background image

4.5 Supply System 

The unit has a default setting of 3Phase 4wire (3P4). 

Use this 

section to set the type of electrical system. 

From the set-up menu, use 

and 

 buttons to select the 

system option. 
The screen will show the currently 
selected power supply. 

Press 

 to enter the selection 

routine. The current selection will 
flash. 

Use 

 and 

 buttons to 

select the required system option: 
1P2(W),3P3(W), 3P4(W). 

Press 

 to confirm the 

selection. SET indicator will 
appear. 

Press 

 to exit the system selection routine and return to the 

menu. SET will disappear and you will be returned to the main 
set-up Menu. 

4.6 CLR 

The meter provides a function to reset the maximum demand 
value of current and power. 

From the set-up menu, use 

and 

 buttons to select the 

reset option. 

Press 

 to enter the selection 

routine. The dIt will flash. 

Press

 

 to confirm the setting and press 

 to return to 

the main set up menu. 

4.7 Change Password 

Use the 

 and 

to choose the change 
password option. 

Press the 

 to enter the 

change password routine. The 
new password screen will appear 
with the first digit flashing. 

Use 

 and 

 to set the first 

digit and press 

 to confirm 

your selection. The next digit will 
flash. 
Repeat the procedure for the 
remaining three digits. 

After setting the last digit, SET will 
show. 

Press 

 to exit the number setting routine and return to the 

Set-up menu. SET will be removed. 

4.8 DIT Demand Integration Time 

This sets the period in minutes over which the current and power 
readings are integrated for maximum demand measurement. The 
options are: off, 5, 10,15 30,60 minutes. 

From the set-up menu, use 

and 

 buttons to select the DIT 

option. The screen will show 
the currently selected integration 
time. 

Press 

 to enter the selection 

routine. 
The current time interval will flash. 

Use 

 and 

buttons to select the time required. 

Press 

 to confirm the 

selection. SET indicator will 
appear. 

Press 

 to exit the DIT selection routine and return to the 

menu. 

5 Specifications 

5.1 Measured Parameters 

The unit can monitor and display the following parameters of a 
single phase two wire (1p2w), three phase three wire (3p3w) or 
three phase four wire (3p4w) system. 

5.1.1 Voltage and Current 

• Phase to neutral voltages 100 to 289V a.c.

(not for 3p3w supplies).

• Voltages between phases 173 to 500V a.c.

(3p supplies only).

• Continuous Overload voltage 120%
• Percentage total voltage harmonic distortion

(THD%) for each phase to N ( not for 3p3w

  supplies). 
• Percentage voltage THD% between phases

(three phase supplies only).

• Current 100A (Direct connected)
• Continuous Overload current 120%
• Current THD% for each phase.
• Burden <10VA (nom 2VA)
• Self powered from any phase

5.1.2 Power factor and Frequency and Max. Demand 

• Frequency in Hz
• Instantaneous power:
• Power 0 to 3600 MW
• Reactive power 0 to 3600 MVAr
• Volt-amps 0 to 3600 MVA
• Maximum demanded power since last Demand

reset Power factor

• Maximum neutral demand current, since the last

Demand reset (for three phase supplies only)

5.1.3 Energy Measurements 

• Imported/Exported active

energy

• Imported/Exported

reactive energy

• Total active energy
• Total reactive energy

0 to 9999999.9 kWh 

0 to 9999999.9 kVArh 

0 to 9999999.9 kWh 
0 to 9999999.9 kVArh 

5.2 Measured Inputs 

Voltage inputs through 4-way fixed connector with 2.5mm² 
stranded wire capacity. Single phase two wire(1p2w), three 
phase three wire(3p3w) or three phase four wire(3p4w) 
unbalanced. Line frequency measured from L1 voltage or L3 
voltage. 

5.3 Accuracy 

• Voltage

0·5% of range maximum 

• Current

0·5% of nominal 

• Frequency

0·2% of mid-frequency 

• Power factor

1% of unity (0.01) 

• Active power (W)

±1% of range maximum 

• Reactive power (VAr)

±1% of range maximum  

• Apparent power (VA)

±1% of range maximum  

• Active energy (Wh)

Class 1 IEC 62053-21 

• Reactive energy (VARh)   ±1% of range maximum
• Total harmonic

1% up to 31st harmonic 

distortion

• Response time to

1s, typical, to >99% of 

step input

final reading, at 50 Hz. 

 5.4 Interfaces for External Monitoring 

Three interfaces are provided: 

• RS485 communication channel that can be

programmed for Modbus RTU protocol

• Relay output indicating real-time measured energy.

(configurable)

• Pulse output 400imp/kWh (not configurable)

The Modbus configuration (baud rate etc.) and the pulse relay 
output assignments (kW/kVArh import/export etc.) are configured 
through the set-up screens. 

5.4.1 Pulse Output 

Opto-coupler with potential free SPST-NO Contact 
(Contact range 5-27VDC / Max current input: Imin 2mA and Imax 
27mA DC). The pulse output can be set to generate pulses to 
represent kWh or kVArh. 

Rate

 can be set to generate 1 pulse per: 

0.01 = 10 Wh/VArh 
0.1 = 100 Wh/VArh 
1 = 1 kWh/kVArh 
10 = 10 kWh/kVArh 
100 = 100 kWh/kVArh 

Pulse width

 200/100/60 ms. 

5.4.2 RS485 Output for Modbus RTU 

For Modbus RTU, the following RS485 communication 
parameters can be configured from the set-up menu: 

Baud rate

 2400, 4800, 9600, 19200, 38400 

Parity 

none (default) / odd / even  

Stop bits

 1 or 2 

RS485 network address

 nnn 

– 3-digit number, 1 to 247 

Modbus™ Word

 order Hi/Lo byte order is set automatically to 

normal as defined by IEEE 754. It cannot be configured from the 
set-up menu. 

5.5 Reference Conditions of Influence Quantities 

Influence Quantities are variables that affect measurement errors 
to a minor degree. Accuracy is verified under nominal value 
(within the specified tolerance) of these conditions. 

• Ambient temperature

23°C ±1°C 

• Input waveform

50 or 60Hz ±2% 

• Input waveform

Sinusoidal (distortion 
factor < 0·005) 

  (if AC) 

factor < 0·05) 

• Magnetic field of

Terrestrial flux 

external origin

5.6 Environment 

• Operating temperature

-25°C to +55°C*

• Storage temperature

-40°C to +70°C*

• Relative humidity

0 to 95%,
non-condensing

• Altitude

Up to 3000m

• Warm up time

1 minute

• Vibration

10Hz to 50Hz, IEC
60068-2-6, 2g

• Shock

30g in 3 planes

*Maximum operating and storage temperatures are in the context
of typical daily and seasonal variation.

5.7 Mechanics 

• DIN rail dimensions

76 x 100 mm (WxH) 
per DIN 43880 

• Mounting

DIN rail (DIN 43880) 

• Sealing

IP51 indoor 

• Material

UL 94 V-0 
Self-extinguishing  

6 Installation and Maintenance 

6.1 Installation notes 

Units should be installed in a dry position, where the ambient 
temperature is reasonably stable and will not be outside the 
range -25 to +55

C. 

Vibration should be kept to a minimum. 
Preferably, mount the Integra so that the display contrast is not 
reduced by direct sunlight or other high intensity lighting. 

Отзывы: