THERMISTOR TEMPERATURE CHARACTERISTICS 

1. Indoor unit and outdoor exchange temperature and outside air temperature sensor temperature 

characteristics

 

TEMP. 

(

Resistance 

(k Ohm) 

Voltage of 

resistance 

TEMP.

(

Resistance

(k Ohm) 

Voltage of 

resistance

TEMP. 

(

)

 

Resistance 

(k Ohm)

 

Voltage of 

resistance

 

 -30 

   63.513 

4.628 

15 

7.447 

2.968 

  60 

1.464 

1.115 

 -29 

  60.135 

4.609 

16 

7.148 2.918 

  61 

1.418 1.088 

 -28 

  56.956 

4.589 

17 

6.863 2.868 

  62 

1.374 1.061 

 -27 

  53.963 

4.568 

18

6.591

2.819

 63

1.331 

1.035

 -26 

  51.144 

4.547 

19 

6.332 2.769 

  64 

1.290 1.009 

 -25 

  48.488 

4.524 

20 

6.084 2.720 

  65 

1.250 0.984 

 -24 

  45.985 

4.501 

21

5.847

2.671

 66

1.212 

0.960

 -23 

  43.627 

4.477 

22 

5.621 

2.621 

  67 

1.175 

0.936 

 -22 

  41.403 

4.452 

23

5.404

2.572

 68

1.139 

0.913

 -21 

39.305 4.426 24 

5.198 2.524 

  69 

1.105 0.890 

 -20 

37.326 4.399 25 

5.000 2.475 

  70 

1.072 0.868 

 -19 

35.458 

4.371 

26

4.811

2.427

 71

1.040 

0.847

 -18 

33.695 4.343 27 

4.630 2.379 

  72 

1.009 0.825 

 -17 

32.030 

4.313 

28

4.457

2.332

73

0.979 

0.805

 -16 

30.458 

4.283 

29 

4.292 

2.285 

 74 

0.950 

0.785 

 -15 

28.972 4.252 30 

4.133 2.238 

 75 

0.922 0.765 

 -14 

27.567 

4.219 

31

3.981

2.192

76

0.895 

0.746

 -13 

26.239 

4.186 

32

3.836

2.146

77

0.869 

0.728

 -12 

24.984 

4.152 

33

3.697

2.101

78

0.843 

0.710

 -11 

23.795 4.117 34 

3.563 2.057 

 79 

0.819 0.692 

 -10 

22.671 4.082 35 

3.435 2.012 

 80 

0.795 0.675 

 -9 

21.606 

4.045 

36

3.313

1.969

81

0.773 

0.658

 -8 

20.598 4.008 37 

3.195 1.926 

 82 

0.751 0.641 

 -7 

19.644 3.969 38 

3.082 1.883 

 83 

0.729 0.625 

 -6 

18.732 

3.930 

39 

2.974 

1.842 

 84 

0.709 

0.610 

 -5 

17.881 

3.890 

40 

2.870 

1.800 

 85 

0.689 

0.595 

 -4 

17.068 

3.850 

41

2.770

1.760

86

0.669 

0.580

 -3 

16.297 3.808 42 

2.674 1.720 

 87 

0.651 0.566 

 -2 

15.565 3.766 43 

2.583 1.681 

 88 

0.633 0.552 

 -1 

14.871 3.723 44 

2.494 1.642 

 89 

0.615 0.538 

 0 

14.212 3.680 45 

2.410 1.604 

 90 

0.598 0.525 

 1 

13.586 3.635 46 

2.328 1.567 

 91 

0.582 0.512 

 2 

12.991 3.590 47 

2.250 1.530 

 92 

0.566 0.499 

 3 

12.426 3.545 48 

2.174 1.495 

 93 

0.550 0.487 

 4 

11.889 3.499 49 

2.102 1.459 

 94 

0.535 0.475 

 5 

11.378 3.452 50 

2.032 1.425 

 95 

0.521 0.463 

 6 

10.893 3.406 51 

1.965 1.391 

 96 

0.507 0.452 

 7 

10.431 3.358 52 

1.901 1.357 

 97 

0.493 0.441 

 8 

9.991 

3.310 

53 

1.839 

1.325 

 98 

0.480 

0.430 

 9 

9.573 3.262 54 

1.779 1.293 

 99 

0.467 0.419 

 10 

9.174 

3.214 

55

1.721

1.262

100

0.455 

0.409

 11 

8.795 3.165 56 

1.666 1.231 

 

 

 

 12 

8.433 3.116 57 

1.613 1.201 

 

 

 

 13 

8.089 

3.067 

58

1.561

1.172

 

 14 

7.760 3.017 59 

1.512 1.143 

 

 

 

 

Содержание TAC-09CHSA/XP

Страница 1: ...Models TAC 09CHSA XP TAC 12CHSA XP CONTENTS 1 Important Notice 2 Technical Specifications 3 Product Dimensions 4 Refrigeration cycle diagram 5 Operation details 6 Wiring diagram 7 Explosion view and...

Страница 2: ...le for the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modificatio...

Страница 3: ...0 1650 Annual energy consumption kwh cooling 410 545 Max Current Cooling A 7 2 8 0 Heating A 7 5 8 8 Max Power input Cooling W 1250 1550 Heating W 1350 1650 Refrigerating System Refrigerant Charge Gra...

Страница 4: ...Manual 3 3 Product Dimensions Indoor Unit Outdoor Unit Model Indoor unit Outdoor unit A B C D E F G H I J K TAC 09CHSD XP 777 250 205 700 550 256 439 302 277 8 48 55 TAC 12CHSD XP 777 250 205 700 550...

Страница 5: ...y Compressor Accumulator Heat exchange condenser Heat exchange Evaporator 2 way valve Liquid side 3 way valve Gas side Cooling Heating Gas side 3 way valve Liquid side 2 way valve Heat exchange Evapor...

Страница 6: ...at Pump is set If you don t press any button within 10 seconds the remote controller is preset as Heat Pump automatically Note If the air conditioner you purchased is a Cooling Only one but you preset...

Страница 7: ...r or load of compressor is abnormity the air conditioner will shut down and show error code 7 IPM module protection IPM module has high temperature over current protection itself if there is signal fe...

Страница 8: ...irst it operates in cooling mode the set temperature ST is RT 2 After that t he system will operate in cooling mode with lowest fan speed for 30 minutes and then change to middle speed for 30seconds a...

Страница 9: ...heat exchanger Temperature OPT is continuously less than 3 while the unit runs for more than 120 minutes and OPT is keeping below 2 for more than 3 minutes Before the air con comes into defrosting com...

Страница 10: ...indoor unit for function test NOTE Do not press the EMERGEMCY Operation switch during normal operation 8 AUTO RESTART Function Option While air conditioner is operating in one mode all of its operatio...

Страница 11: ...z Outdoor failure display There is a LED on outdoor power board it blinks 1s ON and 1s OFF while compressor standby and it always light ON while compressor running If there is failure happened on ODU...

Страница 12: ...pressor overheat fault compressor top switch 9 Short circuit open circuit fault of outdoor temperature sensor 10 Short circuit open circuit fault of outdoor heat exchanger temperature sensor 11 Short...

Страница 13: ...Air Conditioner Service Manual 12 6 Wiring diagram MODEL TAC 09CHSD XP TAC 12CHSD XP INDOOR UNIT OUTDOOR UNIT...

Страница 14: ...ical Box Cover 1 17 210736832 Cable Clamp 1 18 210900478A Terminal 1 19 210901224 Transformer 1 20 210901714EF Main PCB 1 21 210736831 Electrical Box 1 22 210900333 Indoor Sensor Assembly 1 23 1170030...

Страница 15: ...r 1 17 210736832 Cable Clamp 1 18 210900478A Terminal 1 19 210901224 Transformer 1 20 210901714EF Main PCB 1 21 210736831 Electrical Box 1 22 210900333 Indoor Sensor Assembly 1 23 1170030067G Indoor M...

Страница 16: ...120110016J 4 way valve 1 12 211232688B 4 way valve assembly 1 13 210800545 Base 1 14 210800541 Right plate 1 15 1120120021 Two way valve 1 16 1080050003 Valve supporter 1 17 211206766 Three way valve...

Страница 17: ...1120110016J 4 way valve 1 12 211239923 4 way valve assembly 1 13 210800545 Base 1 14 210800541 Right plate 1 15 1120120045 Two way valve 1 16 1080050003 Valve supporter 1 17 211206766 Three way valve...

Страница 18: ...ion under over voltage category III conditions and these means must be incorporated in the fixed wiring in accordance with the wiring rules z The air conditioner must be installed by professional or q...

Страница 19: ...use an excessive accumulation of dust or waste on the inner parts of the device with possible subsequent failures z The user is responsible for having the appliance installed by a qualified technician...

Страница 20: ...ir could contain gas oil or sulphur or near sources of heat z This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of exper...

Страница 21: ...l 2 Air filter 3 Special filter option 4 Display PCB 5 Vertical vane 6 Horizontal vane 7 Remote controller 9 Names of parts Outdoor unit No Name 8 Air outlet grille 9 Electronic box cover 10 2 way val...

Страница 22: ...ion g 20g m A 5m TAC 09CHSA F6 5 0 15 20g m TAC 12CHSA F6 5 0 15 20g m Connecting cables The power cord should be selected according to the following specifications sheet Appliance Amps Wire Size 5 AW...

Страница 23: ...OOR UNIT Do not install the outdoor unit near sources of heat steam or flammable gas Do not install the unit in too windy or dusty places Do not install the unit where people often pass Select a place...

Страница 24: ...ible flange through the hole in the wall to keep the latter intact and clean The hole must slope downwards towards the exterior Note Keep the drain pipe down towards the direction of the wall hole oth...

Страница 25: ...not bend the pipe more than three times at one point z When extending the rolled pipe straighten the pipe by unwinding it gently as shown in the picture 10 2 6Connections to the indoor unit 1 Remove...

Страница 26: ...htening procedures described for the indoor unit Note If the tightening torque is not sufficient there will probably be some leakage With excessive tightening torque there will also be some leakage as...

Страница 27: ...fault code display Health assembly control Communication with outdoor unit Louver motor control Indoor fan control Display pc board Indoor control board Voltage sampling Frequency generation Storage o...

Страница 28: ...5 1 P8 VAL Electric reactor PC monitor P10 3 W P10 2 V COMP Blue W hite Red T o indoor unit Expansion valve Suction T emp sensor Out door coil T emp sensor Outdoor ambient T emp sensor COM P top T emp...

Страница 29: ...V COMP Red White Blue T o indoor unit Expansion valve Suction T emp sensor Out door coil T emp sensor Outdoor ambient T emp sensor COMP top T emp protection Exhaust T emp sensor CN12 ORQ P13 L P14 L P...

Страница 30: ...slot CN6 if loose or not plugged in please connect again 2 Room temperature sensor IRT and Indoor pipe coil temperature sensor IPT damage short or broken Solution check the resistance of the sensor R...

Страница 31: ...tdoor pipe temp sensor outdoor temp sensor exhaust temp sensor connection terminal loose or not plugged in Solution Check the connecter of sensor and slot if loose or not plugged in please connect aga...

Страница 32: ...l correspond to each other on indoor and outdoor units Measure the voltage on outdoor terminal L and N before display of E0 fault If the voltage is 0 please replace indoor main PCB 2 If the 1 N which...

Страница 33: ...ctifier FRD IGBT etc any component broken replace PCB 7 Test the DC voltage between DC and DC If the voltage is less than 50V approximately please replace outdoor PCB 11 5 5 Display EA Reason Current...

Страница 34: ...t affects the normal radiating of the air conditioner and installation again 5 If the above inspections are normal but the fault remains unsolved please replace the outdoor PCB Re energize and check t...

Страница 35: ...ent indication error occurs Clean indoor or outdoor heat exchange Clean indoor heat exchange and outdoor heat exchange Check the refrigerant amount Check the installation condition Installation again...

Страница 36: ...d wire on PWB Replace P WB Cooling mode Check compressor Modify compressor terminal marking Replace PWB Does compressor rotates Replace compressor Check indoor exchange sensor and discharge sensor Mod...

Страница 37: ...link Check terminal L N voltage Yes No Check the rectifier bridge fast recovery diode FRD and IGBT Solve as E0 Check wire connected and replace indoor PCB Normal Abnormal Replace PFC board or outdoor...

Страница 38: ...765 14 27 567 4 219 31 3 981 2 192 76 0 895 0 746 13 26 239 4 186 32 3 836 2 146 77 0 869 0 728 12 24 984 4 152 33 3 697 2 101 78 0 843 0 710 11 23 795 4 117 34 3 563 2 057 79 0 819 0 692 10 22 671 4...

Страница 39: ...047 2 109 21 170 7 192 5 217 33 13 25 14 18 15 17 87 1 922 1 983 2 045 20 161 6 182 1 205 34 12 72 13 6 14 54 88 1 861 1 922 1 983 19 153 1 172 3 193 7 35 12 21 13 05 13 93 89 1 802 1 862 1 923 18 145...

Страница 40: ...117 0 7837 0 8233 0 8641 10 36 04 39 39 43 01 64 4 101 4 288 4 479 118 0 7623 0 8012 0 8413 11 34 42 37 59 41 65 3 961 4 139 4 32 119 0 7415 0 7798 0 8193 12 32 89 35 87 39 1 66 3 827 3 995 4 167 120...

Отзывы: