Important Installation Notes for Air Conditioners

Mounting Styles:  

Vertical (Side/Front/Back) Mounting:  

Condensate Removal System:

Top Mounting:

Maintenance:

Cautions:

Notes on condensation:

Both ‘thru mount’ and ‘flush mount’ units can be positioned in 

any orientation and on any enclosure surface.  It is important to consider interior 
air flow patterns when determining the mounting location.  Also of importance 
is an unrestricted flow of ambient air thru the hot side heat exchanger.  Ease 

of access and inspection must be considered for those applications in 
particularly severe environments which may require occasional 

maintenance.

Vertical mounting refers to the vertical direction of the cold side 
or interior fins and is recommended for applications with high 

humidity, poor and incomplete cabinet seals or any condition which 
may cause the cold side fins to be maintained at temperatures 
below the dew point for long periods of time allowing for the 

formation of condensation.  The vertical fin direction provides a drip 
path whereupon condensation can be collected via a moisture 

removal system (standard on FHP-units) or a drip pan positioned 
below the cold side fins.  Drip pans are optional  for thru mount units.

All FHP-Series and AHP-1400 air conditioners contain a built-in condensate removal system.  The condensate kit consists of a 

antifungal sponge with a condensate wick. PVC tubing is also provided for drainage.  Drip pans are optional for thru mount units 
which must be evaluated on an individual basis.  Equations defining a relationship between the cold side fin and enclosure 
temperatures are provided to assist in the evaluation.

Though often the easiest location to mount it is often the most difficult to protect from  condensation in this orientation due to the 

fin orientation, gravity and any susceptible components below.  If a drip pan is employed by the end user use caution to place 
the pan far enough away from the internal fan to minimize the restriction of air flow. The pan should cover the fin ends as well as 

the fan area.  When there is a choice, the vertical orientation is preferred by most users.

Since the technology is solid-state, there are no filters, compressors, or fluorocarbons  to maintain.  The only moving parts are 

the fans.     It is recommended for harsh or dirty environments that the heat sinks be cleaned from time to time.  This can be 
accomplished by directing compressed air over the external fins or on NEMA 4 versions by hosing the unit down.  This will 

increase the overall life and performance of the system.  

Take care when mounting not to damage the seal between the hot and cold side sinks.  Do not attempt to mount a unit to a 
warped surface or try to make the units mounting surface conform to an unflat surface.  Do not pinch or damage any leads when 

mounting.  Do not over tighten any installation screw, use reasonable force.  Always mount with any condensate drain down.  
Do not compress the cold side between the hot side and any other surface.  Do not obstruct the airflow on either side.  When 
mounting consider the natural air flows of the enclosure.  Connect power only after the installation is complete.

Condensation occurs at the cold side fins when the surface temperature goes below the dew point.  To reduce or remove 
condensate, consider the following:

• Regulate the Fin Temperature above the Dewpoint.
• Keep Enclosure Closed and Sealed from Outside Humidity.
• Use Desiccant (Moisture absorbing Granules.)

• Employ Condensate Removal System/Drip Pans.

If you have any questions regarding your installation, Please feel free to contact our technical department for assistance at 773-
342-4900. 

 

 
 