background image

8. Press the cooler button until the cooling setpoint is 

less than the current temperature by at least five 

degrees. The fan will come on.  The cooling stage(s) 

will sequence on after 30 seconds. 

9. Press the warmer button until the cooling setpoint is 

greater than the current temperature by one degree. 

The cooling stage(s) will sequence off. The fan will 

turn off 30 seconds after the last cooling stage.

10. Take note of the room (and discharge) air tem-

peratures. If the analog output is set for Cooling, 

press the Cooler button until the cooling setpoint is 

less than the current room temperature by at least 

5°. The cooling device should start operating. If the 

analog output is set for Heating, press the Warmer 

button until the heating setpoint is greater than the 

current room temperature by at least 5°. The heating 

device should start operating.

11. Go back to programming step #14 and set the 

setpoint adjust limit back to the desired value. Make 

any other changes in programming, clock, and 

schedule. Set the fan and system modes to their 

desired settings. 

12. If using remote sensors, verify that the reading is 

correct. If not, see 

Wrong Temperature Display 

in 

“Troubleshooting” section.

TROUBLESHOOTING
No Display

Check for 24 VAC on terminals “+24” and “-24”. Check 

the cable connecting the cover to the base for a good 

connection.

Fan Does Not Come On

The fan is on whenever the fan LED is on. If the fan 

should be on, but the fan LED is off, check the fan and 

system switch modes, and the unoccupied fan mode 

in programming. If the fan is off but the fan LED is on, 

check wiring. Short terminals “R” to “G” and see if the 

fan comes on. This is a check for a mechanical relay 

failure. 

 

Heating or Cooling Does Not Come On

At least one stage of heating is on whenever the  heating 

LED is on, and at least one stage of cooling is on when-

ever the cooling LED is on. If heating or cooling should 

be on but the heating or cooling LED is off, check the 

fan and system switch modes. Also, check the heating 

and cooling setpoints, offsets and differentials, and the 

room temperature to be sure heating or cooling should 

be on. If using outdoor air heating and cooling lockouts, 

or discharge air high and low limits, check their values to 

be sure heating or cooling is allowed. If heating or cool-

ing is off, but the corresponding LED is on, check the 

wiring. Short terminals “R” to “Y/W1” or “Y/W2” and see 

if the heating or cooling comes on. This is a check for a 

mechanical relay failure.  

Wrong Temperature Display

Initially, verify the wiring connections to check for prob-

lems (poor connections, opens, or shorts). If the tem-

perature is at a minimum or maximum reading, check 

that the sensor dipswitch positions are correct as shown 

in the Setup section of this document. Also, verify the 

resistance reading for the sensor in question. A remote 

sensor should read 1080 to 1090 ohms at room tem-

perature. The built-in sensor should read 108 to 109 

ohms at room temperature. If any of the temperatures 

are still reading slightly high or low, you can add in a 

temperature offset (calibration) using Ubiquity or TCS 

Insight. In Ubiquity, you can edit the calibration offset 

for each temperature input (room, discharge, outdoor 

air, etc.) on the controller's programming page. For 

example, if the room temperature is reading 2 degrees 

high, you would subtract 2 from the existing offset in 

the room temperature calibration offset field and submit 

the page. In TCS Insight, the process is similar. Refer 

to the Calibrate Using TCS Insight Tech Bulletin # 1019 

for details. As a last resort and only when directed to do 

so by TCS technical support, you may be able to use 

the on-board adjustment pots. Refer to the Thermostat 

Sensor Calibration Tech Bulletin # 1005 for details.

T1

T2
T3

1  2

1  2  3  4  5

adjust display contrast

Service LED is On

If the service LED is on, it may be for monitoring purpos-

es or it may indicate a critical problem. The first monitor-

ing screen accessed by pressing the service status but-

ton will display why the light is on.

 

Outputs Will Not Shut Off

First check the room temperature and the setpoints and 

determine whether the output should be on. There are 

delays and minimum on and off times for the fan and 

heating and cooling stages. Also, check the service 

status menus to verify that the outputs are on. Turning 

the system to “off” will instantly turn all outputs off. The 

thermostat can be reset by pressing the system switch 

button and the service status button simultaneously.  
 

Analog Output Not Working Properly

Check wiring. A separate transformer should be used for 

the SZ1018 and a separate transformer should be used 

for the damper motor(s). Check to make sure that the 

analog output is programmed correctly.
Check the Service Menu. The Mod Out Screen will tell 

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

11

Содержание Superzone SZ1018

Страница 1: ...t Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Digital or analog changeover Product Manual Contents Descripti...

Страница 2: ...devices SZ1018 thermo stats require 8 VA 24 VAC When the SZ1018 are used as a stand alone thermostat without communications the unit transformer may be used to power it However using separate power wi...

Страница 3: ...h the two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting sectio...

Страница 4: ...s the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is entered it will revert to the previous screen Contro...

Страница 5: ...reen Enter whether you want to control by temperature only P or add a time factor P I This is applies to both the stage outputs Time Clock Output Screen Choose whether the auxiliary output will be OPE...

Страница 6: ...Choose whether to control based on DISCHARGE air reset or SPACE temper ature This screen will not appear if the discharge air sensor function is disabled Set to SPACE if this stat will be used within...

Страница 7: ...n Monitoring Screen Setting Clock Schedule The SZ1018 clock and schedule may be set through the keypad on the face or with a PC For more infor mation on programming through the PC consult your softwar...

Страница 8: ...ge air tempera ture will be controlled to this setting by modulating the heating or cooling device Operation UNOCCUPIED SETBACK The SZ1018 operate in either an occupied or unoc cupied mode During the...

Страница 9: ...s required which indicates when the fan is running If the thermostat turns on the FAN and DI1 is not closed after thirty seconds the system will go to OFF disabling all outputs the fan LED will turn o...

Страница 10: ...parameters for analog output 2 Select whether the analog output is set for heating cooling or aquastat Select direct or reverse action Select whether you want the analog output to modulate from 4 to 2...

Страница 11: ...k the wiring Short terminals R to Y W1 or Y W2 and see if the heating or cooling comes on This is a check for a mechanical relay failure Wrong Temperature Display Initially verify the wiring connectio...

Страница 12: ...tatus service status 7 MOD OUT 2 100 OPEN service status MOD OUT 2 Screen Shows the percentage of modulating output 2 DI2 and DI3 Status Screen Shows DI2 status and filter status or DI3 status Main Mo...

Страница 13: ...up section PROGRAMMING The ability to program control parameters is allowed by fac tory default An access code may be required as set in pro gramming step 43 or access may be denied altogether using d...

Отзывы: