LZS-A
A500-33 Power Supply
This manual is a description of specifications, features and applications of LZS-A500 power supplies.
RATINGS AND SPECIFICATIONS *
Maximum Ratings
Units
LZS-A500-3
Table 2
Output Voltage Range
V
18-29.4
Output Current (Power) @ 60°C**
A(W)
21 (504)
DC Output @ 24V
Output Current (Power) @ 70°C**
A(W)
12.6 (302)
Operating Temperature
°C
100% rated load from -30°C to 60°C derate linearly to
60% @ 70°C (4%/°C)
Start-up Temperature
°C
-40° to +70°
Input Specifications
Units
LZS-A500-3
Table 3
Input Voltage Range***
VAC
85-265 (47-440Hz) Single Phase
VDC
100-380
Input Current (RMS, maximum)
A
8 RMS
Inrush Current (Peak, at cold start)
A
25A /110VAC; 45A / 220VAC
Power Factor Harmonics
-
EN61000-3-2 Compliant
Power Factor (at max output power)
-
0.99 typical @ 85VAC
Input Power (maximum)
W
615W @ 21A (504W) and 85VAC line
Input Surge Protection
-
1kV Differential Mode; 2kV common mode
Input EMI Conducted Emissions
-
FCC Class B, CISPR 22 Class B
Efficiency (at max.output power)
%
84 typical @ 110VAC line
Output Performance Specifications
Units
LZS-A500-3
Table 4
Voltage Line Regulation
%
0.1
Voltage Load Regulation
%
0.1
Ripple and Noise @ 20 MHz
measurement Bandwidth.
(PARD-mVP-P)
75
Temperature Coefficient
%/°C
.01
Startup Time (at 110 VAC input)
Sec.
Less than 1 second
Overshoot
mV
No overshoot at turn on or turn off
Holdup Time (Full Power/220VAC)
mS
10
Ride through (Full Power/220VAC)
mS
20
Voltage Sag Immunity
(Full Power/110VAC)
-
Semi-F47 compliant
Load Transient Response
+/-1% of Vo ; 1A/
µ
S; Recovers to within
(25% step load change)
-
+/-0.2% in < 1.25 mS
* Refer to figures 1-7 for supply-load connection information.
** Output current and power, as measured at output terminals, must be less than or equal to
quoted maximum values for a given ambient temperature.
*** Regulatory agency compliance applies only for operating frequencies between 47-63Hz.
No safety agency approvals for 100-380 VDC operation. Minimum turn-ON voltage for
DC Input is 110 VDC, unit will operate as low as 65 VDC after Power-up. Lambda doesn’t
recommend operation below 100 VDC for more than one minute, or damage may occur.