IMPORTANT!
Please read before installation

This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important  to install or
service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:

• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical  codes.
• Pay close attention to all warning and caution notices given in

this manual.

•The unit must be supplied with a dedicated electrical line.

This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.

If necessary, get help

These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.

In case of improper installation

The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system and

then the wiring one; proceed in the reverse orden when removing
the units.

When wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing are

completed or reconnected and checked, to ensure the grounding.

• Highly dangerous electrical voltages are used in this system.

Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause

accidental injury and death

.

Ground the unit 

following local electrical codes.

• The Yellow/Green wire cannot be used for any connection

different from the ground connection.

• Connect all wiring tightly. Loose wiring may cause overheating

at connection points and a possible fire hazard.

• Do not allow wiring to touch the refrigerant tubing, compressor,

or any moving parts of the fan.

• Do not use multi-core cable when wiring the power supply and

control lines. Use separate cables for each type of line.

When transporting

Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.

When installing...
... In a ceiling or wall

Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.

... In a room

Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls
and floors.

... In moist or uneven locations

Use a raised concrete base to provide a solid level foundation for
the outdoor unit.
This prevents damage and abnormal vibrations.

... In area with strong winds

Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)

Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.

When connecting refrigerant tubing

• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare

and union tubes before connecting them;  screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.

• Check carefully for leaks before starting the test run.

NOTE:

Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.

When servicing

• Turn the power OFF at the main power board  before opening

the unit to check or repair electrical parts and wiring.

• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no

metal scraps or bits of wiring have been left inside the unit being
serviced.

• Ventilate the room during the installation or testng the refrigeration

system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.

WARNING

CAUTION

WARNING

2

Содержание 38.7107.083

Страница 1: ...TDOOR UNIT GRF188R5TAA GRF228R5TAA GRF228R7TAA GRF188R5TAA GRF228R5TAA GRF228R7TAA 0 8180 537 1 July 2008 b SPLIT SYSTEM AIR CONDITIONER GRF228R7TAA 38 7107 085 GRF228R5TAA 38 7107 084 Model No Product Code No GRF188R5TAA 38 7107 083 ...

Страница 2: ...ot allow wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin alu...

Страница 3: ...her Component specifications 11 3 DIMENSIONAL DATA 12 4 REFRIGERANT FLOW DIAGRAM 13 5 PERFORMANCE DATA 14 5 1 Performance Charts 14 5 2 Cooling Capacity 17 5 3 Heating Capacity 20 6 ELECTRICAL DATA 21 6 1 Electrical characteristics 21 6 2 Electric Wiring Diagram 24 6 3 System Wiring Diagram 24 Table of Contents 3 ...

Страница 4: ... RANGE Temperature Maximum Minimum Indoor Air Intake Temp Cooling Maximum Minimum Heating 8 C D B 9 C W B Outdoor Air Intake Temp 32 C D B 23 C W B 19 C D B 14 C W B 27 C D B 43 C D B 19 C D B 24 C D B 18 C W B 4 ...

Страница 5: ... tube diameter Wide tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 24 C W B Heating Indoor air temperature 20 C D B Outdoor air temp...

Страница 6: ...be mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 27 C W B Heating Indoor air temperature 20 C D B Outdoor air temperature 7 C D B 6 C W ...

Страница 7: ...de tube mm in Dimensions Weight Unit dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Weight Net kg Shipping kg Shipping volume m3 DATA SUBJECT TO CHANGE WITHOUT NOTICE Remarks Rating conditions are Cooling Indoor air temperature 27 C D B 19 C W B Outdoor air temperature 35 C D B 27 C W B Heating Indoor air temperature 20 C D B Outdoor air temperature 7 C D B 6...

Страница 8: ...igh Nominal output W Coil resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 50 1700 Thermal protector N A N A FV50S 670 C R 1 780 C S 2 175 Internal Rotary Hermetic 5KS205EAA21 370 Propeller 1 Ø 400 KFG6 51SB5P 1 6 900 80 15 2 440 40 BRN WHT 9...

Страница 9: ...il resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE Acrylic baked on enamel finish Aluminium plate fin Copper tube 2 1 4 0 60 60 RB68A Freol Alpha 68M 1130 C R 1 166 C S 1 534 Internal 1800 Thermal protector N A N A Rotary Hermetic 5JS270DAA0...

