1-4 Indoor Fan Performance
If external static pressure is too great (due to long extension of ducts, foe example), the air flow volume may drop too low at
each air outlet. This problem may be solved by increasing the fan speed using the following procedure:
(1)
Remove the screw on the electrical component box
and remove the cover plate.
(2)
Disconnect the fan motor sockets in the box.
(3)
Take out the booster cable (sockets at both ends)
clamped in the box.
(4)
Securely connect the booster cable sockets between
the disconnected fan motor sockets in step 2
as shown in the Fig. 1-1
(5)
Place the cable neatly in the box and reinstall the cover plate.
Fig. 1-1
HH:
Using the booster cable
H:
At shipment
How to read the diagram
The vertical axis is the external static pressure (Pa) while the orizzontal one is the AIR FLOW RATE (m3/h).
The characteristic curves for HH, H, M and L fan speed are shown. The nameplate values shown are based on the
H air flow rate. For the type 7/9/12 flow rate is 600 m3/h while the external static pressure is 49 Pa at H position.
If external static pressure is too great (due, for example, to long duct extension), the air flow rate may drop too
much at each air outlet. This problem can be solved increasing the fan speed with the booster cable.
NOTE
12000
16/18000
EXT
ERNAL
ST
AT
IC
PRESSURE (mmW
.G
.)
m3/h
m3/h
EXT
ERNAL
ST
AT
IC
PRESSURE (mmW
.G
.)
9
Содержание 38.7130.072
Страница 10: ...2 DIMENSIONAL DATA DSAFP125R5I 10...
Страница 11: ...DSAFP165 185R5I 11...
Страница 14: ...4 PROCESS AND FUNCTIONS 4 1 control functions 14...
Страница 15: ...15...
Страница 16: ...16...
Страница 18: ...5 2 How to replace PCB 18...
Страница 19: ...5 3 How to replace EEPROM with EEPROM included in PCB service pack 19...
Страница 20: ...20...
Страница 21: ...5 4 Table of settings 21...
Страница 22: ...6 SERVICE PROCEDURE 6 1 Meaning of alarm message 22...
Страница 23: ...6 2 Led indicator messages on outdoor control PCB 23...
Страница 24: ...6 3 Symtoms and parts to inspect 24...
Страница 25: ...6 4 Details of alarm messages resistance 25...
Страница 26: ...26...
Страница 27: ...27...
Страница 28: ...28...
Страница 29: ...7 OUTDOOR UNIT MAINTENANCE REMOTE CONTROL 29...
Страница 30: ...30...
Страница 31: ...31...
Страница 32: ...32...
Страница 33: ...33...
Страница 34: ...34...
Страница 35: ...35...
Страница 36: ...36...