3. Disassemble the beam to allow easy access into the cabinet as shown in Figure 4-7.
Figure 4-7: Rear Panel Disassembly
4.7
AC Input Power Connection
This Power System has protective device (circuit breaker) which disconnect each current-carrying
conductors with the following ratings:
2x 80A for 30kW 3-Phase 208Vac.
3x 80A for 45kW 3-Phase 208Vac.
4x 80A for 60kW 3-Phase 208Vac.
2x 40A for 30kW 3-Phase 480Vac.
1 X 80A and 1 X 40A for 45kW 3-Phase 480Vac.
2x 80A for 60kW 3-Phase 480Vac.
CAUTION
The Power System shall be electrically connected to a supply by either means of permanent
connection, which can be detached only by the use of a tools or by connector meeting the
requirements of IEC 60309. Connection of this Power System to an AC mains should be made by an
electrician or other qualified personnel in accordance with local electricity standards, rules and
regulations.
CAUTION
There is a potential shock hazard if the power system is not connected to an electrical safety ground
via the safety ground terminal in the AC input connector.