13
Example:
Pre-set zone temperature: 23˚C
Minimum opening: 30%
Maximum opening: 90%
Range: 5˚C
Hysteresis: 2˚C
In the above example, the thermostatic valve starts closing at the temperature of 18˚C (pre-set value minus Range). The
minimum opening is reached when the zone temperature reaches the pre-set value.
Once the pre-set temperature has been reached, the temperature starts falling. At the temperature of 21˚C (pre-set value
minus hysteresis), the valve starts opening. The maximum opening is reached at the temperature of 18˚C.
EMERGENCY MODE – this function opens the actuators if an alarm occurs in a zone (sensor failure, communication
error).
PROTECTION – Once this function has been selected, the controller checks the temperature. If the pre-set value has
been exceeded by the number of degrees specified in the <range> parameter, all actuators in the zone will close (0%
of opening). This protection is enabled by default.
2.10.
WINDOW SENSORS
Registration – in order to register a window sensors, select <Registration> and press quickly the communication
button on the window sensor. Release the button and watch the control light.
- control light flashes twice - proper communication established.
- control light lights up continuously - no communication with the main controller.
NOTE
The controller supports the maximum of 6 window sensors in a zone.
Sensor removal – this function is used to remove all the registered sensors in a given zone from the controller
memory.