Tatsuta Electric Wire & Cable AD-AS-1C-SR Скачать руководство пользователя страница 2

The sensor is easy to be affected by the electromagnetic induction concerning the structure; in case that you are worried about the electromagnetic   

interference, please consult us.     

Be sure to perform operation confirmation after the installing has been carried out.   
When there is dirt on the shell and the case body, please use soft rag such as the gauze with neutral detergent diluted by water to wipe them gently.     

Specifications

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Important Safety Instructions! 

 

       

                 

        Caution Label 

         

                   

Precautions 

□Carry out installation or wiring following the method instructed in the operation manual.   

       

□Conduct maintenance and periodic inspection following the method instructed in the operation manual.   

□Confirm the rated voltage and supply voltage before installing the detector.   

       

□Never soak it in water!     

□Do not install the detector    in places with high temperature and high humidity.   

□When assembling to the machine for use, don’t install in any locations easily accessible to the general public.    

       

□Avoid using the detector in any location subject to excessively dusty environment. 

□Avoid using the detector in any location close to sources of vibration, organic gas or strong electromagnetic induction.       

□When  performing  maintenance  on  this  detector,  don’t  use  solvents  such  as  alcohol,  toluene  and  diluents,  etc.  □  Never  modify  or  disassemble  the     

detector. 

 

       

□Do not use the sensor as the electric wire! 

□Please contact us in case of any failure.   

Customer Consultation

 

 

Shanghai Representative Office: Room B28/F, Huadu Mansion, No.838 Zhang Yang Road, Pudong, Shanghai   

 

ZIP 200122 

 

TATSUTA Electric Wire & Cable Co., Ltd. 

 

Tel

0086-21-5058-5177

   

Fax

0086-21-5058-5199 

    Headquarter:

  〒

578-8585                                                                           

     

Tokyo Branch:

  〒

210-0015     

2-3-1, Iwata-cho, Higashi-Osaka City, Osaka Prefecture                       

     

3rd floor, Nihon-Seimei Kawasaki Bldg., 1-1, Minami-machi,                                                                                                             

                                                                                                                         

     

Kawasaki Ward, Kawasaki City, Kanagawa Prefecture   

  Tatsuta Electric Wire & Cable Co., Ltd. System Electronics Division

         

Tatsuta Electric Wire & Cable Co., Ltd. System Electronics Division                                                         

 

System Department System Division                                                       

     

  System Department, Sales Division 

 

  Tel 

0081-6-6721-3335      Fax 

0081-6-6725-0018 

                     

Tel

  :

0081-044-221-7691        Fax 

0081-44-221-7695 

 

                             

No

1CSRAC-1004-0 

Item 

Specifications 

Power source 

AC100V/200V

 

±10% 

common to 50Hz/60Hz 

 

Sensor electrode voltage  

AC5.5V (maximum value) 

Water leakage detection level 

Switched to three sections: L: 0.5MΩ,M

1.0MΩ

H

2.0MΩ, respectively ±20% 

Power/contact delay 

Power ON/ change of non-voltage output: 120mS or less 
Power OFF/change of non-voltage contact output: 300mS±20% 

Power consumption 

2VA or less   

Indicator LED 

Dual purpose for power source/water leakage and break alarming (lighting up 
once  during  water  leakage  detection  and  lighting  up  twice  during  break 
detection)   

 
No-voltage contact 

1 group of 1a and 1c respectively 
 

Rated load 

 

Resistive load 
AC125V

 

0.5A 

DC30V

 

2A 

   

Cautions

 

 

■To avoid the occurrence of fault

!     

 

Do not touch the detector with wet hands 

Do not insert foreign substances inside the detector 
from the gap 

Carry out the maintenance and regular check under 

the instructions of operators or instructiona manual. 

About Caution Mark 

Erroneous operation of this water leakage detector not complying with the caution mark 

or the following cautions may not only lead to possible fatality or serious injury, but also 
fire, electric shock or detector failure may occur.   

Be sure to read the cautions and this instruction manual carefully. 

Отзывы: