5-2 Cool Mode Operation
In Cooling Mode, the operation of the compressor (CM), Outdoor Fan (FMO) and Indoor Fan (FMI) are
determined by:
1) the difference between the room air temperature (RAT) and the set point temperature (SPT)
2) the protection level at which the system is operating
NOTES
In addition to the temperature difference of above, the operation of the main components (CM, FMO,
FMI) is also controlled by protection function.
The minimum off time of compressor is 3 minutes.
The indoor fan can change speed only after it has operated at the same speed for 30 sec if in AUTO
and 1 sec for the other settings (High, Med, Low).
5-3 Heat Mode Operation
The Heating mode operation is similar to the Cooling mode operation. The CM, FMO and FMI are controlled
by the same parameters.
NOTES
1. After the CM has stopped, the FMI runs for 30s in order to purge heat from the indoor coil.
2. The FMI will not be turned on until the indoor coil temperature is warm enough to prevent the supply of
cold air (see COLD DRAFT PREVENTION feature for details).
The indoor fan can change speed only after it has operated at the same speed for 30 sec if in AUTO and
1 sec for the other settings (High, Med, Low).
14
Содержание 38.7104.050
Страница 9: ...2 DIMENSIONAL DATA MRAF98R5IAA MRAF128R5IAA 9...
Страница 12: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams MRAF98R5IAA MRAF128R5IAA 12...
Страница 27: ...6 3 SYSTEM DOES NOT RUN 27...
Страница 29: ...6 4 OUTDOOR UNIT DOES NOT RUN AND NO FAULT IS DISPLAIED 6 5 ONLY OUTDOOR UNIT IS OFF 29...
Страница 30: ...6 6 OUTDOOR UNIT FAULT SIGNALING 30...
Страница 32: ...32...
Страница 33: ...6 8 NOISY PROBLEM 33...
Страница 34: ...7 CHECKING ELETRICAL COMPONENTS 7 1 34...
Страница 35: ...7 2 35...