4.

 

DISCONNECT PIGTAIL CONNECTOR 83471-1 (Live Line Connector) 

4.1.

 

Installation 

1.  Before installation ensure that the sliding wedge is secure in the connector body and moves easily on 

the thread. 

2.  Turn eyebolt counterclockwise until wedge bottoms against body. 

3.  Bolt the jumper cable terminal to the NEMA pad. 

CAUTION 

Installation torque not to exceed 54.2 Nm [40 ft-lb] for ½ inch silicone bronze hardware. 

4.  Using a hot stick, grip disconnect eyebolt, and secure disconnect assembly utilizing the stabilizing ribs 

as shown in Figure 5. 

Figure 5 

Wedge 

Position Wedge 

and Tap in Place 

Tool 

Install Tap 

Disconnect Pigtail 

Connector 

Stabilizer Ribs in 

Hot Stick Grooves 

 Hot Stick 