background image

OPERATING INSTRUCTIONS

 

AST46DS

 

 

TE CONNECTIVITY SENSORS 

/// AST46DS OPERATING INSTRUCTIONS            

 

 03/2019

 

Page 4

 

 

 

 

 

 
 
 
Zero Adjustment 

 

The Zero button will adjust the output signal and display to the base reading range.

 

 

Ensure the product is in a non-hazardous environment.

 

 

Remove the front display cover by hand to access the “Zero” button.

 

 

Connect the AST46DS using standard wiring instructions with an 8-28VDC power supply.

 

 

Do not remove power from the product during the Zero adjustment process. If “

CHECKBYTE 

ERROR

” displays, contact factory.

 

 

Make sure that the process connection is not pressurized and is open to atmosphere to reset 

to 0 PSIG. If the zero pressure is adjusted with pressure, it can be calibrated up to 5% of the 

full span (i.e. 5 PSI for a 100 PSI transmitter). “Zero adjustments above or below 5% will 

result in an “

OUT OF RANGE

” condition displayed on the LCD.

 

 

Press the “Zero” button until the display reads “

ZERO

”. The AST46DS will then read 0.0 for 

pressure units if the calibration was started in units, 1.000 for a 1-5V output, or 4.00 for a 4-

20mA output. (Compound and bi-directional transmitters will “zero” to the factory calibrated 

zero offset).

 

 

Re-install the front display cover.

 

Units

 

 

Ensure the product is in a non-hazardous environment.

 

 

Remove the front display cover to access the “Units” button.

 

 

Connect the AST46DS using standard wiring instructions with an 8-28VDC power supply.

 

 

Press the Units” button to cycle between the display options until you reach the desired units.

 

 

Re-install the front display cover.

 

Over Pressure Display 

At 5% over-pressure, the display will begin to blink at 1/2Hz.

 

Removing Power 

 If you power off AST46DS, it will default back to the last setting for the display and zero 

calibration.

 

 

 

 

 

 

 

NORTH AMERICA 

 

 

Measurement Specialties, Inc., 
a TE Connectivity Company 
6801 Kaiser Drive 
Fremont, CA, 94555 
Tel +1 800 522 6752 
[email protected] 

 

 

te.com/sensorsolutions

 

Measurement Specialties, Inc., a TE Connectivity Company.

 

AST, TE Connectivity, and TE connectivity (logo) are trademarks. All other logos, products and/or company names referred to herein might be trademarks of their respective owners.

 

The information given herein, including drawings, illustrations and schematics which are intended for illustration purposes only, is believed to be reliable. However, TE Connectivity makes 

no warranties as to its accuracy or completeness and disclaims any liability in connection with its use. TE Connectivity‘s obligations shall only be as set forth in TE Connectivity‘s Standard 

Terms and Conditions of Sale for this product and in no case will TE Connectivity be liable for any incidental, indirect or consequential damages arising out of the sale, resale, use or misuse 

of the product. Users of TE Connectivity products should make their own evaluation to determine the suitability of each such product for the specific application.

 

© 2016

 

TE Connectivity Ltd. family of companies

 

All Rights Reserved. 

 

 

 

 

 

  

 

 

 

    

Rev 00

 

06.22.2016

 

Отзывы: