The blower is activated. The pump starts irrespective of the 
current temperature. The controller awaits for pressing the 
OPTIONS button. Next, the alarm is deactivated and the normal 
operation of the controller is restored. 

III.c) Temperature protection 

The controller has an auxiliary protection in case of damage to 
a bimetal sensor: upon exceeding the temperature of 85°C, the 
alarm is activated and the LCD displays: 

III. d) Boiling protection

This function prevents excessive temperature of the boiler (only 
when the boiler priority function is on) i.e. when the boiler set 
temperature is e.g. 55°C and the current boiler temperature is 
62°C, the controller activates the fan. When the temperature 
reaches as much as 80°C, the CH pump is activated. If the 
temperature continuous increasing, the alarm turns on at 85°C. 
This may happen, when the boiler is damaged, the sensor is 
installed improperly and the pump is damaged. However, if the 
temperature decreases, at the threshold value of 60 °C, the 
blower will be started and it will continue operation until the 
boiler set temperature is reached. 

III.e) Fuse

The controller is equipped with a WT 

2.5A

 fuse to protect the 

means. 

WARNING:

 No fuse of the higher value should be used. 

Installation of the fuse of a higher ampere value may 
result in a damage to the controller. 

12

Содержание ST-28

Страница 1: ...1...

Страница 2: ...4 of 12 March 2003 introducing the provisions of the Low Voltage Directive LVD 2006 95 ECE and the Ordinance of the Minister of Infrastructure Dz U 03 90 848 of 02 April 2003 introducing the provision...

Страница 3: ...of the device etc make sure the controller is not connected to the mains The installation should be conducted by a certified electrician Prior to commissioning of the controller the measurements of th...

Страница 4: ...e flue gas outlet temperature the right of the screen shows the power of the fan Press EXIT to return to the main menu ST 81thermal controller is designed for central heating boilers ST 81 thermoregul...

Страница 5: ...set up to meet individual requirements depending on the type of fuel and a boiler TECH shall bear no responsibility for the erroneous setup of the controller II Controller functionalities This section...

Страница 6: ...e status is indicated by an asterisk in the right bottom corner of the display asterisk indicates that the fan is enabled The function allows safe operation of the boiler The furnace door must not be...

Страница 7: ...The option enables setup of CH pump and UHW pump activation temperatures this refers to temperatures measured on the boiler Both pumps do not work below the set temperature If the set temperature is...

Страница 8: ...activated at 60 C whereas the operation mode will be restored upon drop to 58 C The hysteresis value may range from 2 C to 6 C II f Hysteresis of UHW This option allows setup of the set temperature h...

Страница 9: ...pon reaching the set temperature the UHW pump is deactivated and the CH pump starts In this mode the operation of the fan is limited to 62 C at the boiler to prevent boiler overheating This condition...

Страница 10: ...activation of this function the LCD displays three items Boiler temperature CH vessel temperature UHW and set temperature II j Fixed CH Pump In this mode pumps are activated concurrently above the set...

Страница 11: ...measures The alarm status is indicated by a sound and a special message is displayed on the LCD To restore operation of the boiler press the OPTIONS button III a Thermal protection This is an auxilia...

Страница 12: ...the boiler set temperature is e g 55 C and the current boiler temperature is 62 C the controller activates the fan When the temperature reaches as much as 80 C the CH pump is activated If the tempera...

Страница 13: ...be removed Furthermore the measurements of the grounding efficiency of the electric motors of CH pump UHW pump and fan must be taken No Item Unit 1 Power supply V 230V 50Hz 10 2 Power input W 2 3 Env...

Страница 14: ...he plug is not connected to the means WARNING Incorrect installation of the wires may result in a damage to the controller The controller cannot operate in a closed central heating circulation system...

Страница 15: ...umps 6 II e Hysteresis of the boiler 7 II f Hysteresis of UHW 8 II g UHV pump 8 II i Summer mode 10 II j Fixed CH Pump 11 II k Default settings 11 III Safety measures 12 III a Thermal protection 12 II...

Страница 16: ...16...

Отзывы: