Apollo Maxx User Manual
9
Battery Voltage
Charge Current
Soft Start
Bulk
Absorption
Float
Recycle
Icc
11.5V
10 days
1h
5
mins
½ Icc
Figure 2-6 Multi Stage Sophisticated Charging Algorithm for Lead Acid Battery
Float charging and recycle charging program guarantee your battery getting proper maintenance
in case of long time connected and less aging in case of long time connected with no use.
Battery Sample Cable (Temperature and Voltage)
Battery temperature is a key factor in correct charging for lead acid battery, the charging formula
must be adjusted (automatically and in real time) according to the actual battery temperature to
ensure that the batteries are fully charged but not overcharged or undercharged. All charging
voltages recommended by the battery manufacture are in fact ONLY applied at 20
℃
-25
℃
.
The Bat sample cable (battery temperature and voltage sensor) supplied with Apollo Maxx
measures the temperature of the battery and automatically makes adjustments at real time to
properly charge your batteries at compensation rate of
– 4mV/
℃
/cell. In case of the lacking of the
Bat sample cable, Apollo Maxx will use 25
℃
as default setting. This feature is especially
recommended for sealed batteries and/or when an important temperature fluctuations occurs on
the battery.
Multi Chemical Batteries Available
Apollo Maxx offers premium charging algorithm for the common chemical acid batteries including
AGM, GEL, Flooded, lead-carbon and Lithium battery. You can set the battery parameters through
the LCD interface and the TBB Link software.
Lithium Battery Compatible
Apollo Maxx has built in communication protocol compatible with for Super L lithium battery from