background image

1

3

4

1. Mark the location of the hole on either side of the mounting

plate as shown. and drill it at a 5 downward angle, as shown.

2. The hole is drilled at an angle, to prevent condensed or rain

water from penetrating back into the room.

3. Trim the hole in the wall with a

80 mm commercial plastic tube.

PENETRATION OF WALL FOR TUBING

Fig. 10
A.OUTDOOR SIDE

1.Drill 80 mm

B.INDOOR SIDE

2.Wall

SUSPENDING AND RELEASING THE UNIT FROM THE
MOUNTING PLATE

Fig.11
1.Indoor unit

3.Top hooks

2.Snap catches 4.Botoon hooks

Fig.12
1.Mounting plate
2.Lower hook

CONDENSATE HOSE
CONNECTION

1. Attach the condensate drain hose to the corrugated hose in the

rear groove of the indoor unit.

2. Wrap the drain hose

together with the
refrigerant tubes and
electrical cables.

3. Ensure that the

condensate drain
hose is at all points
installed in a
downward slope
manner.

4. When installing the

drain hose avoide
traps and U-bends.
The end of the drain
hose should not be
immersed in water.

5. For a lefthand outlet,

lay the drain hose on
the bottom of the
indoor unit rear
groove.

6. When the installation

location requires long
horizontal sections, a
vent must be provided
at the top of the hose
to prevent overflow of
the unit drain pan.

7.Upon completing the installation, test the water drain by pouring

at least two liters of water into the unit drainpan. Check that the
water drains off.

Fig.13
1.drain hose
2.Clamp
3.Downward slope

Fig.16
1.Vent
2.Downword drain
3.Water drain hose

Fig.15
1.Electric calbe
2.Refrigerant tubing
3.Condensate drain hose

Fig.14
1.Trap
2.U-bend
3.End immersed in water

5

1

2

Fig 10

Fig 11

Fig 12

1

2

3

1. Make sure that the refrigerant tubes, electric cables and condensate

water hose are well insulated with closed cell rubber based insulating
tubes(6 mm thickness), are wrapped together with UV stabilized non-
adhesive plastic tape, and are passed through the hole in the wall.

2. Hang the indoor unit on the two hooks that are located near the top

edge of the mounting plate.

3. Press the lower part of the indoor unit against the mounting plate

until the catches snap into the slots and lock the indoor unit to the
mouting plate.

4. Check the installation by pulling the unit towards you.

5. To release the unit from the mounting plate, lift up the unit and then

pull the unit towards you, to ensure that the hooks are locked.

1

2

3

Fig 13

1

3

2

Fig 14

1

2

3

Fig 15

Fig 16

2

B

A

1

2

5

O

Содержание GRF124C5TAA

Страница 1: ...2 Tube flaring tool 13 Torque wrench 14 Adjustable wrench 15 Reamer for reburring 16 Hex key Tools required for installation not supplied OPERATING LIMITS Cooling Maximum conditions Outdoor temperatur...

Страница 2: ...ing to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When...

Страница 3: ...ect sunlight 3 The location must allow convenient electrical draingage and tubing connections 4 Installation site should provide an easy passage to outdoors 5 The unit must be mounted on a strong wall...

Страница 4: ...Direction of tubing Fig 4 Fig 6 Fig 6 1 Mounting pads x4 950mm 1800mm Fig 5 50 mm n mi 50 mm n mi 2300 mm n mi 400 mm n mi 80 mm min 2 1 1 100 mm n mi 100 mm n mi 500 mm n mi 100 mm n mi AUTO c F AM...

Страница 5: ...ere are five possible routes for installing the refrigeration tube as shown 2 For route 6 cut the bottom notch in the rear 3 For routes 5 or 7 cut the side notches in the rear and in the front panel F...

Страница 6: ...es long horizontal sections a vent must be provided at the top of the hose to prevent overflow of the unit drain pan 7 Upon completing the installation test the water drain by pouring at least two lit...

Страница 7: ...wire cable 6 connector instead 7 connect the other end of the twin wire cable 6 to the outdoor unit twin wire terminal 9 8 Secure the multiple wire power cable with the cable clamps 9 Fasten the twin...

Страница 8: ...oil Fig 24 1 Suction valve 2 Service port 3 Liquid valve Fig 24a 1 Charging set 2 Vacuum pump 3 OUTDOOR UNIT 4 Service valve TUBE SIZE Liquid line 1 4 Suction line 3 8 Suction line 1 2 Suction line 5...

Страница 9: ...between hole sides and tubing with sealer 3 Attach wiring and tubing to the wall with clamps where necessary 4 Operate the air conditioner together with the customer and explain all functions 5 Expla...