Страница 1: ...30 TON AC OPERATING AND SERVICE MANUAL STARTING S N AC030 21 00001 REV...

Страница 2: ...ents 2 Safety Information 5 Technical Data Specifications 6 Operator Control Panel 8 Operation and Service 9 Troubleshooting 10 Electrical Schematic 12 Electrical Panel Layout 13 Piping Schematic 14 S...

Страница 3: ...are identified in this publication TCRS cannot anticipate every possible circumstance that might involve a potential hazard The warnings in this publication and on the product are therefore not all in...

Страница 4: ...a message is attached to a part that is replaced install a message on the replacement part General Hazard Information Attach a Do Not Operate warning tag to the start switch or controls before the uni...

Страница 5: ...cleaning allow the machine to cool to reduce the possibility of fine debris igniting when redeposited on hot surfaces Fluid Penetration Always use a board or cardboard when you check for a leak Leakin...

Страница 6: ...on 32 AMPS each Condenser Fan Motor WATTS 2700 WATTS x 2 FLA 4 AMPS x 2 Circuit Protection 10 AMPS each Blower Motor WATTS 3100 WATTS x 2 FLA 5 AMPS x 2 Circuit Protection 10 AMPS each Condensate Pump...

Страница 7: ...or FAULT touch button RED when fault is active press to display Fault screen Config touch button Password protected to set initial system settings Monitor touch button Press to display Monitor screen...

Страница 8: ...that system should not run above and will shut down Temp Offset Temperature offset above setpoint when system will start Select Temp Display Selects temperature display units Celsius or Fahrenheit CO...

Страница 9: ...3 A condenser cooled by an electronically commutated EC fan 4 A liquid line filter dryer to absorb moisture and contaminants 5 A liquid line sight glass for monitoring the refrigerant charge and moist...

Страница 10: ...e is present replace condenser motor High Pressure Cutout Fault High pressure trip Check condenser fan operation Check for restricted condenser air flow Check for refrigerant over charge Press High Pr...

Страница 11: ...10 Electrical Schematic Contact TCRS at 440 658 2020...

Страница 12: ...11 Contact TCRS at 440 658 2020...

Страница 13: ...Electrical Panel Layout 12 Contact TCRS at 440 658 2020...

Страница 14: ...13 Piping Schematic Contact TCRS at 440 658 2020...

Страница 15: ...Contact TCRS at 440 658 2020 Structural Sheet Metal BOM 14...

Страница 16: ...Contact TCRS at 440 658 2020 15...