5-11. Parallel Operation 

Current balancing function is provided. There are 3 operation modes possible which is (A), (B) and (C).   

(A)To Increase the Output Current 

Current balancing function activates by connecting PC-to-PC terminal and COM-to-COM terminal, and output current 

of each power supply is equivalently supplied to load. Wires to PC terminals shall be as short as possible, same length 
and twisted. 

There is a possibility that output could be unstable caused by external noise. For this case, disconnect COM terminal 

and connect -S terminal from parallel power supply to a single point on the load. Please refer connection Method (A)-2. 

1. 

 

Adjust the output voltage of each power supply to be same value within 1% or 100mV, whichever is smaller. 

2. 

 

Use same length and type of wires for all load lines. 

3. 

 

Maximum value of output current in parallel is up to 80% of all paralleled models. The purpose of the current       

balancing  function  is  the  static  power-up.  Therefore  the  output  voltage  might  decrease  according  to  the 
condition of dynamic load. There might be a step in the rise waveform during parallel operation. 

4. 

 

Up to 5 units can be connected in parallel. 

(B)To Use as a Backup Power Supply 

1. 

 

Set power supply output voltage higher by the forward voltage drop of diode. 

2. 

 

Adjust the output voltage of each power supply to be same value. 

3. 

 

Use within the specifications for output voltage and output power. 

 

(C)In the case of parallel connections, it is possible to control the output voltage by adjusting the volume from only 1 
unit. Choose 1 unit that would act as the master and this unit’s volume will determine the output voltage. The volume on 
each slave units must be turned clockwise to maximum position. Then adjust the master volume to set the output voltage. 

Connection for this application is shown in figure (c).

 

 

 

       

   

 

 

                                                                                         

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Method (B) 

 

Power Supply

 

Load

 

Io

 

Vf

 

Vf

 

 

Vo

 

Vo+Vf

 

Vo+Vf

 

Output Power(W)=(Vo+Vf)

 

×

Io

 

+S  

 

-

 

 

+S  

 

-

 

 

 

PC  

 

 

+S  

 

-

 

 

-

 

 

PC  

Load  

 

Power Supply  

 

+S

COM 

 

COM 

 

Method (A)-2 

Method (A)-1 

 

PC  

 

+S  

 

+S  

 

-

 

 

-

 

 

PC  

 

Load  

 

Power Supply  

 

COM 

COM 

Method (C) 

Power Supply

 

Load

 

 

+S

-S

 

PC 

COM 

PV 

REF 

REF  PV  COM  PC 

+S

-S

 

Содержание HWS 1500 Series

Страница 1: ...changed or dis assembled Do not use this product under unusual condition such as emission of smoke or abnormal smell and sound etc Please stop using it immediately and shut off the product It might le...

Страница 2: ...lity of product failure or malfunction Provide countermeasure for prevention of lightning surge voltage as there is risk of damage due to abnormal voltage Connect together the frame ground terminal of...

Страница 3: ...anical stress applied directly to the product Please keep away from direct sunlight For long term storage temperature and humidity the following conditions shall be used as a guideline Temperature ran...

Страница 4: ...e the shielded wire Remote ON OFF control lines shall be twisted or use the shielded wire 2 1 Front Panel Explanation HWS1500 Front Panel Output terminal Output terminal ON Output Power On indication...

Страница 5: ...sensing function is unnecessary 5 PC Current balance terminal For output current balancing in parallel operation 6 COM Ground for PC and PV signal 7 PV Output voltage external control terminal For po...

Страница 6: ...terminal with wire Please use attachment connector for each connection In the following cases the output is shut down When CNT and TOG is opened When PV and REF is opened Attached connector when ship...

Страница 7: ...circuit with CN01 or CN02 connector of load of load M8 Bolts and nuts for connecting to the load line These are not attached to the product Connector JST S12B PHDSS Remove standard attached connector...

Страница 8: ...ched to the product Connector JST S12B PHDSS Remove standard attached connector and use the harness made by the customer Housing JST PHDR 12VS Contact JST SPHD 001T P0 5 3 7V model 2 of output 4 of ou...

Страница 9: ...Output CNT TOG Remote ON OFF Control S S COM PV Output Current Balance PC PF Standby supply Latch Circuit OVP Circuit UVP Circuit Low output Voltage Detection Photo coupler Delay Circuit Output Sensin...

Страница 10: ...P FAN ALM ACTION SHUT DOWN 1 Level 2 4V H 12V or Open 0V L 0 8V or Short 2 OVP Point 3 7V 125 140 12V 15V 24V 125 145 36V 125 138 48V 115 135 60V 115 125 3 OCP Point 6V 7V 24V 36V 60V Model Input volt...

Страница 11: ...shutdown type is provided OCP function operates when the output current exceeds 105 of maximum DC output current specification and the over current or short circuit condition continues 5 second or mo...

Страница 12: ...t is connected The output is turned to ON when TOG and CNT terminals are shorted and output is turned to OFF when these terminals are opened When the function is not used connect TOG and CNT terminals...

Страница 13: ...pe is too long 5 10 Series Operation For series operation either method A or B is possible There might be a step in the rise waveform during series operation Note1 Please connect a diode for by pass w...

Страница 14: ...alancing function is the static power up Therefore the output voltage might decrease according to the condition of dynamic load There might be a step in the rise waveform during parallel operation 4 U...

Страница 15: ...een output and CNT PF shall be more than 10MW at 100VDC For safety operation voltage setting of DC isolation tester must be done before the test Ensure that it is fully discharged after the test CNT T...

Страница 16: ...ly may be damaged by high impulse voltage at timer switch on and off Connect input and output as follows If output is left open during test output voltage might appear momentarily This product have mo...

Страница 17: ...from 30 to 120 at the PV voltage is from 1 5V to 6 0V Note Only as for the model of 5 36V output the output voltage is used from 20 to 120 at the PV voltage is from 1V to 6 0 V Note Only as for the mo...

Страница 18: ...nnector after input is cut off 4 Connect external variable resistor 50kW between REF terminal and COM terminal Then connect middle point of external variable resistor to PV terminal sensing current is...

Страница 19: ...the above contents prior to operation For application that requires output voltage below 20 due to different type of application for the user s system there might be a situation behavior different fr...

Страница 20: ...sty environment 4 Built in fan is limited life part which require periodic replacement Replacement will be charge 5 The ambient temperature of this power supply is less than 50mm from the center of a...

Страница 21: ...or safety purposes connect protective earthing terminal to the mounting set ground terminal 6 Recommended torque for the terminal piece 7 Recommended wiring Recommended circuit protector AC250V30A Rec...

Страница 22: ...minal connection is properly tighten by a regulated tightening torque 4 Check if the wire material is not too thin 5 Check if the output voltage control V ADJ is properly adjusted OVP might be trigger...

Страница 23: ...iance with the Low Voltage Directive EMC Directive and RoHS Directive UKCA MARKING UKCA Marking when applied to a product or packing material for a product covered by this handbook indicates complianc...

Отзывы: