TCL Air Conditioner Service Manual 

                                                                                             

13

 

 

Press the Timer button(‘h’ flashes). 

 

Use the 

▲▼

 button to select the time at which the air conditioner must activate (between 0 and 10 

hours can be set at every half hour-between 10 and 24 hours can be set at every hour). 

 

Press the Timer button (‘h’ stops flashing) and the preset time appears in the display. 

 

Press the Timer button again to delete the selected data from the memory. 

Note : If no buttons are pressed during the programming of the timer function, thee remote control will 
switch off automatically after 10 seconds. 

(2)  To switch the air conditioner off at the desired time, follow the procedure specified below (the remote control 

and air conditioner are switched off): 

 

Press the timer button. 

 

Use the 

▲▼

 button to select the time at witch. 

13. EMERGENCY Operation 

When the EMERGENCY Operation switch is pressed once, COOLING mode is selected and if in 3 seconds the 
EMERGENCY Operation switch is pressed again, mode is selected. Then pressed once again, the unit is switch 
off. 
When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY Operation 
switch on the front of the indoor unit. The unit will start. 
The first 30 minutes of operation will be the test run operation. The operation is for servicing. The indoor fan runs 
at high speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal. 
After 30 minutes of test run operation the system shifts to AUTO COOLING/HEATING mode, and the indoor fan 
runs in automatic speed. The operation continues unit the EMERGENCY operation switch is pressed or a button 
on the remote controller is pressed, the normal operation will start. 
NOTE: Do not press the EMERGEMCY Operation switch during normal operation. 

14.  AUTO RESTART Function(Option)

 

1.When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan 
speed are memorized by the indoor electric control PCB. The AUTO RESTART function sets to work the 
moment power has restored after power failure. Then, the unit will restart automatically. 
2. How to set the AUTO RESTAR function. 

 

Press the emergency switch and power supply to the PCB following, keep 10seconds and the buzzer will 
beep three times. The AUTO-RESTAR is set. 

 

Do the operation again, the buzzer will beep four times and the AUTO-RESTAR function is cancelled. 

15. 

Failure Display and Handling

 

a) Failure 

Display 

When the controller is failure, the buzzer will voice long for three times, and displays the failure from the 
failure lamp. 

b) Failure 

Code 

If have the digital pipe that display the failure code for digital pipe, or display for the run lamp. 

Type of failure 

The lamp flash 

Display of digital pipe 

The failure of room temperature sensor 

Once/cycle 

E1 

The failure of indoor pipe temperature sensor 

Twice/cycle 

E2 

The failure of indoor fan motor 

6 times/cycle 

E6 

c) Failure 

Handling 

 

When the room temperature sensor or the indoor pipe temperature sensor is failure, the system will be 
shut off, the compressor will be OFF, and the outdoor fan and the indoor fan will be OFF. The system 
doesn’t receive the signal of remoter controller except the signal of shut off it. When the failure 
disappear, the controller can operate in normal mode. before this, presses the “ON/OFF” to start the 
system, and it will operate in COOLING or HEATING for 30 minutes, and follows shut off. During 

Содержание TAC-07CSA

Страница 1: ...2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 6 4 WIRING DIAGRAM 14 5 EXPLOSION VIEW 20 6 PARTS LIST 27 Models TAC 07CSA M TAC 09CSA M TAC 12CSA M TAC 18CSA M TAC 24CSA M TAC 07CHSA M TAC 09CHSA M...

Страница 2: ...formation nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior n...

Страница 3: ...puter controlled reverse system Fan System Indoor air circulation m3 h 480 480 480 480 Indoor fan type Cross flow Cross flow Cross flow Cross flow Cooling rpm 1100 1000 900 1100 1000 900 1100 1000 900...

Страница 4: ...rocomputer controlled reverse system Fan System Indoor air circulation m3 h 530 530 800 800 Indoor fan type Cross flow Cross flow Cross flow Cross flow Cooling rpm 1250 1150 1050 1250 1150 1050 1060 9...

Страница 5: ...Expansion device Capillary tube Defrosting system Microcomputer controlled reverse system Fan System Indoor air circulation m3 h 1100 1100 Indoor fan type Cross flow Cross flow Cooling rpm 1300 1200...

Страница 6: ...ler 6 2 5 3 7 1 1 1 TCL Air Conditioner Service Manual Operation Details Remote Control The remote controller is not presetted as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time af...

Страница 7: ...ditioner Service Manual 7 REMOTE CONTROLLER The four types of remote controller is as follow GYKQ 05 GYKQ 10e optional GYKQ 11e optional GYKQ 12e optional Note The function of remote controller above...

Страница 8: ...essor Outdoor fan OFF when the indoor pipe temperature is 50 Outdoor fan ON when the indoor pipe temperature is 48 Compressor OFF when the indoor pipe temperature is 62 Compressor ON when the indoor p...

Страница 9: ...ode is selected without setting temperature the system will set the temperature at 23 automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate accordin...

Страница 10: ...e of the IPT is less then 35 for 2 minutes When the defrosting operation time on this condition exceeds 8minutes it will terminate C After the compressor operation continuously for 20 minutes and the...

Страница 11: ...e the set temperature will be raised by 1 1 hour later and by 2 2 hour later When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 2hour later Af...

Страница 12: ...e standard position and then set to the desired angle The positioning is decided as follows When the ON OFF button is pressed When the vane control is change from AUTO to MANUAL When the SWING is fini...

Страница 13: ...is pressed or a button on the remote controller is pressed the normal operation will start NOTE Do not press the EMERGEMCY Operation switch during normal operation 14 AUTO RESTART Function Option 1 Wh...

Страница 14: ...he signal of remoter controller except the signal of shut off it When the system check the voltage is 220V and the delay control is finished it operates at normal again When the indoor fan motor is fa...

Страница 15: ...sensor Room Temp sensor Transformer Power Supply Brown Blue PCB CN1 CN2 TH1 TH2 P2 1 P5 P4 P2 2 NO K1 COM 4 3 CN8 CN6 CN5 CN4 CN3 M M N 3 2 1 Outdoor Unit 1 2 3 N YLW GRN Blue Yellow Red Brown OUTDOO...

Страница 16: ...ensor Transformer Power Supply Brown Blue PCB CN1 CN2 TH1 TH2 P2 1 P5 P4 P2 2 NO K1 COM 4 3 CN8 CN6 CN5 CN4 CN3 M M N 3 2 1 Outdoor Unit 1 2 3 N YLW GRN Blue Yellow Red Brown OUTDOOR UNIT Fan Capacito...

Страница 17: ...TAC 18CSA M INDOOR UNIT FM SM SM OUTDOOR UNIT Compressor Blue Capacitor Compressor R M Red Protector White Black C S CM Fan Capacitor ORG FM YLW GRN Optional Part Fan Motor White Black Blue Blue YLW G...

Страница 18: ...n Relay P5 P1 P3 P4 Red White Blue Yellow FM SM SM Room Temp Sensor Vane Motor Fan Motor Transformer CN3 P9 1 P9 2 CN5 1 CN5 2 CN6 CN7 CN8 P2 1 CN2 CN1 OUTDOOR UNIT Compressor Valve White Black C CM R...

Страница 19: ...SM OUTDOOR UNIT Compressor White Black CM R M S RedBlue Compressor Capacitor Protector C White Brown YLW GRN Yellow Fan Capacitor FM Optional Part Fan Motor Outdoor Unit Indoor Unit Red Red Blue Blue...

Страница 20: ...pressor White Black CM C R M S Blue Red Compressor Capacitor Fan Yellow YLW GRN Optional Part Fan Motor FM Protector White Brown Contactor Power Supply Outdoor Unit Indoor Unit Red Blue Blue Blue Yell...

Страница 21: ...itioner Service Manual 21 EXPLOSION VIEW MODEL TAC 07CSA M TAC 07CHSA M TAC 09CSA M TAC 09CHSA M TAC 12CSA M TAC 12CHSA M INDOOR UNIT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25...

Страница 22: ...TCL Air Conditioner Service Manual 22 EXPLOSION VIEW MODEL TAC 18CSA M TAC 18CHSA M TAC 24CSA M TAC 24CHSA M INDOOR UNIT 1 2 3 4 5 6 7 8 9 10 11 12 13 29 28 27 2 25 24 23 22 21 20 1 18 17 16 14 15...

