1-4 Indoor Fan Performance

If external static pressure is too great (due to long extension of ducts, foe example), the air flow volume may drop too low at
each air outlet. This problem may be solved by increasing the fan speed using the following procedure:

(1)

Remove the screw on the electrical component box
and remove the cover plate.

(2)

Disconnect the fan motor sockets in the box.

(3)

Take out the booster cable (sockets at both ends)
clamped in the box.

(4)

Securely connect the booster cable sockets between
the disconnected fan motor sockets in step 2
as shown in the Fig. 1-1

(5)

Place the cable neatly in the box and reinstall the cover plate.

Fig. 1-1

HH:

Using the booster cable

H:

At shipment

How to read the diagram

The vertical axis is the external static pressure (Pa) while the orizzontal one is the AIR FLOW RATE (m3/h).
The characteristic curves for HH, H, M and L fan speed are shown. The nameplate values shown are based on the
H air flow rate. For the type 7/9/12 flow rate is 600 m3/h while the external static pressure is 49 Pa at H position.
If external static pressure is too great (due, for example, to long duct extension), the air flow rate may drop too
much at each air outlet. This problem can be solved increasing the fan speed with the booster cable.

NOTE

12000

16/18000

EXT

ERNAL

 ST

AT

IC

 PRESSURE (mmW

.G

.)

m3/h

m3/h

EXT

ERNAL

 ST

AT

IC

 PRESSURE (mmW

.G

.)

9

Содержание 38.7130.072

Страница 1: ...TECHNICAL DATA SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER DSAFP165R5I 38 7130 073 0 8180 455 1 October 2005 DSAFP185R5I Model No Product Code No DSAFP125R5I 38 7130 072 38 7130 074...

Страница 2: ...w wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line...

Страница 3: ...CB service pack 19 5 4 Table of setting 21 6 SERVICE PROCEDURE 22 6 1 Meaning of alarm message 22 6 2 Led indicator messages on outdoor control PCB 23 6 3 Symptoms and parts to inspect 24 6 4 Details...

Страница 4: ...rigerant Refrigerant control Dimensions Weight Dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Volume m3 Weight Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT...

Страница 5: ...nt control Dimensions Weight Dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Volume m3 Weight Net kg Shipping kg DATA SUBJECT TO CHANGE WITHOUT NOTICE Power noise...

Страница 6: ...p 20 C BLU BRN 95 BRN BLK 37 BLK GRY 15 GRY VLT 15 WLT RED 30 RED YEL 101 Safety devices Type Operating temp Open C Close C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA...

Страница 7: ...68 BRN BLK 9 BLK GRY 36 GRY VLT 18 VLT RED 18 BRN YEL 105 Safety devices Type Operating temp Open C Close C Run capacitor F VAC Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJECT TO CHAN...

Страница 8: ...r E1 E2 Resistance k Thermistor Room sensor TA Resistance k Drain pump Model Rating Voltage Input Flow rate Safety float switch Model Contact rating 0 4 l min BI 1300 2725 230V AC DC 0 5A PC 309564003...

Страница 9: ...Place the cable neatly in the box and reinstall the cover plate Fig 1 1 HH Using the booster cable H At shipment How to read the diagram The vertical axis is the external static pressure Pa while the...

Страница 10: ...2 DIMENSIONAL DATA DSAFP125R5I 10...

Страница 11: ...DSAFP165 185R5I 11...

Страница 12: ...3 ELECTRICAL DATA 3 1 Electric Wiring Diagram 7P terminal board 1 L 2 N U1 U2 R1 R2 wiring remote controller power supply inter unit control 12...

Страница 13: ...he unit to be operated by the remote controller even if it is not CN072 connected to an outdoor unit In this case alarm E04 which indicates trouble in the serial communication between the indoor and o...

Страница 14: ...4 PROCESS AND FUNCTIONS 4 1 control functions 14...

Страница 15: ...15...

Страница 16: ...16...

Страница 17: ...Read Only Memory EEPROM is a component in which the various information necessary for functionning can be electronically written or erased This component holds informations that is essential for the r...

Страница 18: ...5 2 How to replace PCB 18...

Страница 19: ...5 3 How to replace EEPROM with EEPROM included in PCB service pack 19...

Страница 20: ...20...

Страница 21: ...5 4 Table of settings 21...

Страница 22: ...6 SERVICE PROCEDURE 6 1 Meaning of alarm message 22...

Страница 23: ...6 2 Led indicator messages on outdoor control PCB 23...

Страница 24: ...6 3 Symtoms and parts to inspect 24...

Страница 25: ...6 4 Details of alarm messages resistance 25...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...28...

Страница 29: ...7 OUTDOOR UNIT MAINTENANCE REMOTE CONTROL 29...

Страница 30: ...30...

Страница 31: ...31...

Страница 32: ...32...

Страница 33: ...33...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...36...

Страница 37: ...R D 28 Reyrieux BP 131 01601 Tr voux CEDEX France T l 04 74 00 92 92 Fax 04 74 00 42 00 R C S Bourg en Bresse B 759 200 728...

Отзывы: