X4 AC Drive User’s Manual
Chapter 7: X4 Parameters
1428D-0607
- 81 -
© 2007 TB Wood’s All Rights Reserved
Required parameter modifications for this program are provided in Table 7-8, with explanations.
Table 7-8: Required Parameter Settings for Sample Sequencer Program
Parameter
Value
Explanation
Seq Appl
“1 sec Base”
Sets 1 second time increments
DI1 Configure
“Seq1”
Allows DI1 to end state 3
DO1 Configure
“SeqOut-01”
Allows DO1 to be active in state 2
Preset Speed 1
5 Hz
Speed for state 3
Preset Speed 6
50 Hz
Speed for state 1
Seq Cntl1
00010000110
No outputs/FWD/Timed/Primary Ramp/Preset
Speed 6
Seq Count 1
3600
1 hour = 3600 seconds
Seq Cntl 2
01000001000
Enable Output/Stop/Timed/Alt Ramp/Speed Ignored
Seq Count 2
120
2 minutes = 120 seconds
Seq Cntl 3
00101100001
No outputs/REV/DI Value/Primary Ramp/Preset
Speed 1
Seq Count 3
1
Seq1 active