Страница 10: ...t W Coil resistance Ambient temp 25 C Ω Safety devices Type Operating temp Open C Close C Run capacitor µF VAC Heat Exch Coil Coil Rows Fin pitch mm Face area m2 External Finish DATA SUBJECT TO CHANGE WITHOUT NOTICE 440 Thermal protector 130 5 N A 6 4 760 60 WHT PNK 50 7 WHT BRN 88 9 Propeller 1 Ø 460 Y7S623B54 1 Rotary Hermetic 5JS270PAA21 1800 Thermal protector N A N A V W 5 562 FV50S 1130 U V 5...

Страница 11: ...RF228R5TAA GRF228R7TAA 4 way Valve 20S Coil model Coil rating Coil resistance Ω at 20 C High Pressure Switch HP set pressure open close electrical rating DATA SUBJECT TO CHANGE WITHOUT NOTICE ACB 2UB106 42 1 bar 33 1 5 bar AC 250V 1 6A N A STF 01AJ504D1 AC 220 240 V 50 Hz N A ACB 2UB106 42 1 bar 33 1 5 bar AC 250V 1 6A STF 0201G3 V2 410060 300 LDK 241 AC 208 240V 50 60Hz 4 5W 11 ...

Страница 12: ...SIONAL DATA GRF188R5TAA dimension mm GRF228R5TAA GRF228R7TAA dimension mm WIDE TUBE D 15 88 5 8 NARROW TUBE D 6 35 1 4 NARROW TUBE D 6 35 1 4 WIDE TUBE D 12 7 1 2 4 Ø12 for anchor bolt 4 Ø13 for anchor bolt 12 ...

Страница 13: ...ith a proper insulation material The thickness of the insulation should be a min 8mm CAUTION After a tube has been insulated never try to bend it into a narrow curve because it can cause the tube to break or crack cooling cycle heating cycle indoor unit MPAF188R5TAA outdoor unit GRF228R5TAA GRF228R7TAA outdoor unit GRF188R5TAA indoor unit MPAF228R5TAA wide tube O D 12 7mm 1 2 narrow tube O D 6 35m...

Страница 14: ... 00 10 5 0 5 10 15 20 25 Outdoor inlet air D B C High pressure at wide tube service valve MPa 5 0 5 5 6 0 6 5 7 0 7 5 8 0 8 5 9 0 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 32 27 19 5 0 5 5 6 0 6 5 7 0 7 5 8 0 8 5 9 0 10 5 0 5 10 15 20 25 Outdoor inlet D B temp C Operating current A Indoor inlet air D B C 27 20 15 0 60 0 70 0 80 0 90 1 00 1 10 1 20 20...

Страница 15: ...or inlet air D B C High pressure at wide tube service valve MPa 7 0 7 5 8 0 8 5 9 0 9 5 10 0 10 5 11 0 11 5 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 32 27 19 7 0 7 5 8 0 8 5 9 0 9 5 10 0 10 5 11 0 11 5 10 5 0 5 10 15 20 25 Outdoor inlet D B temp C Operating current A Indoor inlet air D B C 27 20 15 0 50 0 60 0 70 0 80 0 90 1 00 1 10 20 25 30 35 40 4...

Страница 16: ...10 15 20 25 Outdoor inlet air D B C High pressure at wide tube service valve MPa 3 0 3 5 4 0 4 5 5 0 5 5 20 25 30 35 40 45 Outdoor inlet air D B temp C Operating current A Indoor inlet air D B C 32 27 19 3 0 3 5 4 0 4 5 5 0 5 5 10 5 0 5 10 15 20 25 Outdoor inlet D B temp C Operating current A Indoor inlet air D B C 27 20 15 0 50 0 60 0 70 0 80 0 90 1 00 1 10 20 25 30 35 40 45 Outdoor inlet air D B...

Страница 17: ... 41 4 07 TC 5 75 5 43 5 25 5 00 4 70 4 33 CM 0 68 0 91 1 14 1 38 1 61 1 84 21 SHC 2 54 2 38 2 30 2 20 2 07 1 91 23 SHC 2 99 2 80 2 73 2 62 2 49 2 34 19 25 SHC 3 45 3 21 3 14 3 03 2 91 2 75 27 SHC 3 88 3 62 3 57 3 95 3 33 3 17 29 SHC 4 34 4 02 3 98 3 87 3 75 3 59 31 SHC 4 80 4 45 4 40 4 29 4 16 4 01 TC 6 05 5 76 5 57 5 30 4 98 4 59 CM 1 09 1 25 1 41 1 57 1 73 1 89 23 SHC 2 48 2 35 2 27 2 16 2 03 1 ...

