Indoor temperature is lower than the set value. The default is 5
℃
,
above 7
℃
, alarm will disappear
Ht High temperature alarm
Indoor temperature is higher than the set value. The default is 35
℃
,
below 33
℃
, alarm will disappear
FEr Fan fault alarm
If alarm for unit 1, will switch to unit 2, Then unit 1 will stop running. If the
alarm for unit 2, then the unit 2 will shutdown.
Check if the switch input is faulty , fan is damaged or cable is broken
After alarm is released, system will restart after 1 minute.
CEr Compressor fault alarm
Check if the switch input is faulty , compressor is damaged or cable is
broken
HP1 Circuit 1 High pressure alarm
Check if the heat dissipation fin of outdoor unit is dirty or plugging
Or refrigerant is over charged, or outdoor ventilation and heat dissipation
is not good.
LP1 Circuit 1 Low pressure alarm