3.3 3.2
27 SHC 4.4 4.3 4.2 4 3.9 3.7
29 SHC 5 4.8 4.7 4.6 4.4 4.3
31 SHC 5.5 5.4 5.3 5.1 5 4.8
TC 8.42 8.17 7.88 7.59 7.24 6.88
CI 2.59 2.77 2.98 3.26 3.54 3.82
23 25 SHC 3.1 3 2.9 2.8 2.7 2.6
27 SHC 3.7 3.6 3.5 3.4 3.2 3.1
29 SHC 4.2 4.2 4 3.9 3.8 3.7
31 SHC 4.8 4.7 4.6 4.5 4.4 4.2
TC 8.76 8.45 8.2 7.91 7.61 7.27
CI 2.67 2.86 3.03 3.34 3.64 3.93
25 27 SHC 3 2.9 2.8 2.7 2.6 2.5
29 SHC 3.6 3.4 3.4 3.3 3.2 3
31 SHC 4.1 4 3.9 3.8 3.7 3.6
1. SPECIFICATIONS
1-7
Cooling Capacity