Explanations on Specifications 

 

1. Input Voltage Range 

  Input  voltage  range  for  CN100A24  Series  is  indicated 
below.     

 

Input Voltage Range : 14.4 - 36VDC 

 

  Ripple voltage (Vrpl) which results from rectification and 
filtering of commercial AC line is might be included within 
the input voltage as shown in Fig. 1-1. In this case, ripple 
voltage  must  be  limited  within  the  voltage  described   
below. 

 

Allowable Input Ripple Voltage : 2Vp-p 

 
  When this value is exceeded, the output ripple voltage 
becomes large. 

  Take note that sudden input voltage change might be 
cause variation of output voltage transitionally.   

  Also,  input  voltage  waveform  peak  value  must  not 
exceed above input voltage range.   
 
 

 

 

 
 
 
 
 
 
 
 
 
 
 

Fig.1-1 Input Ripple Voltage 

 
 
 
 

Basic Connection 
 
 

 
 
 
 
 
 
 
 
 

Fig.1-2 Basic Connection 

 

 
 

Input Fuse 

  This power module has no built-in fuse. Use external fuse 
to acquire various Safety Standards and to improve safety. 
  Also,  use  fast-blow  type  or  normal-blow  type  for  every 
module.   

  Furthermore, fuse must be connected to the +Vin side 
if  –Vin  side  is  used  as  ground,  or  fuse  must  be 
connected to –Vin side if +Vin side is used as a ground.   

 

Input Fuse Recommended Current Rating :   

CN100A24 : 15A 
CN50A24 :    8A

 

C1 : 

  To  prevent  the  effect  of  input  line  inductance  to  the 
power  module,  connect  electrolytic  capacitor  between 
+Vin and –Vin terminals.   
  Furthermore, use electrolytic capacitor  with  low  ESR 
value.  Especially  take  note  that  during  line  turn  off  at 
low ambient temperature, power module output will not 
normally shut down.   
 

Recommended Capacitor Value : 470

μ

F and above 

                            (Voltage Rating 50V and above) 

 

Notes 

1.

 

  Use  low  impedance  electrolytic  capacitor  with 
excellent temperature characteristics. 

(Nippon Chemi-con LXY Series or equivalent) 

 

2.

 

  Use  more  than  two  recommended  capacitor 
above  in  parallel  when  ambient  temperature 
becomes lower than –20

  to reduce ESR. 

 

3.

 

  When input line inductance becomes excessively   
high due  to  insertion  of  choke  coil,  operation  of 
the  power  module  could  become  unstable.  For 
this case, increase C1 value more than the value 
indicated above. 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fuse

CN-A24

+Vin

-Vin

+V

-V

+S

-S

TRM

Base-plate

CNT

C1

C3

C2

+

-

Load

Vrpl 
2V   
or lower 

Содержание CN-A24 Series

Страница 1: ...t Voltage Range as specification Insulation failure smoking burning or other damage might occur to the unit Do not use this product in environment with a strong electromagnetic field corrosive gas or...

Страница 2: ...Protection OVP 9 Over Temperature Protection OTP 10 Remote Sensing S S terminal 11 ON OFF Control CNT terminal 12 Redundant Operation 13 Parallel Operation 14 Series Operation 15 Operating Ambient Tem...

Страница 3: ...a 2 TDK Lambda CN A24 Series Instruction Manual Block Diagram Sequence Time Chart Vin Vin CNT V V TRM S S 5V model Only 5V model Only Switching frequency fixed 360kHz...

Страница 4: ...tput Terminal CNT ON OFF Control Terminal S Remote Sensing Terminal Vin Input Terminal TRM Output Voltage Trimming Terminal S Remote Sensing Terminal V Output Terminal Base plate can be connected to F...

Страница 5: ...for every module Furthermore fuse must be connected to the Vin side if Vin side is used as ground or fuse must be connected to Vin side if Vin side is used as a ground Input Fuse Recommended Current...

Страница 6: ...an 20 to reduce ESR 3 Take note of the allowable ripple current of the capacitor to be used Especially when load adding capacitors for abrupt current changes be sure to verify that ripple current does...

Страница 7: ...higher 2 1 Allowable maximum output current maximum output power adjusting output voltage Becomes less than maximum output current of specification 2 2 Connect an external resistor Radj up between TRM...

Страница 8: ...voltage Note Please connect the amplifier so as not to interfere in internal impedance of the trim circuit when you apply the external voltage For applications other than the above refer to the TRM c...

Страница 9: ...he rated output voltage value When output voltage exceed OVP set point output voltage shut down OVP setting value is fixed and therefore cannot be externally adjusted When OVP is triggered output can...

Страница 10: ...erminal 3 At L level source current from CNT terminal to Vin terminal is 0 4mA 0 5mA 4 The maximum CNT terminal voltage is 35V 1 Output ON OFF control Fig 11 1 CNT Connection 1 2 Secondary output side...

Страница 11: ...en temperature changes can cause condensation buildup and other harmful affects to each terminal solder 18 Storage Ambient Humidity Take enough care when storing the power module because rust which ca...

Страница 12: ...put output Capacitor ratio of Input FG C4 C5 and Output FG C6 C7 C4 C5 C6 C7 1 1 3 1 5 Fig 20 4 Example of connecting external application 21 Isolation Resistance Use DC isolation tester MAX 500V betw...

Страница 13: ...on pattern will increase because of voltage drop of pattern Relationship between allowable current and pattern width varies depending on materials of printed circuit board thickness of conductor It i...

Страница 14: ...110 C for 30 40 seconds 2 Soldering iron 350 C within 3 seconds Note Soldering time changes according to heat capacity of soldering iron pattern on printed circuit board etc Please confirm actual perf...

Страница 15: ...s For cases where output voltage adjustment is used is the resistor or volume setting connections correctly done 3 Output voltage is low Is specified input voltage applied Are the remote sensing termi...

Страница 16: ...1 CN A24 HAQ 10T 57 9 25 4 36 8 7 5 W 1 at convection cooling 1 For CN A24 1 HAQ 10T Convection cooling Thermal resistance 7 5 W Forced air cooling L C C L 12 R0 5 57 9 1 0 49 7 0 2 36 8 0 3 28 0 0 2...

Отзывы: