MFC Kit Instructions
3.0 Pre-Installation Planning
8
Table 1: MFC Sine Wave Filter Technical Specifications
Current Ratings
480 V: 5
– 1200 Amps
600 V: 8
– 750 Amps
Intermittent overload current of 150% for 1 minute / hour
VFD Output Voltage
480 V and 600 V, 3-phase, at fundamental base frequency configured to Volts
per Hz
VFD Output Frequency
Up to 80 Hz
VFD Carrier Frequency
2 kHz to 16 kHz
Filter Performance
Maximum peak voltage of output waveform
480 V models: 815 V
600 V models: 1,018 V
Maximum dV/dt of output waveform
480 V models: 5 V/
μs
600 V models: 6 V/
μs
Environmental Conditions
Maximum Elevation
6,600 ft (2,000 m), derating required for operation above this level
Operating Temp
-30°C (-22°F) to 50°C (122°F)
Cooling provisions required for operation above this temperature.
Ambient Storage Temp
-40°C (-40°F) to 50°C (122°F)
Maximum Humidity
95% non-condensing
Reference Technical Standards
Voltage Drop
3% at nominal voltage, frequency and rated current
Capacitors
High endurance design (no PCBs)
Agency Approvals
UL & cULus Listed
Part Number Encoding
The figure below indicates the significance of each character in the MFC part number. The example
part number MFC130AR designates an MFC kit that is rated 130A, 480 Volts and does not include
resistors.
Figure 1: MFC Kit Part Number Encoding
NOTE:
Individual part drawings for each component included in the MFC Filter Kits are found at:
https://transcoil.com/products-kmg-mfcdrawings-htm/