9

11.  Auto Vane Operation control 

(1)  Vane motor drive 

The unit is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the 
motor are controlled by pulse signal transmitted from indoor microprocessor. 

(2) Positioning  

The vane is once pressed to the vane stopper below to confirm the standard position and then set to the 
desired angle. The positioning is decided as follows: 

 

When the ON/OFF button is pressed. 

 

When the vane control is change from AUTO to MANUAL. 

 

When the SWING is finished. 

 

When the test run starts. 

 

When the power supply turns ON. 

(3)  The auto vane changes as follows by pressing the VANE CONTROL button. 
(4) VANE AUTO mode  

In vane auto mode, the microprocessor automatically determines the vane angle and operation to make the 
optimum room-temperature distribution. 

(5) SWING mode 

When presses the SWING button, the vane swings. 

12. TIMER Operation 

(1)  To activate the air conditioner at the desire time, follow the procedure specified below(the remote control 

and air conditioner are switched off): 

 

Press the Timer button. 

 

Select the desired mode by pressing the Mode button. 

 

Select the desired temperature by pressing the 

 

 button (only possible when the ‘cool’ or ‘heat’ 

mode is selected). 

 

Select the ventilator speed (low, medium or high) or automatic mode (only possible when the feel, Cool 
or Heat mode is selected) by pressing the Fan button. 
The ventilator always operates in the Auto mode when the Dry mode is selected. 

 

Select Swing or no Swing by pressing the Swing button. 

 

Press the Timer button (‘h’ flashes). 

 

Use the 

▲▼

 button to select the time at which the air conditioner must activate (between 0 and 10 

hours can be set at every half hour-between 10 and 24 hours can be set at every hour). 

 

Press the Timer button (‘h’ stops flashing) and the preset time appears in the display. 

 

Press the Timer button again to delete the selected data from the memory. 

Note: If no buttons are pressed during the programming of the timer function, the remote control will switch 

off automatically are after 10 seconds. 

(2)  To switch the air conditioner off at the desired time, follow the procedure specified below (the remote control 

and air conditioner are switched off): 

 

Press the Timer button. 

 

Use the 

▲▼

 button to select the time at which the air conditioner must deactivate (between 0 to 10 

hours can be set at every half hour-between 10 to 24 hours can be set at every hour). 

 

Press the Timer button (‘h’ stops flashing), and the preset time will appear in the display. 

 

Press the Timer button again to delete the selected data from the memory. 

Note: If no buttons are pressed during the programming of the timer function, the remote control will switch 
off automatically after 10 seconds. 
 
Note: if ‘h’ is flashing and you press the ON/OFF/RUN button once, the preset temperature will appear in 

Содержание TAC-42CF

Страница 1: ...ING AIR CONDITIONERS CONTENTS 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 4 4 WIRING DIAGRAM 5 5 EXPLOSION VIEW 12 6 PARTS LIST 18 Models TAC 42CF TAC 42CHF TCL SERVICE MANUAL No TE040720 ...

Страница 2: ...nformation nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior notice The accurate specifications are presented on the nameplate label How to order spare parts To have your order filled promptly and correctly please furnish the following information 1 Model No wi...

Страница 3: ...e φ9 53 Expansion device Capillary tube Defrosting system Microcomputer controlled reverse system Fan System Indoor air circulation m3 h 1000 1000 Indoor fan type Cross flow Cross flow Cooling rpm 550 480 380 550 480 380 Heating rpm N A 550 480 380 Dry rpm 380 380 Indoor fan speed H M L Sleep rpm 380 380 Indoor fan motor output W 160 160 Outdoor air circulation m 3 h Outdoor fan type Propeller fan...

Страница 4: ...TION MODE Selection Button Used to select the type of operation mode AUTO Cooling Dry Fan Only for Cooling Only and Heating Only for Heat Pump FAN SPEED CONTROL Button Used to select the indoor fan motor speed Auto High Mid and Low TCL Air Conditioner Service Manual 4 TCL Air Conditioner Service Manual ...

Страница 5: ...temperature and time ON TIMER Button Used to select ON TIMER operation OFF TIMER Button Used to select OFF TIMER operation The indication symbols on LCD A U T O Indicator Sleep Mode Indicator Clock Indicator Cooling Indicator Air Flow Direction Indicator ON TIMER Indicator Dry Indicator Set Room Temp Indicator OFF TIMER Indicator Fan Indicator Fan Speed Indicator Order of ON and OFF Timer Heating ...

Страница 6: ... Control During HEATING operation the outdoor fan motor and compressor are controlled by the indoor pipe temperature to prevent the high temperature of compressor Outdoor fan OFF 56 Outdoor fan ON 50 Compressor OFF 60 Compressor ON 50 2 AUTO Mode Operation 1 When the AUTO mode is selected the operation mode and initial set temperature are determined by the initial room temperature at start up of t...

Страница 7: ... be controlled 5 HEATING Mode Operation Only available for Heat Pump 1 When the HEATING mode is selected without setting temperature the system will set the temperature at 23 automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according to the setting by the remote controller and the operation is as following Set Temp 1 Set Temp 1 Room Temp Tim...

Страница 8: ...xceeds 10 minutes Defrosting time chart Outdoor Fan ON OFF ON Reversing Valve ON OFF ON Compressor Relay ON OFF ON OFF ON 39S 5S Defrost Count MAX 12min 19S 15S t 6 Assistant Thermistor Function Assistant thermistor is add the thermitor of the electricity to rise the heating capacity automatically not effected by the signal of the remote controller about assistant thermistor ON OFF buttons 1 When ...

Страница 9: ...rocessor to feedback the rotational frequency Comparing the current rotational frequency with the target rotational frequency the microprocessor adjusts fan motor electric to make the current rotational frequency close to the target rotational frequency With this control when the fan speed is switched the rotational frequency changes smoothly 2 When the rotational frequency feedback signal has not...

Страница 10: ...matic mode only possible when the feel Cool or Heat mode is selected by pressing the Fan button The ventilator always operates in the Auto mode when the Dry mode is selected Select Swing or no Swing by pressing the Swing button Press the Timer button h flashes Use the button to select the time at which the air conditioner must activate between 0 and 10 hours can be set at every half hour between 1...

Страница 11: ... during normal operation 14 AUTO RESTART Function Option When the indoor unit is controlled with the remote controller the operation mode set temperature and the fan speed are memorized by the indoor electric control PCB The AUTO RESTART function sets to work the moment power has restored after power failure Then the unit will restart automatically 15 Failure Display and Handling a The failure of ...

Страница 12: ...r stops the indoor fan operates in cold air prevention control The system doesn t receive the signal of remoter controller except the signal of shut off it When the system check the voltage is 220V and the delay control is finished it operates at normal again When the indoor fan motor is failure the compressor is stopped the outdoor fan and indoor fan is stopped and display the failure The system ...

Страница 13: ...TCL Air Conditioner Service Manual 12 WIRING DISGRAM MODEL TAC 42CHF INDOOR UNIT OUTDOOR UNIT ...

Страница 14: ...TCL Air Conditioner Service Manual 13 MODEL TAC 42CF INDOOR UNIT OUTDOOR UINT ...

Страница 15: ...or COOLING HEATING 214590114 FRONT PLATE 1084590106 FAN GUARD 1100070001 COMPRESSOR 1120160003 LIQUID STORE CAN 1120120010 TWO WAY VALVE 1124590113 CAPILLARY ASSEMBLY same for heating cooling AND cooling only 1094590101 OUTDOOR PCB for heating cooling 1094590201 OUTDOOR PCB for only cooling 1214590105 PARTITION 1120130012 THREE WAY VALVE 1214590101 BASE 1214590103 RIGHT PLATE 1214590110 TOP COVER ...

Страница 16: ...090210 OPERATION PANEL 1094090202 OPERATION PCB for heating cooling 1094090404 OPERATION PCB for only cooling 1074090121 INDOOR GRILLE 1074090122 AIR FILLTER 1074090121 GRILLE 1214090116 MIDLLE PANEL 1170010004 SWING MOTOR 1074090108 HORIZONTAL VANE 1074090110 VERTICAL VANE 1074090103 BASE ...

Страница 17: ...TCL AIR CON SERVICE MANUL 1214090121 EVAPORATOR ASSEMBLY 1094090301 MAIN PCB for heating cooling 1094091102 MAIN PCB for only cooling 1170030010 INDOOR MOTOR 1070010004 INDOOR FAN ...

Отзывы: