DC Inverter Air
Evaporator tube
E2
26
The temperature of the indoor tube is higher than the set value
temperature sensor
when cooling mode.
Condenser tube
E3
10
The temperature of the indoor tube is higher than the set value
temperature sensor
when heating mode.
System fault
E4
23
The tube temperature is abnormal in cooling or heating
indoor fan fault
E6
21
、
28
Indoor fan stop or run abnormally
Outdoor temperature
E7
9
Open circuit or short circuit of outdoor room temperature sensor
sensor fault
Exhaust temperature
E8
11
Open circuit or short circuit of outdoor exhaust gas temperature
sensor
sensor
Variable frequency drive
E9
14
、
30
The driver module protect happen three times in 30 minutes.
module fault
Outdoor fan fault
EF
16
、
20
Outdoor DC fan motor stop or run abnormally
Current sensor fault
EA
13
System can't collect current data normally.
Indoor EEPROM fault
EE
27
EEPROM data receive failed
Outdoor EEPROM fault
EE
19
PCB can't collect EEPROM data normally.
Compressor housing top
EP
8
The temperature of compressor housing top is more high or
switch fault
temperature switch fault
Voltage sensor fault
EU
12
System can't collect current voltage data normally.
Back gas temperature
EH
18
Open circuit or short circuit of outdoor exhaust gas temperature
sensor
sensor
power off Instantly
55
Instant power off
compressor input voltage
34
Compressor input voltage lack of phase
lost phase
High pressure protect
P3
24
High pressure protect
Model matching error
29
Capacity matching error
P1: Protection shutdown when voltage is higher than 275V or lower than 160V
Treatment Method: (voltage detection circuit in the inverter module board)
1.
Use the multi‐meter to test whether the power supply between Phases A, B and C and Neutral Line is among
180V‐260V;
2.
Whether the module communication line is reliably connected with the communication interface of main
control panel;
3.
Whether the power supply module is reliably connected with filter boards L and N;
4.
Replace the inverter module board;
5.
Replace the motherboard of outdoor unit
P4: Inverter Compressor Exhaust High Temperature Protection
Treatment Method:
1.
Test whether the compressor exhaust temperature is normal (below 115°);
2.
If it is normal, please test whether the resistance of exhaust temperature sensor is consistent
with that in attached page (Annex 4);
99
/
113
Содержание ITCA-60CHRA/DV3I
Страница 1: ...Technical Manual for DC Inverter Air Conditioner 1 113...
Страница 13: ...DC Inverter Air 1 4 Electrical Wiring Diagram 13 113...
Страница 14: ...DC Inverter Air 1 5 Air Velocity and Temperature Distributions Airflow velocity 14 113...
Страница 22: ...DC Inverter Air 22 113...
Страница 28: ...DC Inverter Air 2 3 Service Space 2 4 Wiring Diagrams 28 113...
Страница 41: ...DC Inverter Air 3 2 Wirin g Diagra ms 41 113...
Страница 42: ...DC Inverter Air A irflow velo city Discharge angle 60 FLOOR 42 113...
Страница 43: ...DC Inverter Air Airflow velocity Temperature 43 113...
Страница 64: ...DC Inverter Air 7 2 Electrical Wiring Diagram 2 1 TCA 36HRA DV 64 113...
Страница 65: ...DC Inverter Air 2 2 TCA 48H RA DV3 TCA 60HRA DV3 65 113...
Страница 66: ...DC Inverter Air 2 2TCA 18HRA DVO TC A 24HRA DVO 66 113...
Страница 82: ...DC Inverter Air 82 113...