HarmonicGuard
®
HSP
Maintenance and Service
10
HSP IOM Manual - Rev. A
Reference Drawings
When troubleshooting, refer to the drawings provided for the specific equipment. Typical drawings are
provided in this manual.
Fuse Specifications
Table 2 lists the specifications for the L-R-C filter power circuit fuses in the HSP 480 volt models.
Refer also to the drawings and other information shipped with the unit.
Table 2 – Fuse Specifications for HSP 480 Volt Models*
HSP
Rating
(HP)
Power Circuit
Fuse Ratings
Amps
Type
5
15
Bussmann
JKS
or equivalent
7.5
15
10
20
15
20
20
30
25
40
30
45
40
60
50
70
60
80
75
100
100
150
* contact factory for additional information
Table 3 – Fuse Specifications for HSP 240 Volt Models
HSP
Rating
Power Circuit Fuse Ratings
(HP)
Amps
Type
5
20
7.5
25
10
30
15
40
20
50
25
70
Class T, Fast Acting
30
80
40
110
50
125
60
175
75
200
100
300
Replacement Parts
If replacement parts are needed, please contact your TCI representative. To assure that the HSP single-
phase harmonic filter continues to perform to its original specifications, replacement parts should
conform to TCI specifications.
Factory Contacts and Tech Support
For technical support, contact your local TCI distributor or sales representative.
You can contact TCI directly at 800-TCI-8282. Select "Customer Service" or "Tech Support" and have
your HSP single-phase harmonic filter nameplate information available.