teca 0-L0I4-5-000 Скачать руководство пользователя страница 3

TECA

1-888-TECA-USA (832-2872)

www.thermoelectric.com

AHP-250 Air Conditioner / Heat Exchanger

Air Cooled

12 VDC, 24 VDC

Through Mounted

129 BTU/HR

Nema-12, 4, 4X

FEATURES

• Compact (only 6” X 4.75” X 6.6”)

• Mounts and operates in any orientation:

horizontal, vertical, etc.

• Lower vibration and noise

• No moving parts except fans

• Environmentally safe

• No compressor, fluorocarbons or filters

• Heat via reverse polarity

• Virtually maintenance-free operation

• Weight  4.4 LBS.

Active Cooling

35 °C

Heat Exchanger (ECO-Mode)

25 °C

Active Heating

10 °C

Typical Hysteresis

5 °C

Operating Ambient

-40/+70 °C

Operating Enclosure

-10/+60 °C

CONTROL TEMPERATURES

Voltage

12 VDC, 24 VDC

Current, Active

6 AMPS, 3 AMPS

Current, ECO-Mode

0.3 AMPS

POWER INPUTS

Cooling (Traditional)

128 BTU/HR

Cooling (Din 3168)

38 WATTS

Cooling COP (at L35 L35)

0.53

Heating (Traditional)

> 245 BTU/HR

Heating (Din 3168)

> 72 WATTS

Heating COP

> 1.0

PERFORMANCE RATINGS

CONFIGURATIONS

INTEGRAL

MODEL

PART NUMBER

NOTES

TEMPERATURE

VOLTAGE

CURRENT

ENVIRONMENT

CONTROL

VDC

AMPS

AHP-250FFHC

0-L094-1-000*

Industrial fans

None

12

6

NEMA-12, IP 52

AHP-250FFHC

0-L095-1-000*

Industrial fans

None

24

3

NEMA-12, IP 52

AHP-250FF

0-L0J4-0-000

Industrial fans

TC-4F

12

6

NEMA-12, IP 52

AHP-250FF

0-L0J5-0-000

Industrial fans

TC-4F

24

3

NEMA-12, IP 52

AHP-250FFHC

0-L0I4-1-000

Industrial fans

TC-7F

12

6

NEMA-12, IP 52

AHP-250FFHC

0-L0I5-1-000

Industrial fans

TC-7F

24

3

NEMA-12, IP 52

AHP-250XEHC

0-L094-5-000*

Industrial sealed HS fan

None

12

6

NEMA-4, IP 56

AHP-250XEHC

0-L095-5-000*

Industrial sealed HS fan

None

24

3

NEMA-4, IP 56

AHP-250XE

0-L0J4-4-000

Industrial sealed HS fan

TC-4F

12

6

NEMA-4, IP 56

AHP-250XE

0-L0J5-4-000

Industrial sealed HS fan

TC-4F

24

3

NEMA-4, IP 56

AHP-250XEHC

0-L0I4-5-000

Industrial sealed HS fan

TC-7F

12

6

NEMA-4, IP 56

AHP-250XEHC

0-L0I5-5-000

Industrial sealed HS fan

TC-7F

24

3

NEMA-4, IP 56

AHP-250XHC

0-L094-3-000*

Military grade HS fan

None

12

6

NEMA-4X, IP 56

AHP-250XHC

0-L095-3-000*

Military grade HS fan

None

24

3

NEMA-4X, IP 56

AHP-250X

0-L0J4-2-000

Military grade HS fan

TC-4F

12

6

NEMA-4X, IP 56

AHP-250X

0-L0J5-2-000

Military grade HS fan

TC-4F

24

3

NEMA-4X, IP 56

AHP-250XHC

0-L0I4-3-000

Military grade HS fan

TC-7F

12

6

NEMA-4X, IP 56

AHP-250XHC

0-L0I5-3-000

Military grade HS fan

TC-7F

24

3

NEMA-4X, IP 56

* Heat/Cool function via reverse polarity capable external controller

Содержание 0-L0I4-5-000

Страница 1: ...follow all instructions carefully before installation Only qualified technicians should install this equipment If you have any questions regarding your equipment please do not hesitate to call us at 773 342 4900 and we will be happy to assist you We are open from 8 00 am 4 30 pm Central Time Included in this packet you will find Installation Notes for Air Conditioners Product Literature and Specif...

Страница 2: ...ften the most difficult to protect from condensation in this orientation due to the fin orientation gravity and any susceptible components below If a drip pan is employed by the end user use caution to place the pan far enough away from the internal fan to minimize the restriction of air flow The pan should cover the fin ends as well as the fan area When there is a choice the vertical orientation ...

Страница 3: ...2 AHP 250FFHC 0 L095 1 000 Industrial fans None 24 3 NEMA 12 IP 52 AHP 250FF 0 L0J4 0 000 Industrial fans TC 4F 12 6 NEMA 12 IP 52 AHP 250FF 0 L0J5 0 000 Industrial fans TC 4F 24 3 NEMA 12 IP 52 AHP 250FFHC 0 L0I4 1 000 Industrial fans TC 7F 12 6 NEMA 12 IP 52 AHP 250FFHC 0 L0I5 1 000 Industrial fans TC 7F 24 3 NEMA 12 IP 52 AHP 250XEHC 0 L094 5 000 Industrial sealed HS fan None 12 6 NEMA 4 IP 56 ...

Страница 4: ... C 50 C Enclosure Air y 1 35x 51 y 1 34x 52 Cold Sink y 1 15x 51 7 y 1 13x 52 6 AHP 250 Air Conditioner Air Cooled MOUNTING STYLE Through Mounted ENVIRONMENTS SERVED NEMA 12 IP 52 NEMA 4 4X IP 56 RATING TRADITIONAL 129 BTU hr 0 F T 162 BTU hr 20 F T RATING DIN 3168 38 Watts L35 L35 28 Watts L35 L50 DIMENSIONS Air Flow Pattern ...

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ...TC 7F with relays inside the bracket pre wired to the unit Loosen these screws to slide the TC 7F bracket out ...

Страница 9: ...to the AHP 250XEHC Fit the AHP 250XEHC along with pre wired TC 7F controller bracket assembly through the mounting cutout on the enclosure Making sure wires are not pinched between the enclosure and the unit secure the AHP 250XEHC on the enclosure ...

Страница 10: ... two screws to secure the bracket in place After the installation of the AHP 250XEHC on the enclosure is complete slide the TC 7F bracket under the cold side fan finger guard and re tighten the two screws Please note that on this guide the enclosure mounting gasket and hardware are not shown ...

Страница 11: ...ree of charge to Buyer or credit to buyer the price of the defective products ALL OTHER WARRANTIES EXPRESS OR IMPLIED ARE EXCLUDED INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE IN NO EVENT SHALL TECA BE LIABLE FOR ANY CLAIM BASED UPON BREACH OF EXPRESS OR IMPLIED WARRANTY OR ANY OTHER DAMAGES WHETHER SPECIAL INDIRECT INCIDENTAL CONSEQUE...

Отзывы: