Wiring                                      

The SZ2165 terminal designations are shown below.

Remote SenSoR WiRing

The SZ2165 accepts six 1000 

 two-wire platinum sensors. Consult 

the TS Series Temperature Sensor submittal datasheet for a com-

plete listing of packaging and application styles. When using TCS 

Basys Controls three-wire sensors, use the black and red leads, and 

either clip or twist off the white lead. The wiring length should not 

exceed 250 feet.

1

Black

Red

Black

Red

Black

Red

Black

Red

Black

Red

Black

Red

MIXING VALVE

+

-

A

B

AO1

GND

DI1
DI2

POWER

GND

GND

GND

AO2

24

VAC

GND

DI4

DI3

DI5

SZ2165

BOILER CONTROLLER

ANALOG

OUTPUTS

DIGITAL

INPUTS

PUMP

BOILER PUMP1

BOILER PUMP2

OVERRIDE

BOILER/

CHILLER

CHILLER PUMP

NO1
COM

COM

COM

COM

COM

COM

B

NO2

NO3

A

NO9

NO8

NO7

NO6

NO5

COM

NO4

TEMPERATURE INPUTS

HOT WATER

SUPPLY RETURN

CHILLED WATER

SUPPLY RETURN

OUTDOOR

MIXED

WATER

S

U

P

e

R

t

R

o

L

tm

KBPS

4.8

9.6

19.2

BOILER4

BOILER3

BOILER2

BOILER1

ALARM

CHILLER2

CHILLER1/

ENABLE

BOILER PUMP1

BOILER PUMP2

DIGITAL

OUTPUTS

ALARM

CHILLER2

CHILLER1/ENA

BOILER PUMP1

BOILER PUMP2

BOILER1

BOILER3

BOILER2

BOILER4

POWER

OVERRIDE

OCC

SERVICE

DATA

+P

AI1

PRESSURE

ANALOG

INPUTS

T

1

T

1

T

2

T

2

T

3

T

3

T

4

T

4

T

5

T

5

T

6

T

6

+

-

+

+

+

XMTR

4

4

REF

2-wire, 4 to 20 mA transmitter.Sensor input 

wiring 18 AWG, twisted, shielded pair.  

7

Dry contact. Must not be powered.

4

Sensor input wiring 18 AWG, twisted, shielded pair.

3

For communication wiring, use twisted, shielded 22 

AWG. Must be run separately.

1

24 VAC transformer. See powering instructions.

2

External relay. 24 VAC Coil

5

4 to 20 mA output. 600 ohm max. Do not power 

actuator with power from the controller.  The 

controllers are half-wave rectified, whereby the 

power ground is common with the signal ground.

6

ReF

Add 500 ohm

 resistor (included in bag) to 

convert 0/4 to 20mA to, 0/2 to 10 VDC. 

8

3

3

3

3

3

3

R

R

R

R

R

R

R

R

5

R

2

5

5

5

5

5

5

5

5

6

6

PA

VA

7

4

4

4

2

8

8

PoWeRing the SZ2165

The SZ2165 is powered from 24 VAC +/- 20 %. If wiring for com-

munications, dedicated power must be used to power the SZ2165. 

Several S-series controllers may be powered from the same trans-

former, provided that the transformer has enough power.

Caution:

 Do not connect to 120VAC. When multiple TCS/Basys 

Controls devices are using a single transformer, the polar-

ity of the power wiring must be maintained because all 

TCS devices are half-wave rectified and have common 

return paths.

Содержание SZ2165

Страница 1: ...utdoor air reset control Two digital inputs for pump status External time clock input Six digital outputs for boilers and boiler pumps Adjustable offsets and differentials on digital outputs Lead Lag...

Страница 2: ...ILER PUMP2 BOILER1 BOILER3 BOILER2 BOILER4 POWER OVERRIDE OCC SERVICE DATA P AI1 PRESSURE ANALOG INPUTS T 1 T 1 T 2 T 2 T 3 T 3 T 4 T 4 T 5 T 5 T 6 T 6 XMTR 4 4 REF 2 wire 4 to 20 mA transmitter Senso...

Страница 3: ...chedule and 0 00 to 0 00 for the B schedule 0 00 12 00AM starts the day and 24 00 12 00AM ends the day Note occupied times that span midnight have to be coordi nated using two days time schedules NOTE...

Страница 4: ...or a 1 hour maximum after which the boiler pump will turn back on and the unit will function normally DI5 can be used for Chiller Pump Proving or Monitoring If Chiller Pump Proving is selected the con...

Страница 5: ...n outdoor air reset schedule If the outdoor air temperature is 0 F the hot water tem perature is controlled at 200 F If the outdoor air temperature is 60 F the hot water temperature is controlled at 8...

Страница 6: ...enable rotation based on runtime then enter the time between change 5 hours to 1000 hours BOILER STAGES Select the number of Boiler Stages that will be used in the Boiler Stage Rotation If using 4 st...

Страница 7: ...nal to help the system stabilize The Error Deadband is typically 0 It is pre dominantly used in a situation where a small amount of error would cause a large swing in the output or response for exampl...

Страница 8: ...rate selection jumper for the QD1010 and the SZ2165 are the same and that Revelation is configured for that same baud rate Address 248 will always work provided that the SZ2165 is NOT connected to a...