408-78067 

Rev A

 

of 4

 

3.2. 

Wire Strip  

3.2.1  Applicable wire size: AWG #8~#16(1.3~8.4mm2), Strip length: 13.7

±

0.5mm.                      

*Strip length could be confirmed by comparing with strip gauge on 2 sides of receptacle 
assembly as Fig.2 shows. 

3.2.2  In case of any undesirable twist, bending or loosening of conductors after stripping, fix the 

shape of the wires and confirm length with strip gauge before using.                                         
*Do not use extremely deformed wire after stipping. 

3.2.3  Cutting surface of conductor and insulator of processed wires shall be smoothly flat. 

 

   

 

         

 

 

   

 

 

 

 

 

 

 

 

 

Fig.2 

 

3.3. 

Method of connecting wire with spring opener (2260828-1) 

When reconnecting with other wires, only wire of same diameter and stranded condition could be used. 

 

3.3.1  Install the spring opener to the receptacle assembly and push the lever of opener at illustrated 

direction in Fig.3. 

3.3.2  Insert wire until the end while pushing the lever of opener simultaneously. Do not over push the 

opener when it touches receptacle assembly. 

3.3.3  Release the lever of opener and pull the wire slightly to confirm if the cable is fixed by spring.  

 

 

Fig. 3 

 

STRIP GAUGE 

Strip length 
13.7±0.5mm 

Wire 

3.3.2 

3.3.1 

3.3.3 

Do not over push the opener when it touches 
receptacle assembly. 