FHP-1501 Air Conditioner
Air Cooled
120/240 VAC Input
Flush Mounted
NEMA-12, NEMA-4
FEATURES
• Externally mounted (no intrusion)
• Mounts in multi-unit array for incremental capacity
• Compact (only 15”L X 12”W X 9”D)
• Weighs only 55 lbs. (25 kg)
• Ambient range -10ºC to +70ºC
• No compressor, fluorocarbons or filters
• Virtually maintenance-free operation
• Stainless steel exterior housing
• Dual voltage (120/240 VAC)
• No moving parts except fans
• Environmetally safe
• Mounts and operates in any orientation
(condensate removal system may not work properly in
all orientations)
INCLUDES
• Integral power supply
• Condensate removal system
• Adjustable temperature control
• Mounting gasket for NEMA-12, NEMA-4 seal
• Mounting hardware
SPECIFICATIONS
OPERATING
OPERATING
PERFORMANCE
VOLTAGE
CURRENT
TEMP.
AMBIENT
ENCLOSURE
AGENCY
MODEL
PART NUMBER
NOTES
RATING
VAC
AMPS.
CONTROL
TEMPERATURE
TEMPERATURE
APPROVALS
BTU/HR
50/60 HZ
RANGE °C
RANGE °C
FHP-1501
7-2181-0-000
Cool only
1000-1100
120/240
8.0/5.5
TC-6F†
-40/+65
-10/+60
UL1995/CSA22.2
FHP-1501
7-2151-0-000
Cool only
1000-1100
120/240
8.0/5.5
EXT*
-40/+65
-10/+60
UL1995/CSA22.2
FHP-1501
7-21F1-0-000
Cool only
1000-1100
120/240
8.0/5.5
85°F (30°C)
-40/+65
-10/+60
UL1995/CSA22.2
FHP-1501HC
7-2131-1-000
Heat/Cool
1000-1100
120/240
8.0/5.5
TC-3F
-40/+65
-10/+60
UL1995/CSA22.2
FHP-1501HC
7-2151-1-000
Heat/Cool
1000-1100
120/240
8.0/5.5
EXT*
-40/+65
-10/+60
UL1995/CSA22.2
FHP-1501XE
7-2181-4-000
Cool only
1000-1100
120/240
8.0/5.5
TC-6F†
-40/+60
-10/+60
UL1995/CSA22.2
FHP-1501XE
7-2151-4-000
Cool only
1000-1100
120/240
8.0/5.5
EXT*
-40/+60
-10/+60
UL1995/CSA22.2
FHP-1501XE
7-21F1-4-000
Cool only
1000-1100
120/240
8.0/5.5
85°F (30°C)
-40/+65
-10/+60
UL1995/CSA22.2
FHP-1501XEHC
7-2131-5-000
Heat/Cool
1000-1100
120/240
8.0/5.5
TC-3F
-40/+65
-10/+60
UL1995/CSA22.2
FHP-1501XEHC
7-2151-5-000
Heat/Cool
1000-1100
120/240
8.0/5.5
EXT*
-40/+65
-10/+60
UL1995/CSA22.2
* Unit is set for 5-32 VDC external signal, relay(s) include
† Unit evaluated by ETL
56
TECA
1-888-TECA-USA (832-2872)
www.teca-usa.com
N
E
M
A
12
N
E
M
A
4
INCLUDES
• Other temperature settings for single set point controls
• Custom finishes
catalog 2011 working on.qxp 6/29/2011 1:25 PM Page 56