TCL Air Conditioner Service Manual 

                                                                                             

10

the display. You can now adjust the temperature with the 

▲▼

 button. Press the Timer button again to 

display the time, which can now also be adjusted

.

 If the Timer button is pressed again, the data is stored and 

the remaining time(that the air conditioner will be in operation) will appear in the display. 
 

 

Pressing the ON/OFF/RUN button instead of the Timer button deactivates the remote control. 

Note: check that the TIMER INDICATOR on the indoor unit lights up after the timer has been set. 
Press the Timer function to check the settings in the display. 

13. EMERGENCY-TEST Operation 

When the EMERGENCY Operation switch is pressed once, COOLING mode is selected and if in 3 seconds the 
EMERGENCY Operation switch is pressed again, HEATING mode is selected. Then pressed once again, the unit 
is switch off. 
When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY Operation 
switch on the front of the indoor unit. The unit will start. 
The first 30 minutes of operation will be the test run operation. The operation is for servicing. The indoor fan runs 
at high speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal. 
After 30 minutes of test run operation the system shifts to AUTO COOLING/HEATING mode, and the indoor fan 
runs in automatic speed. The operation continues unit the EMERGENCY operation switch is pressed or a button 
on the remote controller is pressed, the normal operation will start. 
NOTE: Do not press the EMERGEMCY Operation switch during normal operation. 

14.AUTO RESTART Function (Option) 

When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan 
speed are memorized by the indoor electric control PCB. The AUTO RESTART function sets to work the 
moment power has restored after power failure. Then, the unit will restart automatically. 

15.  Failure Display and Handling 

a)  The failure of the resistance of heat sensitive: 

When the resistance of heat sensitive reads the temperature is lower than 

50

  or over than 110

 that 

judge the heat sensitive is bad. 

b)  The Outdoor Protection Control 

When the system checks the signal from outdoor of the voltage is 0V, the system delay 1second to start for 
check the signal again, if checks the signal of the voltage is 0V too, that the system not to star, or operates on 
normal. 

c) Failure 

Display 

When the controller is failure, the buzzer will voice long for three times, and displays the failure from the 
failure lamp. 

d) Failure 

Code 

If have the digital pipe that display the failure code for digital pipe, or display for the run lamp. 

Type of failure 

The lamp flash 

Display of digital pipe 

The failure of room temperature sensor 

Once/cycle 

E1 

The failure of indoor pipe temperature sensor 

Twice/cycle 

E2 

Outdoor protection function 

5 times/cycle 

E5 

The failure of indoor fan  6 times/cycle E6 

e) Failure 

Handling 

 

When the room temperature sensor or the indoor pipe temperature sensor is failure, the system will be 
shut off, the compressor will be OFF, and the outdoor fan and the indoor fan will be OFF. The system 
doesn’t receive the signal of remoter controller except the signal of shut off it. When the failure 
eliminated, the controller can operate in normal mode. before this, presses the “ON/OFF” to start the 
system, and it will operate in COOLING or HEATING for 30 minutes, and follows shut off. During 

Содержание TAC-24CF/E

Страница 1: ...G AIR CONDITIONERS CONTENTS 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 4 4 WIRING DIAGRAM 5 5 EXPLOSION VIEW 12 6 PARTS LIST 18 Models TAC 24CF E TAC 24CHF E TCL SERVICE MANUAL No TE040610 ...

Страница 2: ...nformation nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior notice The accurate specifications are presented on the nameplate label How to order spare parts To have your order filled promptly and correctly please furnish the following information 1 Model No wi...

Страница 3: ... φ9 53 Expansion device Capillary tube Defrosting system Microcomputer controlled reverse system Fan System Indoor air circulation m3 h 1200 1200 Indoor fan type Cross flow Cross flow Cooling rpm 480 430 380 480 430 380 Heating rpm N A 480 430 380 Dry rpm 380 380 Indoor fan speed H M L Sleep rpm 380 380 Indoor fan motor output W 76 76 76 Outdoor air circulation m 3 h Outdoor fan type Propeller fan...