Страница 23: ...TCL Air Conditioner Service Manual 23 EXPLOSION VIEW Model TAC 07CSA M TAC 09CSA M TAC 12CSA M OUTDOOR UNIT 1 2 3 5 4 6 7 9 10 11 12 13 14 15 16 17 8 18 19 20 21 22 23 24 25 26...

Страница 24: ...TCL Air Conditioner Service Manual 24 EXPLOSION VIEW MODEL TAC 18CSA M OUTDOOR UNIT 1 2 3 5 4 6 7 9 10 11 13 14 15 16 17 8 18 19 20 21 22 23 24 25 12...

Страница 25: ...TCL Air Conditioner Service Manual 25 EXPLOSION VIEW Model TAC 24CSA M OUTDOOR UNIT 1 2 3 5 4 6 7 9 10 11 13 14 15 16 17 8 18 19 20 21 22 23 24 25 26 12...

Страница 26: ...TCL Air Conditioner Service Manual 26 EXPLOSION VIEW MODEL TAC 07CHSA M TAC 09CHSA M TAC 12CHSA M OUTDOOR UNIT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30...

Страница 27: ...TCL Air Conditioner Service Manual 27 EXPLOSION VIEW MODEL TAC 18CHSA MM OUTDOOR UINT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 19 17 18 20 21 22 23 24 25 26 27 28...

Страница 28: ...TCL Air Conditioner Service Manual 28 EXPLOSION VIEW MODEL TAC 24CHSA M OUTDOOR UNIT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 19 17 18 20 21 22 23 24 25 26 27 28 29...

Страница 29: ...PCB 1 11 Display PCB Box 1 12 Air Filter 2 13 Front Panel 1 14 Power Supply Cord 1 15 Upper Vane 1 16 Lower Vane 1 17 Drainage Hose 1 18 Cable Clamp 1 19 Terminal 1 20 Terminal Fixing Board 1 21 Vane...

Страница 30: ...ront Panel 1 14 Electrical Box Cover 1 15 Power Supply Cord 1 16 Vane A 1 17 Vane B 1 18 Drainage Hose 1 19 Cable Clamp 1 20 Vane Motor 2 21 Terminal1 Terminal2 1 1 22 Terminal Fixing Board 1 23 Senso...

Страница 31: ...ront Plate 1 10 Fan Guard 1 11 Capillary Assembly 1 12 Compressor and its Accessories 1 13 Discharge Pipe 1 14 Suction Pipe 1 15 Base 1 16 Two way Valve 1 17 Valve Supporter 1 18 Three way Valve 1 19...

Страница 32: ...Fan Guard 1 10 Suction Pipe 1 11 Base 1 12 Compressor and its Accessories 1 13 Right Plate 1 14 Valve Supporter 1 15 Two way Valve 1 16 Three way Valve 1 17 Electrical Box Cover 1 18 Capacitor Strip...

Страница 33: ...d 1 10 Suction Pipe 1 11 Base 1 12 Compressor and its Accessories 1 13 Right Plate 1 14 Valve Supporter 1 15 Two way Valve 1 16 Three way Valve 1 17 Electrical Box Cover 1 18 Capacitor Strip 1 19 Cabl...

Страница 34: ...ssories 1 12 Suction Pipe 1 13 Three way Valve connecting Pipe 1 14 Discharge Pipe 1 15 4 way Vane Assembly 1 16 Condenser connecting Pipe 1 17 Base 1 18 Right Plate 1 19 Two way Valve 1 20 Valve Supp...

Страница 35: ...Capillary Assembly 1 12 Suction Pipe 1 13 Three way Valve connecting Pipe 1 14 Discharge Pipe 1 15 4 way Vane Assembly 1 16 Condenser connecting Pipe 1 17 Base 1 18 Two way Valve 1 19 Valve Supporter...

Страница 36: ...1 Capillary Assembly 1 12 Suction Pipe 1 13 Three way Valve connecting Pipe 1 14 Discharge Pipe 1 15 4 way Vane Assembly 1 16 Condenser connecting Pipe 1 17 Base 1 18 Two way Valve 1 19 Valve Supporte...

Отзывы: