2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

1

SZ2165

Boiler Controller

Product Manual           

Description                                        

The SZ2165 is a microprocessor based boiler controller. It is 

designed for use on multi-stage boiler applications and includes 

chiller support and control.

  

Features                                           

•  Stand-alone or network operation

•  365-day time clock with two holiday schedules, automatic leap 

year and daylight saving correction

•  No backup battery required for control parameters, schedule or 

clock

•  Hot water supply and return water temperature inputs

•  Mixed water temperature input

•  Chilled water supply and return temperature input

•  Two digital outputs for chillers

•  One digital output for alarm

•  Outdoor air temperature input

•  Outdoor air reset control

•  Two digital inputs for pump status

•  External time clock input

•  Six digital outputs for boilers and boiler pumps

•  Adjustable offsets and differentials on digital outputs

•  Lead/Lag sequencing (rotation) of up to four boilers

•  Two modulating analog outputs for valves and VFD

•  LEDs for monitoring status

•  Automatic rotation of pumps

•  Alarm output

•  Selectable normally open or normally closed relay outputs

Contents                                           

Description

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Features

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Mounting

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Wiring

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

Setup

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Programming

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Sequence of Operations

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

Checkout & Troubleshooting

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

LED Description

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

Mounting                                           

The SZ2165 is designed for mounting using four #10 sheet metal 

screws. Prior to mounting, the jumpers should be placed. (See setup 

instructions.) If the unit will be stand-alone, all programming should 

be completed before installation. If the unit will be wired for communi-

cations, a unique address should be programmed into the unit. (See 

programming instructions.)

Содержание SZ2165

Страница 1: ...utdoor air reset control Two digital inputs for pump status External time clock input Six digital outputs for boilers and boiler pumps Adjustable offsets and differentials on digital outputs Lead Lag...

Страница 2: ...ILER PUMP2 BOILER1 BOILER3 BOILER2 BOILER4 POWER OVERRIDE OCC SERVICE DATA P AI1 PRESSURE ANALOG INPUTS T 1 T 1 T 2 T 2 T 3 T 3 T 4 T 4 T 5 T 5 T 6 T 6 XMTR 4 4 REF 2 wire 4 to 20 mA transmitter Senso...

Страница 3: ...chedule and 0 00 to 0 00 for the B schedule 0 00 12 00AM starts the day and 24 00 12 00AM ends the day Note occupied times that span midnight have to be coordi nated using two days time schedules NOTE...

Страница 4: ...or a 1 hour maximum after which the boiler pump will turn back on and the unit will function normally DI5 can be used for Chiller Pump Proving or Monitoring If Chiller Pump Proving is selected the con...

Страница 5: ...n outdoor air reset schedule If the outdoor air temperature is 0 F the hot water tem perature is controlled at 200 F If the outdoor air temperature is 60 F the hot water temperature is controlled at 8...

Страница 6: ...enable rotation based on runtime then enter the time between change 5 hours to 1000 hours BOILER STAGES Select the number of Boiler Stages that will be used in the Boiler Stage Rotation If using 4 st...

Страница 7: ...nal to help the system stabilize The Error Deadband is typically 0 It is pre dominantly used in a situation where a small amount of error would cause a large swing in the output or response for exampl...

Страница 8: ...rate selection jumper for the QD1010 and the SZ2165 are the same and that Revelation is configured for that same baud rate Address 248 will always work provided that the SZ2165 is NOT connected to a...

Отзывы: