HANDBOOK FOR CPFE500F SERIES                   

61006

Issue2

Page 1

GENERAL SAFETY INSTRUCTIONS

High Voltage Warning

Dangerous voltages are present within the power supply.

Critical Components

This product is not authorised for use as a critical component in nuclear control systems, life
support systems or equipment for use in hazardous environments without the express written
approval of the Managing Director of TDK-Lambda UK Ltd.

Servicing

This product is not customer serviceable.
Unit repairs shall only be carried out by TDK- Lambda UK Ltd or their authorised agents.

Contact: TDK-Lambda UK Ltd

Kingsley Avenue
Ilfracombe
Devon, EX34 8ES
Tel 01271 856600
Fax 01271 864894

Safety Class of Protection

The unit is designed for the following parameters : Material Group IIIb, Pollution Degree 2,
Overvoltage Category II, Class 1 (earthed), Indoor use. The unit is considered as fixed and
rated IPX0.  The CPFE500F-12 and CPFE500F-24 are classed as having SELV outputs.
The CPFE500F-48 is classed as having a NON SELV output. All outputs are capable of
providing hazardous energy (>240VA). The final equipment should provide protection to
service personnel against inadvertent contact with the PSU output terminals.

Installation

This product is designed for use within other equipment which restrict access to authorised
competent personnel only. The unit covers/chassis must not be made user accessible.
The appliance may be mounted in any orientation except inverted (baseplate uppermost).
The customer has to ensure the baseplate temperature remains below certain limits.
Horizontal orientation input 90-149V baseplate temperature limited to 75°C.
Horizontal orientation input 150V or greater baseplate temperature limited to 85°C.
All other orientations baseplate temperature limited to 85°C.
With open frame version, any orientation is permitted at 85°C baseplate temperature.
The mains input connector is not acceptable for use as field wiring terminals.
The appliance must be securely mounted and the baseplate properly bonded to the main
protective earth contact before any connection to AC mains supply is made.
The ventilation openings must not be impeded – ensure a space at least 5cm between any
obstruction and the ventilation openings.

Environmental Parameters

Operation

Storage & Transportation

Temperature

-40

0

C to +50

0

(note 1,2)

-40

0

C to +85

0

C

Humidity

30% to 90% RH, non-
condensing

10% to 95% RH, non-condensing

Air Pressure

70kPa to 106kPa

54kPa to 106kPa

Altitude

-200m to 2000m

-200m to 2000m

* Note 1 – heatsinking must be provided to ensure the PSU baseplate temperature does not exceed 85DegC (see diagram for measurement location)

and installation notes.

* Note 2 – For 3 year life expectancy,  continuous temperature of electrolytic capacitors should not exceed :- 

C11,12,25,26  67.5°c

C22,23,16,17  81°c

Level of Insulation

Primary mains circuit to earth

2.25~2.35KVDC

Primary mains circuit to output

4.25~4.35KVDC

Output to earth

500VDC max

Input Parameters

Maximum input voltage range

85 – 265VAC 

(note 3)

Nominal input voltage range

100 – 240VAC

Input frequency range

47 – 63 Hz 

(note 3)

Maximum input current

8.2Arms

Earth leakage

1650µA Max

Efficiency (25°c,100% Load)

80% min

* Note 3 - In cases where conformance to various specs (UL, EN) are required, input voltage range will be 100~240VAC(50/60Hz).

Output Parameters

CPFE500F-12

CPFE500F-28

CPFE500F-48

Nom output Voltage

12VDC ± 1%

28VDC ± 1%

48VDC ± 1%

Max adjust range 

(note 4)

9.6-14.4V

22.4-33.6V

38.4-57.6V

Maximum output
current

42A

18A

10.5A

Overcurrent protection

105-140%

105-140%

105-140%

Overvoltage
Protection

125-145% latched
shutdown

125-145% latched
shutdown

125-145% latched
shutdown

Over-temp Protection

Latched Shutdown
at 90~115°C
baseplate
temperature

Latched Shutdown
at 105~130°C
baseplate
temperature

Latched Shutdown
at 105~130°C
baseplate
temperature

* Note 4 - Max output power is limited to 504W