Страница 4: ...ller 6 2 5 3 7 1 1 1 TCL Air Conditioner Service Manual Operation Details Remote Control The remote controller is not presetted as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time after the remote controller replace batteries or is energized the arrowhead will flashes on the front of Heat or Cool on LCD of the remote controller User can preset the remote controller type dependin...

Страница 5: ...rol During HEATING operation the outdoor fan motor and compressor are controlled by the indoor pipe temperature to prevent the high temperature of compressor Outdoor fan OFF 52 Outdoor fan ON 48 Compressor OFF 62 Compressor ON 48 2 I Feel Mode Operation 1 When the I Feel mode is selected the operation mode and initial set temperature are determined by the initial room temperature at start up of th...

Страница 6: ... be controlled 5 HEATING Mode Operation Only available for Heat Pump 1 When the HEATING mode is selected without setting temperature the system will set the temperature at 23 automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according to the setting by the remote controller and the operation is as following Set Temp 1 Set Temp 1 Room Temp Tim...

Страница 7: ...s 10 minutes Defrosting time chart Outdoor Fan ON OFF ON Revering Valve ON OFF ON Compressor Relay ON OFF ON OFF ON 39S 5S Defrost Count MAX 12min 19S 15S t 6 Assistant Thermistor Function Assistant thermistor is add the thermitor of the electricity to rise the heating capacity automatically not effected by the signal of the remote controller about assistant thermistor ON OFF buttons 1 When the co...

Страница 8: ...ocessor to feedback the rotational frequency Comparing the current rotational frequency with the target rotational frequency the microprocessor adjusts fan motor electric to make the current rotational frequency close to the target rotational frequency With this control when the fan speed is switched the rotational frequency changes smoothly 2 When the rotational frequency feedback signal has not ...

Страница 9: ...matic mode only possible when the feel Cool or Heat mode is selected by pressing the Fan button The ventilator always operates in the Auto mode when the Dry mode is selected Select Swing or no Swing by pressing the Swing button Press the Timer button h flashes Use the button to select the time at which the air conditioner must activate between 0 and 10 hours can be set at every half hour between 1...

Страница 10: ...on Option When the indoor unit is controlled with the remote controller the operation mode set temperature and the fan speed are memorized by the indoor electric control PCB The AUTO RESTART function sets to work the moment power has restored after power failure Then the unit will restart automatically 15 Failure Display and Handling a The failure of the resistance of heat sensitive When the resis...

Страница 11: ...oesn t receive the signal of remoter controller except the signal of shut off it When the system check the voltage is 220V and the delay control is finished it operates at normal again When the indoor fan motor is failure the compressor is stopped the outdoor fan and indoor fan is stopped and display the failure The system doesn t receive the signal of remoter controller except the signal of shut ...

Страница 12: ...GRN YLW GRN 50Hz L N BROWN BLUE YLW GRN BROWN BLUE YLW GRN WHITE P3 P2 P1 L N L N BOX 1 1 COMP θ RT IPT TH1 TH2 θ INDOOR UNIT OUTDOOR UNIT 1130080198 OUTDOOR UNIT O U TD O O R W IR IN G D IA G R A M C O M PR ESSO R M O TO R C M C S M R W H ITE R ED B LU E Y LW G R N WHITE R ELA Y FA N M O TO R B LU E C A PA C ITO R M Y ELLO W R ED W H ITE B LU E R ED Y LW G R N B R O W N 1 N L BROWN BLUE YLW GRN W...

Страница 13: ... VALVE P3 P4 P5 CN6 CN7 RT IPT NTC OPT TEMPERATURE CONTROLLER HEATER RED BLUE HEATER PROTECTOR NON ELECTRIC IC AUXILIARY HEATING MODEL WITHOUT AUXILIARY HEATER INDOOR UNIT L N 3 2 L N 1 2 3 1130080201 OUTDOOR UINT OUTDOOR WIRING DIAGRAM COMPRESSOR BUILD IN OR VISIBLE PROTECTOR MOTOR CAPACITOR RED YLW M YLW GRN CM C S R WHITE RED M BLUE BLUE FAN MOTOR BUILD IN PROTECTION VALVE COIL CN7 NTC OPT CONT...

Страница 14: ...TCL Air Conditioner Service Manual 14 EXPLOSION VIEW MODEL TAC 24CF E INDOOR UNIT ...

Страница 15: ...TCL Air Conditioner Service Manual 15 EXPLOSION VIEW MODEL TAC 24CHF E INDOOR UNIT ...

Страница 16: ...TCL Air Conditioner Service Manual 16 EXPLOSION VIEW MODEL TAC 24CF E OUTDOOR UNIT 1 2 3 5 4 6 7 9 10 11 13 14 15 16 17 8 18 19 20 21 22 23 24 25 26 27 28 12 ...

Страница 17: ...TCL Air Conditioner Service Manual 17 EXPLOSION VIEW MODEL TAC 24CHF E OUTDOOOR 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 19 17 18 20 21 22 23 24 25 26 27 28 29 30 ...

Страница 18: ...age1 1 15 1200710101 Rubber Water Drainage2 16 1210710101 Evaporator Assembly 1 17 1210520115 Right Plate 1 18 1210520113 Top Plate 1 19 1210520114 Left Plate 1 20 1070520101 Base 1 21 1170050002 Fan Motor 2 22 1070010008 Centrifugal Fan 2 23 1150520104 Volute Casing 1 24 1074060115 Lead Flow Circle 1 25 1080520105 Electrical Parts Box 1 26 1074020122 1074020914 Cable Clamp1 Cable Clamp2 1 1 27 11...

Страница 19: ...er 41 1090010071 Remote Control 42 1073030303 Remote Control Supporter 43 1190060022 Base Carton 44 1190060023 Left Right Beehive Carton 45 1190060024 Middle U Beehive Carton 46 1190060025 Middle Cover Beehive Carton 47 1190060026 Base Beehive Carton 48 1190060016 Cabinet Carton 49 1170130002 Power Supply Cord Not shown in Explosion view ...

Страница 20: ...age1 1 15 1200710101 Rubber Water Drainage2 16 1210710101 Evaporator Assembly 1 17 1210520115 Right Plate 1 18 1210520113 Top Plate 1 19 1210520114 Left Plate 1 20 1070520101 Base 1 21 1170050002 Fan Motor 2 22 1070010008 Centrifugal Fan 2 23 1150520104 Volute Casing 1 24 1074060115 Lead Flow Circle 1 25 1080520105 Electrical Parts Box 1 26 1074060118 Cable Clamp 1 27 1170200010 Terminal 1 28 1170...

Страница 21: ...1 Remote Control 42 1073030303 Remote Control Supporter 43 1190060022 Base Carton 44 1190060023 Left Right Beehive Carton 45 1190060024 Middle U Beehive Carton 46 1190060025 Middle Cover Beehive Carton 47 1190060026 Base Beehive Carton 48 1190060016 Cabinet Carton 49 1170130002 Power Supply Cord Not shown in Explosion view ...

Страница 22: ... Suction Pipe 1 13 1214561809 Base 1 14 1100060013 Compressor And It Accessories 1 15 1084530503 Right Plate 1 16 1084530502 Valve Supporter 1 17 1120120011 Two way Valve 1 18 1120130013 Three way Valve 1 19 1074530503 Electrical Box Cover 1 20 1080010004 Capacitor Strip 1 21 1074060118 Cable Clamp 1 22 1170200026 Terminal 1 23 1170100007 Compressor Capacitor 1 24 1170100030 Fan Motor Capacitor 1 ...

Страница 23: ... 1120710116 Three way Valve connecting Pipe 1 15 1120710114 Discharge Pipe 1 16 1120110003 4 way Vane Assembly 1 17 1120700206 Condenser connecting Pipe 1 18 1214561809 Base 1 19 1120120011 Two way Valve 1 20 1084530502 Valve Supporter 1 21 1120130013 Three way Valve 1 22 1084530503 Right Plate 1 23 1074530503 Electrical Box Cover 1 24 1074060118 Cable Clamp 1 25 1170200036 Terminal 1 26 108001000...

Отзывы: