background image

Description                             

The SZ1018 are specifically designed for the Superzone 

Commercial Zoning System (Superzone CZS). The 

SZ1018 have a 7-day time clock and is designed for 

applications with modulating zone damper and reheat or 

peripheral heat.

Features                                 

• Stand-alone or network operation

• 7-day time clock

• Discharge air sensor input with high and low limits and reset 

• Outdoor air sensor input with heating & cooling lockout

• Offers up to two stages for heating and/or cooling and the outputs for 

zone damper and reheat 

• Adjustable delay on powerup for soft starts

• P+I control option

• Smart Recovery

• No backup battery required

• Built-in HVAC equipment protection

• 32 character LCD display

• Six LEDs for status monitoring  

• Remote room sensing capability

• User setpoint adjustment limits

• Local and remote override capability 

• System and fan switching with access lockouts  

• Fan interlock safety option

• Filter service input and indication

• Equipment monitoring inputs and indication

• External time clock input 

• Energy management input for setpoint shift 

• Access to programming or schedule may be locked out or limited 

with the use of an access code

• Fahrenheit or Celsius temperature display

• Digital or analog changeover

Product Manual      

Contents                                 

Description

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Features

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Mounting

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Wiring

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

Setup

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Programming

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4

Setting Clock & Schedule

. . . . . . . . . . . . . . . . . . . . . . .

7

Operation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Checkout & Troubleshooting

  . . . . . . . . . . . . . . . . . . . .

10

LED Description

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

Limiting Occupant Access  . . . . . . . . . . . . . . . . . . . . . . 12

User’s Guide

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

Mounting                                

The SZ1018 are designed for wall mounting using two #6 

sheet metal screws, either over a horizontally installed 2" 

x 4" junction box, or directly to block or drywall. 

For best results, the thermostat should be mounted on  

an interior wall which reflects normal room environment, 

at a height of approximately five feet from the floor. Avoid 

areas exposed to direct sunlight, unusual heat or cool 

sources, open doors and windows, unventilated locations 

and hot or cold air from diffusers.
If using a remote room sensor, it should be mounted in 

the manner described above. The thermostat may then 

be mounted in an area which is accessible for adjusting 

its settings. 

Caution

: Remove power from thermostat prior                  

to mounting.

SZ1018

Modulating Zone Thermostat

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

1

Содержание Superzone SZ1018

Страница 1: ...t Access to programming or schedule may be locked out or limited with the use of an access code Fahrenheit or Celsius temperature display Digital or analog changeover Product Manual Contents Descripti...

Страница 2: ...devices SZ1018 thermo stats require 8 VA 24 VAC When the SZ1018 are used as a stand alone thermostat without communications the unit transformer may be used to power it However using separate power wi...

Страница 3: ...h the two set screws located at the top right and the left side to prevent tampering Setup Note If using remote sensor s the calibration may need to be adjusted See Checkout and Troubleshooting sectio...

Страница 4: ...s the following screens Access Code Entry Screen Will appear if access code is required for programming Use 248 as the default If the wrong code is entered it will revert to the previous screen Contro...

Страница 5: ...reen Enter whether you want to control by temperature only P or add a time factor P I This is applies to both the stage outputs Time Clock Output Screen Choose whether the auxiliary output will be OPE...

Страница 6: ...Choose whether to control based on DISCHARGE air reset or SPACE temper ature This screen will not appear if the discharge air sensor function is disabled Set to SPACE if this stat will be used within...

Страница 7: ...n Monitoring Screen Setting Clock Schedule The SZ1018 clock and schedule may be set through the keypad on the face or with a PC For more infor mation on programming through the PC consult your softwar...

Страница 8: ...ge air tempera ture will be controlled to this setting by modulating the heating or cooling device Operation UNOCCUPIED SETBACK The SZ1018 operate in either an occupied or unoc cupied mode During the...

Страница 9: ...s required which indicates when the fan is running If the thermostat turns on the FAN and DI1 is not closed after thirty seconds the system will go to OFF disabling all outputs the fan LED will turn o...

Страница 10: ...parameters for analog output 2 Select whether the analog output is set for heating cooling or aquastat Select direct or reverse action Select whether you want the analog output to modulate from 4 to 2...

Страница 11: ...k the wiring Short terminals R to Y W1 or Y W2 and see if the heating or cooling comes on This is a check for a mechanical relay failure Wrong Temperature Display Initially verify the wiring connectio...

Страница 12: ...tatus service status 7 MOD OUT 2 100 OPEN service status MOD OUT 2 Screen Shows the percentage of modulating output 2 DI2 and DI3 Status Screen Shows DI2 status and filter status or DI3 status Main Mo...

Страница 13: ...up section PROGRAMMING The ability to program control parameters is allowed by fac tory default An access code may be required as set in pro gramming step 43 or access may be denied altogether using d...

Отзывы: