-3. Some part of air conditioner does not operate.
5
-3-1. Only indoor fan does not run.
5
-3-2. Only flap motor does not run.
5
-3-3. Only outdoor fan does not run.
Fan cannot
be turned.
OK
• Check fan rotation.
Turn fan gently once or twice by
hand.
• Check fan casing
foreign matter on
inside.
Fan motor burnout
or foreign matter in
bearings.
Remove foreign
matter or repair.
Repair or replace.
• Measure resistance of outdoor fan
motor winding.
• Check fan motor capacitor.
• Measure resistance of flap motor
winding.
Fan cannot
be turned.
OK
• Check fan rotation.
Turn fan gently once or twice by
hand.
• Check fan casing
foreign matter on
inside.
Fan motor burnout
or foreign matter in
bearings.
Remove foreign
matter or repair.
Repair or replace.
• Measure resistance of indoor fan
motor winding.
• Check fan motor capacitor.
PCB assy is defective.
OK
5-3-2
27
Содержание 387005960
Страница 11: ...2 DIMENSIONAL DATA Unit mm Unit mm 11...
Страница 12: ...3 ELECTRICAL DATA 3 1 Electric Wiring Diagrams KPAF124R5 KPAF185R5 KPAF225R5 12...
Страница 13: ...4 1 Cool Mode Operation 4 FUNCTION 13...
Страница 14: ...4 2 Heat Mode Operation 14...
Страница 15: ...4 3 Auto Cool Heat Mode Operation 15...
Страница 16: ...4 4 Dry Mode Operation 16...
Страница 18: ...2 Outdoor Coil High Pressure Protection 18...
Страница 19: ...4 7 Protection Operations in Heat Mode 1 Outdoor Coil Deice Protection 19...
Страница 20: ...20...
Страница 21: ...2 Indoor Coil High Pressure Protection in Heat Mode 21...
Страница 22: ...4 8 Sleep Function 4 9 Daily Timer Function 4 10 IFEEL Function 22...