The sensor is easy to be affected by the electromagnetic induction concerning the structure; in case that you are worried about the electromagnetic
interference, please consult us.
Be sure to perform operation confirmation after the installing has been carried out.
When there is dirt on the shell and the case body, please use soft rag such as the gauze with neutral detergent diluted by water to wipe them gently.
Specifications
Important Safety Instructions!
Caution Label
Precautions
□Carry out installation or wiring following the method instructed in the operation manual.
□Conduct maintenance and periodic inspection following the method instructed in the operation manual.
□Confirm the rated voltage and supply voltage before installing the detector.
□Never soak it in water!
□Do not install the detector in places with high temperature and high humidity.
□When assembling to the machine for use, don’t install in any locations easily accessible to the general public.
□Avoid using the detector in any location subject to excessively dusty environment.
□Avoid using the detector in any location close to sources of vibration, organic gas or strong electromagnetic induction.
□When performing maintenance on this detector, don’t use solvents such as alcohol, toluene and diluents, etc. □ Never modify or disassemble the
detector.
□Do not use the sensor as the electric wire!
□Please contact us in case of any failure.
Customer Consultation
Shanghai Representative Office: Room B28/F, Huadu Mansion, No.838 Zhang Yang Road, Pudong, Shanghai
ZIP 200122
TATSUTA Electric Wire & Cable Co., Ltd.
Tel
:
0086-21-5058-5177
Fax
:
0086-21-5058-5199
Headquarter:
〒
578-8585
Tokyo Branch:
〒
210-0015
2-3-1, Iwata-cho, Higashi-Osaka City, Osaka Prefecture
3rd floor, Nihon-Seimei Kawasaki Bldg., 1-1, Minami-machi,
Kawasaki Ward, Kawasaki City, Kanagawa Prefecture
Tatsuta Electric Wire & Cable Co., Ltd. System Electronics Division
Tatsuta Electric Wire & Cable Co., Ltd. System Electronics Division
System Department System Division
System Department, Sales Division
Tel
:
0081-6-6721-3335 Fax
:
0081-6-6725-0018
Tel
:
0081-044-221-7691 Fax
:
0081-44-221-7695
No
.
1CSRAC-1004-0
Item
Specifications
Power source
AC100V/200V
±10%
(
common to 50Hz/60Hz
)
Sensor electrode voltage
AC5.5V (maximum value)
Water leakage detection level
Switched to three sections: L: 0.5MΩ,M
:
1.0MΩ
,
H
:
2.0MΩ, respectively ±20%
Power/contact delay
Power ON/ change of non-voltage output: 120mS or less
Power OFF/change of non-voltage contact output: 300mS±20%
Power consumption
2VA or less
Indicator LED
Dual purpose for power source/water leakage and break alarming (lighting up
once during water leakage detection and lighting up twice during break
detection)
No-voltage contact
1 group of 1a and 1c respectively
Rated load
Resistive load
AC125V
0.5A
DC30V
2A
Cautions
■To avoid the occurrence of fault
!
*
Do not touch the detector with wet hands
*
Do not insert foreign substances inside the detector
from the gap
*
Carry out the maintenance and regular check under
the instructions of operators or instructiona manual.
About Caution Mark
Erroneous operation of this water leakage detector not complying with the caution mark
or the following cautions may not only lead to possible fatality or serious injury, but also
fire, electric shock or detector failure may occur.
Be sure to read the cautions and this instruction manual carefully.