6. TROUBLESHOOTING

Precautions before performing inspection or repair

NOTE

PROCEDURE

After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair.

High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge 
(charging voltage DC 280 V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be
careful not to touch any electrified parts before the controller LED (red) turns OFF.

If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow at 
least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller.

  After inspection or repair is completed, be sure to move the operation switch to the DEMO position, turn the power ON, and 

erase the diagnostics contents.

1: If the operation lamp flashes every 0.5 seconds immediately when the power is turned ON,

there is an external ROM (OTP data) failure on the indoor circuit board or a board insertion 
problem, or the board has not been installed.

2: The failure mode is stored in memory even when the power is not ON. Follow the procedure 

below to perform diagnostics.

Operation switch

Ordinarily, be sure 
this is always set to 
NORMAL.

The DEMO position is 
used for inspections 
and similar 
maintenance.

Operation selector

Ordinarily, be sure this is always set to ON.

The OFF and TEST positions are used for 
inspections and similar maintenance.

1

Turn the power switch ON.

2

Move the operation selector on the remote control receiver to OFF (self-diagnostics).

3

If there is a sensor failure or a protective function has activated, self-diagnostics lamps 1, 2, and 3 will illuminate in the 
following pattern: 5 seconds flashing (illuminated) + 2 seconds OFF. (Buzzer sounds once while lamps are OFF.)

Note: If there is no trouble, then self-diagnostics lamps 1, 2, and 3 do not illuminate, and the buzzer does not sound.

4

Diagnostics is completed when the buzzer sounds 3 beeps.

5

  After inspection or repair is completed, be sure to move the operation switch on the indoor unit main body to the DEMO

position, turn the power ON, and erase the diagnostics contents. Then move the operation selector on the remote control 
receiver to the OFF position and check that the diagnostics contents have been erased before using the unit.

Method of self-diagnostics

If the indoor unit operation lamp is flashing every 0.5 seconds, follow the 
procedure below to perform detailed trouble diagnostics.

<Indoor unit main body>

TEST

OFF

ON

TEST

OFF

ON

TIMER OPERATION

Operation selector

Ordinarily, be sure this is always set to ON.
The OFF and TEST positions are used for
inspections and similar maintenance.

17

Содержание 387105945

Страница 1: ...ICE MANUAL INDOOR UNIT KAF94MR5IA KPAF124MR5IA SPLIT SYSTEM AIR CONDITIONER KAF94MR5IA Ceiling Mounted KPAF124MR5IA Floor Mounted Model No Product Code No KAF94MR5IA 387105947 0 8180 390 1 09 2006 387...

Страница 2: ...ing to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When...

Страница 3: ...TA 11 3 1 Air Throw Distance Chart 11 4 ELECTRICAL DATA 13 4 1 Electric Wiring Diagrams 13 5 FUNCTION 14 5 1 Operation Functions 14 5 2 Protective Functions 16 6 TROUBLESHOOTING 17 7 CHECKING ELECTRIC...

Страница 4: ...in Refrigerant Refrigerant tube kit Air clean filter Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping vol...

Страница 5: ...t tube kit Air clean filter Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CH...

Страница 6: ...t W Coil resistance Ambient temp 25 C Safety devices Type Operating temp Open C Close Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m DATA SUBJECT TO CHANGE WITHOUT NOTICE 1 4 45...

Страница 7: ...Close Run capacitor F VAC Flap Motor Type Model Rating Coil resistance Ambient temp 25 C Heat Exch Coil Coil Rows Fin pitch mm Face area m2 DATA SUBJECT TO CHANGE WITHOUT NOTICE 0 29 65 CB FtMRV123EH...

Страница 8: ...H 31 0 DTN C502H3T TKS128B 25 C 5 0 3 0 C 188 0 4 ATR I55 AC 230 V 50 60 Hz 13 7 V 0 4 A 5 48 VA DTN C583G3U TKS121B Primary WHT WHT 307 10 Secondary BRN BRN 1 8 10 150 C 0 0 10 20 30 40 50 60 70 80 9...

Страница 9: ...2 DIMENSIONAL DATA KAF94MR5IA Unit mm 700 200 560 9...

Страница 10: ...KPAF124MR5IA Unit mm Unit mm 9 52 3 8 10...

Страница 11: ...r mounted Cooling 0 1 2 3 4 5 6 7 3 2 1 0 Horizontal distance m Axis air velocity m s Vertical distance m 0 1 2 3 4 5 6 7 3 2 1 0 Horizontal distance m Axis air velocity m s Vertical distance m Room a...

Страница 12: ...1 0 2 3 Horizontal distance m Axis air velocity m s Vertical distance m Axis air velocity Flap angle 45 30 Ceiling mounted 0 1 2 3 4 5 6 7 1 0 2 3 Horizontal distance m Axis air velocity m s Vertical...

Страница 13: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams KAF94MR5IA KPAF124MR5IA 13...

Страница 14: ...t low operation speeds and PAM control at high operation speeds making the most effective use of power The compressor operation frequency varies depending on the relative humidity The indoor fan opera...

Страница 15: ...temperature either 60 minutes prior or 30 minutes prior to the set ON timer time and operation is started in advance of the set ON time The indoor fan speed is Medium COOL Indoor temperature Set temp...

Страница 16: ...tops Once the freeze condition is detected the air conditioner will work less than the maximum frequency until it is turned off Approx 53 Normal operation At start of operation A High LL Stopped A B C...

Страница 17: ...y be sure this is always set to NORMAL The DEMO position is used for inspections and similar maintenance Operation selector Ordinarily be sure this is always set to ON The OFF and TEST positions are u...

Страница 18: ...ostics contents Control 1 Control 2 Initial self Short circuit terminals 2 and 4 on Short circuit terminals 2 and 3 on Probable location of malfunction diagnostics the indoor unit terminal plate the o...

Страница 19: ...MO and start operation using the remote controller If there are no problems with the above then check the outdoor unit 1 The rated voltage must be present between inter unit cables 1 and 2 Connect a 5...

Страница 20: ...tance from the noise source 1 Use shielded wires 2 Move unit away from the noise source Trouble Either of the following trouble may occur 1 The unit may stop suddenly during operation 2 Indicator lamp...

Страница 21: ...measure the resistance by placing a probe on each terminal screw on the terminal plate Fig 2 Note that the ground line terminal should be skipped for the check 7 1 4 Measurement of Insulation Resista...

Страница 22: ...then place a probe on the capacitor terminals as shown in Fig 7 Observe the deflection of the pointer setting the resistance measuring range of the multimeter to the maximum value The capacitor is go...

Страница 23: ...R D 28 Reyrieux BP 131 01601 Tr voux CEDEX France T l 04 74 00 92 92 Fax 04 74 00 42 00...

Отзывы: