INSTRUCTION MANUAL
DRJ15100
Series
TDKLambda
<Page>
12/14
♦ DRJ100
Mounting
(
A
)
Mounting
(
B
)
8. Internal Fuse Rating
Fuse is in Live line.
DRJ series uses timelug fuse.
DRJ15, DRJ30 : AC250V, 2.5A
DRJ50, DRJ100 : AC250V, 3.15A
9. External Fuse Rating
Refer to the following fuse rating when selecting the external input fuse.
Surge current flows when input turn on. Use slowblow fuse or timelug fuse. Fastblow fuse can not be used.
Fuse rating is specified by inrush current value at input turn on.
Do not select the fuse according to actual input current (rms.) values.
DRJ15, DRJ30 : 2.5A
DRJ50, DRJ100 : 3.15A
10. Power supply mounting on DIN RAIL
DRJ series conforms to TS35 size of DIN standard, the width of mounting rail is 35mm.