Страница 18: ...7 59 7 17 6 93 6 60 6 20 5 71 CM 1 31 1 48 1 65 1 82 1 99 2 16 21 SHC 3 35 3 14 3 04 2 90 2 73 2 53 23 SHC 3 95 3 69 3 60 3 46 3 29 3 08 19 25 SHC 4 55 4 23 4 15 4 00 3 85 3 63 27 SHC 5 13 4 78 4 71 5 20 4 39 4 19 29 SHC 5 73 5 31 5 25 5 11 4 95 4 73 31 SHC 6 33 5 87 5 81 5 67 5 50 5 29 TC 7 99 7 60 7 35 7 00 6 57 6 05 CM 1 52 1 66 1 80 1 94 2 08 2 22 23 SHC 3 28 3 10 3 00 2 86 2 68 2 48 21 25 SHC...

Страница 19: ... 7 82 7 39 7 14 6 80 6 39 5 88 CM 1 29 1 48 1 68 1 87 2 06 2 26 21 SHC 3 45 3 24 3 13 2 99 2 81 2 60 23 SHC 4 07 3 81 3 71 3 56 3 39 3 18 19 25 SHC 4 69 4 36 4 27 4 12 3 96 3 74 27 SHC 5 28 4 92 4 85 5 40 4 52 4 32 29 SHC 5 90 5 47 5 41 5 26 5 10 4 88 31 SHC 6 52 6 05 5 99 5 84 5 66 5 45 TC 8 23 7 83 7 57 7 21 6 77 6 24 CM 1 55 1 70 1 85 2 01 2 16 2 31 23 SHC 3 38 3 20 3 09 2 94 2 76 2 56 21 25 SH...

Страница 20: ...s not take into consideration defrost operation 3 Fan speed High 4 Because this air conditioner heats a room by drawing in the heat of the outside air heat pump system The heating efficiency will fall off when the outdoor temperature is very low If sufficient heat cannot be obtained with this air conditioner use another heating appliance in conjunction with it Data referred to Hi Wall models MPAF1...

Страница 21: ... C D B 23 C W B Outdoor Air Temperature 43 C D B HEATING Indoor Unit Complete Unit Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps A 0 40 0 41 5 89 6 70 Power input Kw 0 086 0 087 1 347 1 520 Full load conditions Running Amps A 0 40 0 41 7 59 8 40 Power input Kw 0 086 0 087 1 927 2 100 Rating Conditions Indoor Air Temperature 20 C D B Outdoor Air Temperature 7 C D B 6 ...

Страница 22: ...ir Temperature 43 C D B HEATING Indoor Unit Complete Unit Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps A 0 40 0 67 8 43 9 50 Power input Kw 0 086 0 144 1 920 2 150 Full load conditions Running Amps A 0 40 0 67 9 93 11 00 Power input Kw 0 086 0 144 2 270 2 500 Rating Conditions Indoor Air Temperature 20 C D B Outdoor Air Temperature 7 C D B 6 C W B Full Load Conditio...

Страница 23: ...r Temperature 43 C D B HEATING Indoor Unit Complete Unit Fan Motor Fan Motor Compressor performance at Rating conditions Running Amps A 0 40 0 67 3 23 4 30 Power input Kw 0 086 0 144 1 970 2 200 Full load conditions Running Amps A 0 40 0 67 3 93 5 00 Power input Kw 0 086 0 144 2 370 2 600 Rating Conditions Indoor Air Temperature 20 C D B Outdoor Air Temperature 7 C D B 6 C W B Full Load Conditions...

Страница 24: ...m 3 phase m mm2 m mm2 25 65 1 phase GRF188R5TAA GRF228R5TAA GRF228R7TAA model 2 5 15 20 1 5 delayed fuse 16 A A power supply B control line MPAF188R5TAA MPAF228R5TAA MPAF228R5TAA GRF188R5TAA GRF228R5TAA GRF228R7TAA GRF228R5TAA GRF228R7TAA GRF188R5TAA 24 ...

Страница 25: ...R D 28 Reyrieux BP 131 01601 Trévoux CEDEX France Tél 04 74 00 92 92 Fax 04 74 00 42 00 R C S Bourg en Bresse B 759 200 728 ...

Отзывы: