1-4 Indoor Fan Performance

If external static pressure is too great (due to long extension of ducts, foe example), the air flow volume may drop too low at
each air outlet. This problem may be solved by increasing the fan speed using the following procedure:

(1)

Remove the screw on the electrical component box
and remove the cover plate.

(2)

Disconnect the fan motor sockets in the box.

(3)

Take out the booster cable (sockets at both ends)
clamped in the box.

(4)

Securely connect the booster cable sockets between
the disconnected fan motor sockets in step 2
as shown in the Fig. 1-1

(5)

Place the cable neatly in the box and reinstall the cover plate.

Fig. 1-1

HH:

Using the booster cable

H:

At shipment

How to read the diagram

The vertical axis is the external static pressure (Pa)
while the orizzontal one is the AIR FLOW RATE (m3/h).
The characteristic curves for HH, H, M and L fan speed
are shown. The nameplate values shown are based on the
H air flow rate. For the type 7/9/12 flow rate is 600 m3/h
while the external static pressure is 49 Pa at H position.
If external static pressure is too great (due, for example,
to long duct extension), the air flow rate may drop too
much at each air outlet.
This problem can be solved increasing the fan speed
with the booster cable.

NOTE

EXTERNAL STATIC PRESSURE

m3/h

7/9/12000

16/18000

22000

EXTERNAL STATIC PRESSURE

m3/h

m3/h

EXTERNAL STATIC PRESSURE

11

Содержание 38.7106.982

Страница 1: ...ANUAL SPLIT SYSTEM AIR CONDITIONER Model No Product Code No DSAFM75R5I 38 7106 984 38 7130 019 38 7130 021 DSAFM95R5I 38 7130 020 DSAFM225R5I 38 7106 982 0 8180 441 1 Oct 2005 DSAFM125R5I DSAFM165R5I...

Страница 2: ...w wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line...

Страница 3: ...5 1 Replacing PCB 18 5 2 How to replace PCB 19 5 3 How to replace EEPROM with EEPROM included in PCB service pack 20 5 4 Table of setting 22 6 SERVICING AND MAINTENANCE FUNCTIONS 23 6 1 Indoor unit r...

Страница 4: ...Refrigerant Refrigerant control Dimensions Weight Dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Volume m3 Weight Net kg Shipping kg DATA SUBJECT TO CHANGE WITH...

Страница 5: ...eter Wide tube mm in Refrigerant Refrigerant control Dimensions Weight Dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Volume m3 Weight Net kg Shipping kg DATA SU...

Страница 6: ...r Wide tube mm in Refrigerant Refrigerant control Dimensions Weight Dimensions Height mm Width mm Depth mm Package dimensions Height mm Width mm Depth mm Volume m3 Weight Net kg Shipping kg DATA SUBJE...

Страница 7: ...K 37 BLK GRY 15 GRY VLT 15 WLT RED 30 RED YEL 101 Safety devices Type Operating temp Open C Run capacitor F VAC Electronic expansion valve Coil Valve body Heat Exch Coil Coil Rows Fin pitch mm face ar...

Страница 8: ...18 VLT RED 18 BRN YEL 105 Safety devices Type Operating temp Open C Close C Run capacitor F VAC Electronic expansion valve Coil Valve body Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJ...

Страница 9: ...18 VLT RED 18 BRN YEL 105 Safety devices Type Operating temp Open C Close C Run capacitor F VAC Electronic expansion valve Coil Valve body Heat Exch Coil Coil Rows Fin pitch mm face area m2 DATA SUBJE...

Страница 10: ...sensor E3 Resistance k Thermistor Room sensor TA TF BL Resistance k Drain pump Model Rating Voltage Input Flow rate Safety float switch Model Contact rating 0 C 15 0 5 PBC 41E S42 2 0 C 15 0 4 42 25 C...

Страница 11: ...e neatly in the box and reinstall the cover plate Fig 1 1 HH Using the booster cable H At shipment How to read the diagram The vertical axis is the external static pressure Pa while the orizzontal one...

Страница 12: ...2 DIMENSIONAL DATA DSAFM75 95 125R5I 12...

Страница 13: ...DSAFM165 185 225R5I 13...

Страница 14: ...3 ELECTRICAL DATA 3 1 Electric Wiring Diagram 7P terminal board 1 L 2 N U1 U2 R1 R2 wiring remote controller power supply inter unit control 14...

Страница 15: ...he unit to be operated by the remote controller even if it is not CN072 connected to an outdoor unit In this case alarm E04 which indicates trouble in the serial communication between the indoor and o...

Страница 16: ...4 FUNCTIONS 4 1 Room temperature control 16...

Страница 17: ...4 2 Automatic control for heating and cooling 17...

Страница 18: ...Read Only Memory EEPROM is a component in which the various information necessary for functionning can be electronically written or erased This component holds informations that is essential for the r...

Страница 19: ...5 2 How to replace PCB 19...

Страница 20: ...5 3 How to replace EEPROM with EEPROM included in PCB service pack 20...

Страница 21: ...21...

Страница 22: ...5 4 Table of settings 22...

Страница 23: ...6 SERVICING AND MAINTENANCE FUNCTIONS 23...

Страница 24: ...7 TROUBLE DIAGNOSIS 7 1 Contents of remote controller switch alarm display 24...

Страница 25: ...25...

Страница 26: ...7 2 Outdoor unit control panel LED display 26...

Страница 27: ...7 3 Trouble indications and inspection points 27...

Страница 28: ...28...

Страница 29: ...7 4 Remote controller servicing functions 29...

Страница 30: ...7 5 Multiset alarm codes 30...

Страница 31: ...31...

Страница 32: ...32...

Страница 33: ...33...

Страница 34: ...34...

Страница 35: ...35...

Страница 36: ...36...

Страница 37: ...37...

Страница 38: ...38...

Страница 39: ...39...

Страница 40: ...40...

Страница 41: ...41...

Страница 42: ...42...

Страница 43: ...43...

Страница 44: ...44...

Страница 45: ...45...

Страница 46: ...46...

Страница 47: ...47...

Страница 48: ...48...

Страница 49: ...49...

Страница 50: ...50...

Страница 51: ...51...

Страница 52: ...52...

Страница 53: ...7 6 Inspection of parts 53...

Страница 54: ...54...

Страница 55: ...55...

Страница 56: ...R D 28 Reyrieux BP 131 01601 Tr voux CEDEX France T l 04 74 00 92 92 Fax 04 74 00 42 00 R C S Bourg en Bresse B 759 200 728...

Отзывы: