Page 6
4.2 Standard connection
Conn
ec
ti
o
n
Input 1
Door contact, active when door closed; REX button
Input 2
Request to exit button or handle contact, active when button or
handle pressed; Tamper; Disabling function
Output 1 (transistor)
Door lock control (configurable polarity, default 0V for lock release)
Alarm output
Low power transistor output (+5 V in any alarm state)
I/O Port 3
External tamper (Standard operating mode)
External reader buzzer control (op. mode with entry reader)
Disabling function
Reading synchronization: MASTER / SLAVE mode
Table 6: Standard connection
The door monitoring contact (IN1) is operational after its first change of status since
switching on the module. Full door lock timing acc. to
tab. 8
is used when the door status
contact is not installed and no Forced Door and Door Ajar alarms are triggered.
4.3 LED Indicators
D1
– upper LED; D2 – middle LED; D3 – lower LED
LE
D
ind
ic
at
ors
D1
Red-green
Continuously lit (red)
Online operating mode
Flashing with 4 s period (red)
Offline operating mode
Fast switching (red / green)
Address setting mode;
RS 485 BUS testing mode
Single flash (green)
ID media reading
D2
Yellow
Continuously lit / flashing
Programming mode
Short flashing with 1s per.
Indicating door lock release
(configurable)
D3
Green
Indicating door lock release
Table 7: LED indicators
4.4 Installation instructions
The reader module uses passive RF/ID technology, which is sensitive to RF noise sources.
Noise sources are generally of two types: radiating or conducting.
Conducted noise enters the reader via wires from the power supply or the host. Sometimes,
switching power supplies generate enough noise to cause reader malfunction, it is
recommended to use linear system power supplies.
Radiated noise is transmitted through the air. It can be caused by computer monitors or other
electrical equipment generating electromagnetic fields.
Consequently, a short distance between the reader modules themselves can cause reading
malfunctions
– for correct operation it is necessary to keep a minimum distance of 50 cm.
Various metallic constructions may have a negative influence on this distance; if there are
any doubts, it is recommended to perform a practical test before final mounting.